Ordering Guide Accuracy EMC Compatibility Device Dimensions

Product Code Description Unit: mm


iMeter 8 Advanced Power Quality Analyzer Parameters Accuracy Resolution Power Supply (L+, N-) CE EMC Directive 2014/30/EU (EN61326: 2013)
A 1024 samples/cycle, 8GB On-Board Memory, IEC61000-4-30 Ed. 3 Class A Compliant Voltage (U) ±0.1% 0.001V Standard 95-250VAC/VDC ± 10%, 47-440Hz
Basic Feature ±0.1% Burden < 12W Immunity (EN50082-2)
1024 samples/cycle, 8GB On-Board Memory,
B*~ I1, I2, I3
IEC61000-4-30 Ed. 3 Class A Compliant with 2-150kHz C.E. Measurement SCCPA Option: ±01%+Error of SCCP Overvoltage Category CATIII 300V Electrostatic Discharge EN61000-4-2: 2009
0.001A
5 5A I4 ±0.1% Radiated Fields EN61000-4-3: 2006 +A1: 2008 +A2: 2010
Input Current 1 1A I5 ±0.5% Fast Transients EN61000-4-4: 2012
SCCPA^ SCCP Option for use with CT Clamps with max. 500mV output ±0.2% Surges EN61000-4-5: 2014 +A1: 2017
P, Q, S 0.001kX Digital Inputs ( DIC, DI1 to DI8 or DI16) Conducted Disturbances
VN

Input Voltage 9 400ULN/690ULL + 20% SCCPA Option: ±0.5% EN61000-4-6: 2014


V4

95-250VAC/DC ± 10%, 47-440Hz


Standard Dry contact, 24VDC internally wetted
Magnetic Fields EN61000-4-8: 2010
2 IEC62053-22 Class 0.2S V4N

Power Supply kWh, kVAh 0.1kXh Optional 110V/220V AC/DC externally wetted
3*# 20-60VDC SCCPA Option: IEC62053-21 Class 1 Voltage Dips and Interruptions EN61000-4-11: 2004+A1: 2017
50Hz
Sampling 1000Hz
Ring Wave EN61000-4-12: 2017
5 IEC62053-24 Class 0.5S
System Frequency kvarh IEC62053-23 Class 2 Hysteresis 1ms minimum
6 60Hz 0.1kvarh
A 8xDI + 4xDO + 4xSS Pulse Outputs SCCPA Option: IEC62053-24 Class 1 1

Emission (EN50081-2) 2

B*~ 8xDI + 4xDO + 2xAI + 1xAO + 4xSS Pulse Outputs ±0.2% 3

I/O PF 0.001
C* 16xDI + 8xDO + 4xSS Pulse Outputs SCCPA Option: ±0.5% Limits and Methods of Measurement of
Form A Relay Outputs (DO1 to DO3 or optional DO1 to DO7)
D*~ 8xDI + 4xDO + 2xAI + 2xAO + 2xSS Pulse Outputs Frequency ±0.003Hz 0.001Hz Electromagnetic Disturbance
Type Form A Mechanical Relay Characteristics of Industrial, Scientific EN55011: 2016
N Dry Contact (@24VDC Self-Excitation) Harmonics IEC61000-4-7 Class A 0.001
16xDI+8xDO+2xAI+1xAO
Loading 5A @ 250VAC/30VDC and Medical (ISM) Radio-Frequency
DI Excitation 1# 110V AC/DC External Excitation K-Factor IEC61000-4-7 Class A 0.001 Equipment
Rear Panel
2# 220V AC/DC External Excitation ±0.2°

Communications A 2x100BaseT + 2xRS-485 Phase Angle SCCPA Option: 0.1° Limits and Methods of Measurement of
±0.2°+ Phase Error of SCCP Radio Disturbance Characteristics of EN55032: 2015
Time Sync. A GPS, IRIG-B Form C Relay Outputs (Alarm 1, 2, 3) Information Technology Equipment
U Unbalance ±0.1% 0.01%
Display Language E English Type Form C Mechanical Relay
I Unbalance ±0.5% 0.01% Limits for Harmonic Current Emissions
iMeter 8 - A 5 9 2 5 A N A A E iMeter 8-A5925ANAAE (Standard Model) Loading 8A @ 250VAC/24VDC EN61000-3-2: 2014
Pst, Plt 0.01% for Equipment with Rated Current ≤16 A
±5%
* Additional charges apply.
~ The I/O options "B" and "D" are not supported when the Basic Feature option "B" is selected. Limitation of Voltage Fluctuations and
^ The SCCPA option is compatible with the SCCP models listed in the "SCCP Option" sheet. This option does not come with any Current Clamp. Flicker in Low-Voltage Supply Systems EN61000-3-3: 2013
Please refer to the "SCCP Option" sheet for more information and order the desired model and quantity as a separate item. for Equipment with Rated Current ≤16 A
#
The DI Excitation options “1” and “2” are not supported when the Power Supply option “3” with 20-60VDC is selected. Pulse Outputs (E1+, E1-, E2+, E2-, E3+, E3-, E4+, E4-)
Type Form A Solid State Relay Emission Standard for Industrial
EN61000-6-4: 2007 +A1: 2011

