Comment Response Sheet

Customer RADIANT UTAMA INTERINSCO TBK. Document Title GENERAL ARRANGEMENT DRAWING FOR LIQUID-
LIQUID SEPARATOR VESSEL
Project Title MELIWIS DEVELOPMENT PROJECT Document No. P7098T-A-TD05-7001
Project No. P7098T Rev. No. A Sheet of
Except for the following identified comments, all other comments on this document have been resolved.

No. Section Comment Response By Date Status Remarks


O/C *

1 Confirm PNT 09-Apr-19

Refer to General Arrangement Drawing


2 For Liquid-Liquid Separator Vessel PNT 09-Apr-19
Rev.B Update.

Page 1 of 5
Comment Response Sheet

No. Section Comment Response By Date Status Remarks


O/C *

Refer to General Arrangement Drawing


3 For Liquid-Liquid Separator Vessel PNT 09-Apr-19
Rev.B Update.

Refer to General Arrangement Drawing


4 For Liquid-Liquid Separator Vessel PNT 09-Apr-19
Rev.B Update.

Refer to General Arrangement Drawing


For Liquid-Liquid Separator Vessel
5 PNT 09-Apr-19
Rev.B Update.

Page 2 of 5
Comment Response Sheet

No. Section Comment Response By Date Status Remarks


O/C *

Refer to Detail Drawing For Liquid-Liquid


6 Separator Vessel Rev.A . To be provided PNT 09-Apr-19
later.

Refer to General Arrangement Drawing


7 For Liquid-Liquid Separator Vessel PNT 09-Apr-19
Rev.B Update.

Page 3 of 5
Comment Response Sheet

No. Section Comment Response By Date Status Remarks


O/C *

Refer to General Arrangement Drawing


8 For Liquid-Liquid Separator Vessel PNT 09-Apr-19
Rev.B Update.

Refer to General Arrangement Drawing


For Liquid-Liquid Separator Vessel
Rev.B Update.
We have some changes compared to
RUI's drawing (dwg. no.: 9702-030-
GAR-1001-Rev.G1) to match the
process:
- N9, N11: As per Client “Dwg. no.:
9 9702-030-GAR-1001-Rev.G1”, N9 and PNT 09-Apr-19
N11 nozzle are located at 1000mm from
bottom tangent line. When liquid level
increases to LAH level (1050) and over,
the pressure transmitters are submerged
in liquid, this cause PIT measure both
tank pressure and hydrostatic pressure.
=> Move N9 and N11 to the top of tank

Page 4 of 5
Comment Response Sheet

No. Section Comment Response By Date Status Remarks


O/C *

- N14 should be moved to the lowest


temperature zone. If N14 is located near
the heater, the remote zone's
temperature may be lower than the
required temperature.
- N15 is located at 250 mm from bottom
tangent line. When liquid level
decreases from LAL (300mm) to LALL
(130mm), TIT doesn't contact with liquid.
So it doesn't measure the temperature
of the liquid and may cause a false
temperature alarm.
==> move N15 to 130 mm from the
bottom tangent line.
- The orther nozzles vendor still
elevation, but move to new position for
easy in installation and maintenance.

Additional Notes (if


any)
DISTRIBUTION
* O - Open, C – Closed

Page 5 of 5