You are on page 1of 5

Design calculation sheet

Project no.: Date: 12-Jun-03 Sheet No.: 1 of 1 Computed by: H.M.

Subject: Design of Chimneys Checked by:

Building: Approved by:

Theoretical Draft of Chimney


Altitude Correction
Barometric
Draft per Meter Height Correction
Temperature Rise (K) Altitude (m) Pressure
(Pa) Factor
(Kpa)
60 2 Sea Level 101.325 1
100 3 600 94.41 1.08
150 4 1000 89.87 1.13
200 5 2000 79.5 1.27
300 6
400 7 Type of system Resistance Loss Factor
600 8 Single Boiler 1
900 9 Combined vents 1.5

Mean Temperature in
Fuel Appliance % CO2 Temperature Rise (K) Mass Flow/Input Ratio (Kg/MJ)
Chimney (°C)

Natural Gas Draft Hood 5.3 165 180 0.661

Propane Gas Draft Hood 6 165 180 0.683

Natural Gas Low No Draft


8 220 240 0.454
Efficiency Hood
Natural Gas High No Draft
7 135 150 0.512
Efficiency Hood

No. 2 Oil Residential 9 280 290 0.533

Forced
Oil Draft Over 13.5 165 290 0.368
120 KW

Chimney Sizing

Type of Fuel: No. 2 Oil First Iteration


% CO2 9 f (mm) 176.72
Input Load (KW) 160

Mass Flow/Input Ratio (Kg/MJ) 0.533 Second Iteration

Mean Temperature (°C) 240 f (mm) 170.8123


Temperature Rise (DTK) 210
Chimney Height (m) 10 Third Iteration
Total Piping (m) 14 f (mm) 171.6901
Barometric Pressure (Pa) 101325
Draft per Meter Height (pa) 4.4 Fourth Iteration
Available Draft (pa) 0 f (mm) 171.5567
Altitude Correction Factor 1
Resistance Loss Factor 1 Fifth Iteration
Round Elbow (90°) 0 f (mm) 171.5769
Round Elbow (45°) 0
Tee or 90° Connector 1 Sixth Iteration
Y-Connector 0 f (mm) 171.5738
Cap Top 1
Final Chimney Size
f (mm) 180.0
Design calculation sheet
Project no.: Date: 12-Jun-03 Sheet No.: 1 of 1 Computed by: H.M.

Subject: Design of Chimneys Checked by:

Building: Approved by:

Theoretical Draft of Chimney


Altitude Correction
Draft per Meter Height Barometric Correction
Temperature Rise (K) Altitude (m)
(Pa) Pressure (Kpa) Factor

60 2 Sea Level 101.325 1


100 3 600 94.41 1.08
150 4 1000 89.87 1.13
200 5 2000 79.5 1.27
300 6
400 7 Type of system Resistance Loss Factor
600 8 Single Boiler 1
900 9 Combined vents 1.5

Mean Temperature in Chimney Mass Flow/Input Ratio


Fuel Appliance % CO2 Temperature Rise (K)
(°C) (Kg/MJ)

Natural Gas Draft Hood 5.3 165 180 0.661

Propane Gas Draft Hood 6 165 180 0.683

Natural Gas
No Draft Hood 8 220 240 0.454
Low Efficiency
Natural Gas
No Draft Hood 7 135 150 0.512
High Efficiency

No. 2 Oil Residential 9 280 290 0.533

Forced Draft Over


Oil 13.5 165 290 0.368
120 KW

Design of Chimneys

Type of Fuel: No. 2 Oil Chimney Height (m) 62 Resistance Loss Factor 1.5
% CO2 9 Barometric Pressure (Pa) 101325 Round Elbow (90) 2
Input Load (KW) 1570 Altitude Correction Factor 1 Round Elbow (45) 0
Mass Flow/Input Ratio (Kg/MJ) 0.533 Draft per Meter Height (pa) 6 Tee or 90 Conncetor 1
Mean Temperature (°C) 290 Available Draft (pa) 0 Y Connector 1
Temperature Rise ( DTK) 280 Total Piping (m) 100 Cap Top 2

First Iteration Second Iteration Third Iteration Fourth Iteration Fifth Iteration Sixth Iteration

f (mm) 367.72 f (mm) 471.1435 f (mm) 452.8895 f (mm) 455.6427 f (mm) 455.2166 f (mm) 455.2823

Final Chimney Size


f (mm) 500.0
TIRO NATURAL
Densidad de aire 1.2 kg/m3
Densidad de humos 0.75 kg/m3
Altura eficaz 8 m
Gravedad 9.81 m/s

tiro natural 35.316 Pa

Caudal de humos 759 m3/hr


8.80% 825.8 m3/hr

Presion Residual 90 Pa

Caudal max de Gas potencia 31 m3/hr