Optional SCCPs Technical Specifications Isolation


Max. Load Voltage
Optical
30VDC
Environments

Standards of Compliance
Max. Forward Current 4mA
Voltage Inputs (V1, V2, V3, VN, V4, V4N)
Standard (Un) 400ULN/690ULL +20%
Range 1% to 200% Un for 400ULN nominal Safety Requirements
* PMC-SCCP-5kA-500mV-B-C-C- Overload 2xUn continuous, 4xUn for 1s Optional Analog Input (AI1+, AI1-, AI2+, AI2-)
Model No. PMC-SCCP-50A-500mV-B-A-B PMC-SCCP-200A-200mV-B-B-B PMC-SCCP-500A-500mV-B-B-B EN61010-1: 2010
CE LVD 2014/35/EU

iMeter 8
371/254/150/100
Burden < 0.5VA/per phase Type 0-20/4-20 mA DC EN61010-2-030: 2010
5A 20A/200A 500A 500A/5000A Rogowski Coil
Measurement Range Primary 1-1,000,000V Overload 24 mA maximum
(50A Imax) (200A Imax) (500A Imax) (5000A Imax) Electrical Safety in Low Voltage
Secondary 1-1,500V Distribution Systems up to 1000Vac IEC61557-12: 2018 (PMD)
Max. Allowable Current 50A 260A 500A 10, 000A PT Ratio
AC 10mV/A @ 20A AC 1mV/A @ 500A
V4 Primary 1-1,000,000V and 1500Vdc Side view
AC 10mV/A AC 1mV/A V4 Secondary 1-1,500V
Output Voltage AC 1mV/A @ 200A AC 0.1mV/A @ 5000A
(Max. 500mV) (Max. 500mV) Insulation
(Max. 200mV) (Max. 500mV) Frequency 40Hz-60Hz @ 50Hz, 48Hz-72Hz @ 60Hz Optional Analog Output (AO1+, AO1-, AO2+, AO2-) IEC62052-11: 2003
AC Voltage: 2kV @ 1 minute
±0.3% rdg. ±0.3% rdg. ±0.3% rdg. ±2.0% rdg. IEC62053-22: 2003
Accuracy Type 0-20/4-20 mA DC Insulation Resistance: >100MΩ
±0.02% f.s. ±0.02% f.s. ±0.02% f.s. (1% - 200%) In EN61010-1: 2010
Loading 500Ω maximum Impulse Voltage: 6kV, 1.2/50µs
CAT III 1000V
Protection CAT III 300V CAT III 600V CAT III 600V Overload 24 mA maximum
CAT IV 600V Current Inputs (I11, I12, I21, I22, I31, I32, I41, I42, I51, I52)
Diameter 15mm 24mm 50mm 371/254/150/100mm
Standard (In) 5A (Standard), 1A (Optional) Mechanical Tests
Cable Length 3m 3m 3m 3m
Range 1% to 400% In Response IEC255-2-1: 1989
Termination BNC BNC BNC BNC Vibration Test
Starting Current 0.1% In Endurance IEC255-2-1: 1989
Environmental Conditions
* The Rogowski Coil SCCP comes with an external Universal Power Supply and an integrator. Overload 4xIn continuous, 20xIn for 1s Response IEC255-2-2
Operating Temperature -25°C to 70°C Shock Test
< 0.5VA/per phase @ 5A Endurance IEC255-2-2
Burden Storage Temperature -40°C to 85°C
< 0.1VA/per phase @ 1A Bump Test IEC255-2-2
Humidity 5% to 95% non-condensing
5A/50A (In/Imax),
SCCP-50A-500mV
Atmospheric Pressure
Your Local Representative

max. 500mV Output 63 kPa to 110 kPa

20A/200A (In/Imax), Pollution Degree 2 Power Quality


SCCP-200A-200mV
SCCP Options max. 200mV Output Measurement Category CATIII 1000V
Voltage Characteristics of Electricity Supplied
SCCP-500A-500mV 500A Imax, max. 500mV Output EN50160
by Public Distribution Systems
V.00 05.07.2022

Selectable 500A/5000A (Imax)


