Mean Temperature in
Fuel Appliance % CO2 Temperature Rise (K) Mass Flow/Input Ratio (Kg/MJ)
Chimney (°C)
Forced
Oil Draft Over 13.5 165 290 0.368
120 KW
Chimney Sizing
Natural Gas
No Draft Hood 8 220 240 0.454
Low Efficiency
Natural Gas
No Draft Hood 7 135 150 0.512
High Efficiency
Design of Chimneys
Type of Fuel: No. 2 Oil Chimney Height (m) 62 Resistance Loss Factor 1.5
% CO2 9 Barometric Pressure (Pa) 101325 Round Elbow (90) 2
Input Load (KW) 1570 Altitude Correction Factor 1 Round Elbow (45) 0
Mass Flow/Input Ratio (Kg/MJ) 0.533 Draft per Meter Height (pa) 6 Tee or 90 Conncetor 1
Mean Temperature (°C) 290 Available Draft (pa) 0 Y Connector 1
Temperature Rise ( DTK) 280 Total Piping (m) 100 Cap Top 2
First Iteration Second Iteration Third Iteration Fourth Iteration Fifth Iteration Sixth Iteration
f (mm) 367.72 f (mm) 471.1435 f (mm) 452.8895 f (mm) 455.6427 f (mm) 455.2166 f (mm) 455.2823
Presion Residual 90 Pa