SCCP-5000A-500mV General Guide on Harmonic and Interharmonic
Rogowski Coil, max. 500mV Output
Measurements and Instrumentation, for Power IEC61000-4-7
Primary 1-30,000A Mechanical Characteristics Supply Systems and Equipment Connected Thereto
Email: sales@cet-global.com
Secondary 1-50A
Website: www.cet-global.com CT Ratio Panel Cutout 186x186 mm Flicker Meter - Functional and Design Specifications IEC61000-4-15
I4 Primary 1-30,000A
Unit Dimensions 192x192x182.4mm Testing and Measurement Techniques-Power IEC61000-4-30 Ed. 3
Copyright © CET Inc. All rights reserved.
I4 Secondary 1-50A
IP Rating 52 Quality Measurement Methods Class A Compliant Installation
www.cet-global.com
Sequence and Unbalance iTrigger Statistical Data Recorder (SDR)
The iMeter 8 is CET’s Advanced PQ Analyzer designed for the Multi-Tariff TOU Capability ● Zero, Positive and Negative Sequence Components ● Ability to cross-trigger WFR, DWR, RMSR and DO between ● 16 SDR Logs of maximum 64 parameters each
compliance monitoring market as it offers un-surpassed func- ● U and I Unbalance based on Zero and Negative Sequence iTrigger-enabled devices over a network connection ● Recording of the Max., Min., Avg. and CP95 for Real-time
● Two independent sets of TOU Schedules, each supporting Components Programmable via Web Interface or Communications Measurements including U, I, P, Q, S, PF, Freq., Power, PF,
tionality by combining Class 0.2S accuracy and advanced PQ


Up to 12 Seasons Dips, Swells & Interruptions and Transients Recording Harmonics, Deviations and Unbalances
features in a 192x192x182.4mm housing with a High-Resolution, ●
90 Holidays or Alternate Days and 3 Weekdays ● Transients capture as short as 20us at 1024 samples @ 50Hz for Data and Event Recorders ● Recording interval from 0 to 60 minutes
Color Dot-Matrix LCD display. The iMeter 8 complies with such ●
20 Daily Profiles, each with 12 Periods at min. 15-minute interval sub-cycle disturbance such as capacitor switching and resonance
● 30 days @ 1-minute, 300 days @ 10-minute, 450-day @ 15-minute
8 Tariffs, each providing the following information: Non-Volatile Log Memory ● PQDIF file format, downloadable from the on-board FTP Server
standards as IEC62053-22 Class 0.2S, IEC61000-4-30 Ed. 3

phenomena
kWh/kvarh Import/Export and kVAh

● 8GB on-board non-volatile Log Memory ● Support FIFO or Stop-When-Full mode
● Dips, Swells & Interruptions detection @ 10ms (½ cycle at 50Hz)
Class A Compliant, IEC61000-4-15, IEC61000-4-7, EN50160 as P & Q Import/Export Maximum Demands with timestamp Interval Energy Recorder (IER) and Accumulative Energy
Max./Min. Recorder (MMR)

● Trigger for DO, WF Recording, Disturbance Waveform Recording, Recorder (AER)
well as IEC61850 for Substation Automation. Further, it offers a Register rollover at 100,000,000,000 kXh

RMS Recording and Alarm Email ● 4 Max./Min. Recorders of 20 parameters each
● Both IER Log and AER Log support recording of Total RMS
● 12 Historical Logs for Energy and Maximum Demand RMS/Fundamental/Harmonic/Interharmonic Measurements,
large logging capacity with 8GB of on-board memory, extensive ● Display of ITIC, SEMI F47 and RMSR (RMS Recording) as well as kWh, kvarh Import/Export/Total/Net and kVAh, Total

Demands, Deviations, Unbalances and Flicker


I/O, multiple Time Sync. methods, 2x100BaseT Ethernet and the Event Waveform on the Front Panel and Web Interface Fundamental and Total Harmonic kWh, kvarh Import/Export Setpoints Communications
2xRS-485 ports. In addition, it optionally provides 2xAO and 2xAI Power Quality Features Rapid Voltage Changes (RVC) ● Recording Interval from 1 to 65535 minutes
● Two transfer modes:

Manual: Max./Min. Since Last Reset & Before Last Reset
● Detection of a quick transition in RMS voltage between two ● Maximum Recording Depth @ 65535 records PQ Setpoints Ethernet Ports (P1, P2)
for different applications. These features likely make the iMeter 8 ●
Auto: Max./Min. of This Month & Last Month
● IEC61000-4-30 Ed. 3 Class A Compliant steady-states voltage conditions ● Support FIFO and Stop-When-Full modes ● Transients, Dips, Swells, Interruptions ● Dual 10/100BaseT Ethernet Ports with RJ45 connector
one of the most advanced PQ Analyzer for an intelligent Power IEC61000-4-15, IEC61000-4-7 Compliance Device Log SOE Log

Inrush Current Monitoring ● Rapid Voltage Changes ● Protocols supported: Modbus TCP, HTTPS, SNTP, SMTP, FTP
● 2kHz to 150kHz Conducted Emission Measurements ● 1024 FIFO entries time-stamped to ±1ms resolution ● 1024 FIFO events time-stamped to ±1ms resolution Inrush Current
Quality Monitoring System. ● Monitoring of the ½ cycle RMS Current and capturing of the ● and IEC61850
● Disturbance Direction Indicator ● Power On/Off Records, Setup changes, Time Sync., ● Setpoint events, I/O operations, Dips, Swells, Interruptions, Trigger DO, WFR, DWR, RMSR or Alarm Email
Current waveforms associated with events such as motor ● ● Built-in password protected Web Server for easy data viewing,
● Disturbance Waveform Recording Device Operations and Self-diagnostics Transients, Rapid Voltage Changes, Inrush Current, Mains Signalling
starting and transformer being energized setup configuration and firmware upgrade
RMS Recording and EN50160 Reporting Voltages, Motor Start, etc. Control Setpoints
● Data Recorder (DR) Log Simultaneous client connections for 12xModbus TCP
● PQ Monitoring at HV, MV and LV Utility Substations Disturbance Direction Indicator Record the time and characteristic data of the Setpoint and PQ event ● 256 standard and 16 High-Speed Setpoints

● Fault Capture up to 2,000V peak to peak ● 8 Standard DR Logs ●
& 12xIEC61850
● Data Centers, Semiconductor Fabs, Heavy Industries ● Determine if a Dip Event is located upstream or downstream ● Extensive monitoring sources including U, I, P, Q, S, Demand,
● Waveform Recording in COMTRADE and PQDIF file format ● Recording Interval from 1s to 40 days for Standard DR Log
7x24 Automated Manufacturing Facilities (Compatible with the PQ View software)
● Pinpoint if the cause of the event is external or internal
Time Synchronization Harmonics, Unbalances, Deviations, Flickers, Phase
Typical Up to 64 Parameters for each DR Log with programmable RS-485
● ●

Real-Time Waveform Capture (WFC) and Waveform Recorder (WFR) Reversal/Loss, AI, etc. Dual optically isolated RS-485 port with baud rate from 1.2 to
sources such as Real-time Measurements, Harmonics, ●
● Dips, Swells, Interruptions, Transients, Flickers & Harmonics Monitoring Real-time WFC @ 128 samples/cyclex4 cycles via Front Panel ● Battery-backed Real-time clock @ 6ppm (≤0.5s/day) ● Configurable thresholds and time delays
Power Quality Metering Unbalance and Demand Measurements 38.4kbps

Applications ● Mains and Critical Feeder Monitoring and Web Interface ● Configurable Depth and Recording Offset
● Time Sync. via Modbus RTU/TCP, SNTP, IEEE1588 (PTP) ● Trigger DO, DR, WFR, DWR, RMSR or Alarm Email ● Support Modbus RTU and Ethernet Gateway
WFR with maximum 128 entries ● Optional GPS/IRIG-B Input
● IEC61850 support for Substation Automation and Smart Grid PQ Parameters as per IEC61000-4-30 Ed. 3 Class A Compliant
● ● Support FIFO or Stop-When-Full recording modes
Digital Input Setpoints
● Simultaneous capture of 3-phase Voltage and Current Inputs
● Retrofit Applications with Split-Core Current Probe (SCCP) ● Power Frequency
● No. of CyclesxSamples/Cycles with programmable pre-fault
● Provides control output actions in response to changes in
Magnitude of the Supply Voltage and Current Digital Input status
System Integration

cycles: 400x1024, 800x512, 1600x256, 3200x128
● Flicker ● Trigger DO, DR, WFR, DWR, RMSR or Alarm Email
● Scheduled WFR with maximum repetition of 10,000 times and
● Transients, Dips/Swells and Interruptions
programmable schedule from 1 to 1440 mins
Supply Voltage Unbalance and Current Unbalance PecStar® iEMS
Basic Features Metering

COMTRADE file format, downloadable from the on-board
Inputs and Outputs

● Mains Signalling Voltage on the Supply Voltage ● The iMeter 8 is supported by CET’s PecStar® iEMS
Web Server or FTP Server
● Rapid Voltage Changes ● In addition, the iMeter 8 can be easily integrated into other 3rd
● IEC62053-22 Class 0.2S kWh metering with Multi-Tariff TOU Basic Measurements (1-second update) ● Measurement of Over and Under Deviation parameters Disturbance Waveform Recorder (DWR) party systems because of its support of multiple communications
Digital Inputs
● True RMS @ 1024 samples/cycle sampling ● 3-phase U, I, P, Q, S, and PF as well as U4, I4 and I5 ● Harmonic and Interharmonics Measurements for Voltage ● 128 entries ports as well as different industry standard protocols such as
● Standard 8 or optional 16 channels
● 8GB on-board log memory ● kWh, kvarh Import/Export/Net/Total and kVAh Total and Current ● Simultaneous recording of all Voltage (U1-U4) and Current (I1-I5) Modbus and IEC61850
● Standard volt free dry contact with 24VDC Internal Excitation
● 7” High-Resolution Color Dot-Matrix Display @ 800x480 ● Frequency ● 2 to 150kHz Conducted Emission Measurements Inputs
● Optional 110VAC/DC or 220VAC/DC External Excitation DiagSys
● Time Sync. via SNTP, IEEE 1588 (PTP), IRIG-B or GPS 1PPS output ●
Initial Fault: 35 cycles @ 512 samples/cycle
Harmonic and Interharmonic Measurements ● 1000Hz sampling for status monitoring with programmable
● 256 Standard Setpoints and 16 High-Speed Setpoints ●
Extended Fault: Up to 150 cycles @ 16 samples/cycle
● Display of Real-time Measurements, PQ Events, Waveforms and
High-Speed Measurements
● K-Factor for Current, Crest Factor for Current and Voltage debounce Statistical Trend Charts
● Dual 100BaseT Ethernet and two RS-485 ports ●
Steady State: Up to 360s of 1-cycle absolute peak values
● U and I THD, TOHD, TEHD, TIHD, TOIHD, TEIHD and TH (RMS) ● External status monitoring with programmable debounce Export of IER, AER and SDR Logs as well as EN50160 Reports
● 3-phase U, I, P, Q, S, and PF as well as U4, I4 and I5 @ ½ cycle ●
Post Fault: 15 cycles @ 512 samples/cycle

● U and I Individual Harmonics (%HD and RMS) from 2nd to 63rd # ● Pulse counting with programmable weight for each channel for Generation and Export of Self-defined PQ Analysis Reports
● Frequency @ 1 cycle ●
● U and I Individual Interharmonics (%IHD and RMS) from 1st to 63rd # RMS Recorder (RMSR) collecting WAGES (Water, Air, Gas, Electricity, Steam) information
Display & Web Servers ● Total Harmonic P, Q, S and PF ● 128 entries ● Demand Synchronization and Tariff Switch based on DI Status 3rd Party System Integration
Demands ● Harmonic P, Q, S and PF from 2nd to 63rd in RMS ● 16 parameters maximum, selectable U, I, P, Q, S, PF, Frequency, ● Easy integration into Substation Automation or Utility SCADA
Freq. Deviation Digital Outputs systems via Modbus RTU, Modbus TCP or IEC61850
● True RMS Real-time, Harmonics, Power and Energy Measurements ● Present and Predicted Demand for 3-phase U, I, P, Q, S, and PF ● Harmonic Phase Angle from 2nd to 63rd #
Recording Interval from 0.5 to 60 cycles
● Standard 4 or optional 8 channels Form A Mechanical Relays for The on-board, password-protected Web Server provides
● Demands and Multi-Tariff TOU as well as U4, I4, I5, Frequency ● U and I DC Components ● ●

Recording Depth @ 7200 samples per parameter general purpose control or alarming user-friendly access to its data and supports the configuration for
● Max. & Min. Logs ● Present Demand of 4-phase U & I THD/TOHD/TEHD, 4-phase ● Total Harmonic kWh, kvarh Import/Export/Net/Total ●

Configurable pre-fault samples from 100 to 500


● Standard 4 SS Relays for Energy pulsing applications most Setup parameters via a web browser without the use of
● Sequence & Unbalance Current K-Factor, U/I Unbalance, Over & Under Deviation of ● Total Harmonic kWh, kvarh Import/Export from 2nd to 63rd ●

● Real-time WF Capture of 3-phase Voltages and Currents Voltage and Frequency, 4-phase Fundamental Current
#
%HD and %IHD can be configured as % of Fundamental, % of U/I nominal or % of RMS ● 72 seconds of ½ cycle RMS Recording @ 50Hz or 60 seconds @ 60 Hz Analog Inputs (Optional) proprietary software
● Event Waveforms and ITIC/SEMI F47 Curves ● Max./Min. values per Demand Interval Conducted Emissions in the 2kHz to 150kHz range ● Display of Ua/Ub/Uc/Uab/Ubc/Uca/Ia/Ib/Ic RMSR on the Web Interface ● Two channels 0/4-20mA DC input with programmable zero and
● The on-board, password protected FTP Server allows logged data
● Harmonics & Interharmonics Histogram and Phasor diagrams ● Maximum Demands for This Month & Last Month (or Since ● Real-time amplitude (150/180-Cycle) and the Max., Min., Avg. PQ Event Counters full scales that can be used to measure external transducer signal in CSV format and waveform records in PQDIF or COMTRADE
● Device and SOE Logs, PQ Counters and I/O Status Last Reset & Before Last Reset) and CP95 (in 1-minute interval) for a total of 106 frequency ● Dips, Swells, Interruptions, Transients, Rapid Voltage Changes, format to be downloaded without any special software. The
Analog Output (Optional) downloaded files can be subsequently viewed using software that
● Device Configuration and Diagnostics ● Demand Synchronization with DI segments for the 2-9kHz (Urms and Irms) and 9-150kHz (Urms) range Inrush Current, Mains Signalling Voltages and Total PQ Event Counters
● One or two channels 0/4-20mA DC output with programmable supports the industry standard PQDIF and COMTRADE file formats
zero and full scales
Sequence and Unbalance iTrigger Statistical Data Recorder (SDR)
The iMeter 8 is CET’s Advanced PQ Analyzer designed for the Multi-Tariff TOU Capability ● Zero, Positive and Negative Sequence Components ● Ability to cross-trigger WFR, DWR, RMSR and DO between ● 16 SDR Logs of maximum 64 parameters each
compliance monitoring market as it offers un-surpassed func- ● U and I Unbalance based on Zero and Negative Sequence iTrigger-enabled devices over a network connection ● Recording of the Max., Min., Avg. and CP95 for Real-time
● Two independent sets of TOU Schedules, each supporting Components Programmable via Web Interface or Communications Measurements including U, I, P, Q, S, PF, Freq., Power, PF,
tionality by combining Class 0.2S accuracy and advanced PQ


Up to 12 Seasons Dips, Swells & Interruptions and Transients Recording Harmonics, Deviations and Unbalances
features in a 192x192x182.4mm housing with a High-Resolution, ●
90 Holidays or Alternate Days and 3 Weekdays ● Transients capture as short as 20us at 1024 samples @ 50Hz for Data and Event Recorders ● Recording interval from 0 to 60 minutes
Color Dot-Matrix LCD display. The iMeter 8 complies with such ●
20 Daily Profiles, each with 12 Periods at min. 15-minute interval sub-cycle disturbance such as capacitor switching and resonance
● 30 days @ 1-minute, 300 days @ 10-minute, 450-day @ 15-minute
8 Tariffs, each providing the following information: Non-Volatile Log Memory ● PQDIF file format, downloadable from the on-board FTP Server
standards as IEC62053-22 Class 0.2S, IEC61000-4-30 Ed. 3

phenomena
kWh/kvarh Import/Export and kVAh

● 8GB on-board non-volatile Log Memory ● Support FIFO or Stop-When-Full mode
● Dips, Swells & Interruptions detection @ 10ms (½ cycle at 50Hz)
Class A Compliant, IEC61000-4-15, IEC61000-4-7, EN50160 as P & Q Import/Export Maximum Demands with timestamp Interval Energy Recorder (IER) and Accumulative Energy
Max./Min. Recorder (MMR)

● Trigger for DO, WF Recording, Disturbance Waveform Recording, Recorder (AER)
well as IEC61850 for Substation Automation. Further, it offers a Register rollover at 100,000,000,000 kXh

RMS Recording and Alarm Email ● 4 Max./Min. Recorders of 20 parameters each
● Both IER Log and AER Log support recording of Total RMS
● 12 Historical Logs for Energy and Maximum Demand RMS/Fundamental/Harmonic/Interharmonic Measurements,
large logging capacity with 8GB of on-board memory, extensive ● Display of ITIC, SEMI F47 and RMSR (RMS Recording) as well as kWh, kvarh Import/Export/Total/Net and kVAh, Total

Demands, Deviations, Unbalances and Flicker


I/O, multiple Time Sync. methods, 2x100BaseT Ethernet and the Event Waveform on the Front Panel and Web Interface Fundamental and Total Harmonic kWh, kvarh Import/Export Setpoints Communications
2xRS-485 ports. In addition, it optionally provides 2xAO and 2xAI Power Quality Features Rapid Voltage Changes (RVC) ● Recording Interval from 1 to 65535 minutes
● Two transfer modes:

Manual: Max./Min. Since Last Reset & Before Last Reset
● Detection of a quick transition in RMS voltage between two ● Maximum Recording Depth @ 65535 records PQ Setpoints Ethernet Ports (P1, P2)
for different applications. These features likely make the iMeter 8 ●
Auto: Max./Min. of This Month & Last Month
● IEC61000-4-30 Ed. 3 Class A Compliant steady-states voltage conditions ● Support FIFO and Stop-When-Full modes ● Transients, Dips, Swells, Interruptions ● Dual 10/100BaseT Ethernet Ports with RJ45 connector
one of the most advanced PQ Analyzer for an intelligent Power IEC61000-4-15, IEC61000-4-7 Compliance Device Log SOE Log

Inrush Current Monitoring ● Rapid Voltage Changes ● Protocols supported: Modbus TCP, HTTPS, SNTP, SMTP, FTP
● 2kHz to 150kHz Conducted Emission Measurements ● 1024 FIFO entries time-stamped to ±1ms resolution ● 1024 FIFO events time-stamped to ±1ms resolution Inrush Current
Quality Monitoring System. ● Monitoring of the ½ cycle RMS Current and capturing of the ● and IEC61850
● Disturbance Direction Indicator ● Power On/Off Records, Setup changes, Time Sync., ● Setpoint events, I/O operations, Dips, Swells, Interruptions, Trigger DO, WFR, DWR, RMSR or Alarm Email
Current waveforms associated with events such as motor ● ● Built-in password protected Web Server for easy data viewing,
● Disturbance Waveform Recording Device Operations and Self-diagnostics Transients, Rapid Voltage Changes, Inrush Current, Mains Signalling
starting and transformer being energized setup configuration and firmware upgrade
RMS Recording and EN50160 Reporting Voltages, Motor Start, etc. Control Setpoints
● Data Recorder (DR) Log Simultaneous client connections for 12xModbus TCP
● PQ Monitoring at HV, MV and LV Utility Substations Disturbance Direction Indicator Record the time and characteristic data of the Setpoint and PQ event ● 256 standard and 16 High-Speed Setpoints

● Fault Capture up to 2,000V peak to peak ● 8 Standard DR Logs ●
& 12xIEC61850
● Data Centers, Semiconductor Fabs, Heavy Industries ● Determine if a Dip Event is located upstream or downstream ● Extensive monitoring sources including U, I, P, Q, S, Demand,
● Waveform Recording in COMTRADE and PQDIF file format ● Recording Interval from 1s to 40 days for Standard DR Log
7x24 Automated Manufacturing Facilities (Compatible with the PQ View software)
● Pinpoint if the cause of the event is external or internal
Time Synchronization Harmonics, Unbalances, Deviations, Flickers, Phase
Typical Up to 64 Parameters for each DR Log with programmable RS-485
● ●

Real-Time Waveform Capture (WFC) and Waveform Recorder (WFR) Reversal/Loss, AI, etc. Dual optically isolated RS-485 port with baud rate from 1.2 to
sources such as Real-time Measurements, Harmonics, ●
● Dips, Swells, Interruptions, Transients, Flickers & Harmonics Monitoring Real-time WFC @ 128 samples/cyclex4 cycles via Front Panel ● Battery-backed Real-time clock @ 6ppm (≤0.5s/day) ● Configurable thresholds and time delays
Power Quality Metering Unbalance and Demand Measurements 38.4kbps

Applications ● Mains and Critical Feeder Monitoring and Web Interface ● Configurable Depth and Recording Offset
● Time Sync. via Modbus RTU/TCP, SNTP, IEEE1588 (PTP) ● Trigger DO, DR, WFR, DWR, RMSR or Alarm Email ● Support Modbus RTU and Ethernet Gateway
WFR with maximum 128 entries ● Optional GPS/IRIG-B Input
● IEC61850 support for Substation Automation and Smart Grid PQ Parameters as per IEC61000-4-30 Ed. 3 Class A Compliant
● ● Support FIFO or Stop-When-Full recording modes
Digital Input Setpoints
● Simultaneous capture of 3-phase Voltage and Current Inputs
● Retrofit Applications with Split-Core Current Probe (SCCP) ● Power Frequency
● No. of CyclesxSamples/Cycles with programmable pre-fault
● Provides control output actions in response to changes in
Magnitude of the Supply Voltage and Current Digital Input status
System Integration

cycles: 400x1024, 800x512, 1600x256, 3200x128
● Flicker ● Trigger DO, DR, WFR, DWR, RMSR or Alarm Email
● Scheduled WFR with maximum repetition of 10,000 times and
● Transients, Dips/Swells and Interruptions
programmable schedule from 1 to 1440 mins
Supply Voltage Unbalance and Current Unbalance PecStar® iEMS
Basic Features Metering

COMTRADE file format, downloadable from the on-board
Inputs and Outputs

● Mains Signalling Voltage on the Supply Voltage ● The iMeter 8 is supported by CET’s PecStar® iEMS
Web Server or FTP Server
● Rapid Voltage Changes ● In addition, the iMeter 8 can be easily integrated into other 3rd
● IEC62053-22 Class 0.2S kWh metering with Multi-Tariff TOU Basic Measurements (1-second update) ● Measurement of Over and Under Deviation parameters Disturbance Waveform Recorder (DWR) party systems because of its support of multiple communications
Digital Inputs
● True RMS @ 1024 samples/cycle sampling ● 3-phase U, I, P, Q, S, and PF as well as U4, I4 and I5 ● Harmonic and Interharmonics Measurements for Voltage ● 128 entries ports as well as different industry standard protocols such as
● Standard 8 or optional 16 channels
● 8GB on-board log memory ● kWh, kvarh Import/Export/Net/Total and kVAh Total and Current ● Simultaneous recording of all Voltage (U1-U4) and Current (I1-I5) Modbus and IEC61850
● Standard volt free dry contact with 24VDC Internal Excitation
● 7” High-Resolution Color Dot-Matrix Display @ 800x480 ● Frequency ● 2 to 150kHz Conducted Emission Measurements Inputs
● Optional 110VAC/DC or 220VAC/DC External Excitation DiagSys
● Time Sync. via SNTP, IEEE 1588 (PTP), IRIG-B or GPS 1PPS output ●
Initial Fault: 35 cycles @ 512 samples/cycle
Harmonic and Interharmonic Measurements ● 1000Hz sampling for status monitoring with programmable
● 256 Standard Setpoints and 16 High-Speed Setpoints ●
Extended Fault: Up to 150 cycles @ 16 samples/cycle
● Display of Real-time Measurements, PQ Events, Waveforms and
High-Speed Measurements
● K-Factor for Current, Crest Factor for Current and Voltage debounce Statistical Trend Charts
● Dual 100BaseT Ethernet and two RS-485 ports ●
Steady State: Up to 360s of 1-cycle absolute peak values
● U and I THD, TOHD, TEHD, TIHD, TOIHD, TEIHD and TH (RMS) ● External status monitoring with programmable debounce Export of IER, AER and SDR Logs as well as EN50160 Reports
● 3-phase U, I, P, Q, S, and PF as well as U4, I4 and I5 @ ½ cycle ●
Post Fault: 15 cycles @ 512 samples/cycle

● U and I Individual Harmonics (%HD and RMS) from 2nd to 63rd # ● Pulse counting with programmable weight for each channel for Generation and Export of Self-defined PQ Analysis Reports
● Frequency @ 1 cycle ●
● U and I Individual Interharmonics (%IHD and RMS) from 1st to 63rd # RMS Recorder (RMSR) collecting WAGES (Water, Air, Gas, Electricity, Steam) information
Display & Web Servers ● Total Harmonic P, Q, S and PF ● 128 entries ● Demand Synchronization and Tariff Switch based on DI Status 3rd Party System Integration
Demands ● Harmonic P, Q, S and PF from 2nd to 63rd in RMS ● 16 parameters maximum, selectable U, I, P, Q, S, PF, Frequency, ● Easy integration into Substation Automation or Utility SCADA
Freq. Deviation Digital Outputs systems via Modbus RTU, Modbus TCP or IEC61850
● True RMS Real-time, Harmonics, Power and Energy Measurements ● Present and Predicted Demand for 3-phase U, I, P, Q, S, and PF ● Harmonic Phase Angle from 2nd to 63rd #
Recording Interval from 0.5 to 60 cycles
● Standard 4 or optional 8 channels Form A Mechanical Relays for The on-board, password-protected Web Server provides
● Demands and Multi-Tariff TOU as well as U4, I4, I5, Frequency ● U and I DC Components ● ●

Recording Depth @ 7200 samples per parameter general purpose control or alarming user-friendly access to its data and supports the configuration for
● Max. & Min. Logs ● Present Demand of 4-phase U & I THD/TOHD/TEHD, 4-phase ● Total Harmonic kWh, kvarh Import/Export/Net/Total ●

Configurable pre-fault samples from 100 to 500


● Standard 4 SS Relays for Energy pulsing applications most Setup parameters via a web browser without the use of
● Sequence & Unbalance Current K-Factor, U/I Unbalance, Over & Under Deviation of ● Total Harmonic kWh, kvarh Import/Export from 2nd to 63rd ●

● Real-time WF Capture of 3-phase Voltages and Currents Voltage and Frequency, 4-phase Fundamental Current
#
%HD and %IHD can be configured as % of Fundamental, % of U/I nominal or % of RMS ● 72 seconds of ½ cycle RMS Recording @ 50Hz or 60 seconds @ 60 Hz Analog Inputs (Optional) proprietary software
● Event Waveforms and ITIC/SEMI F47 Curves ● Max./Min. values per Demand Interval Conducted Emissions in the 2kHz to 150kHz range ● Display of Ua/Ub/Uc/Uab/Ubc/Uca/Ia/Ib/Ic RMSR on the Web Interface ● Two channels 0/4-20mA DC input with programmable zero and
● The on-board, password protected FTP Server allows logged data
● Harmonics & Interharmonics Histogram and Phasor diagrams ● Maximum Demands for This Month & Last Month (or Since ● Real-time amplitude (150/180-Cycle) and the Max., Min., Avg. PQ Event Counters full scales that can be used to measure external transducer signal in CSV format and waveform records in PQDIF or COMTRADE
● Device and SOE Logs, PQ Counters and I/O Status Last Reset & Before Last Reset) and CP95 (in 1-minute interval) for a total of 106 frequency ● Dips, Swells, Interruptions, Transients, Rapid Voltage Changes, format to be downloaded without any special software. The
Analog Output (Optional) downloaded files can be subsequently viewed using software that
● Device Configuration and Diagnostics ● Demand Synchronization with DI segments for the 2-9kHz (Urms and Irms) and 9-150kHz (Urms) range Inrush Current, Mains Signalling Voltages and Total PQ Event Counters
● One or two channels 0/4-20mA DC output with programmable supports the industry standard PQDIF and COMTRADE file formats
zero and full scales
Sequence and Unbalance iTrigger Statistical Data Recorder (SDR)
The iMeter 8 is CET’s Advanced PQ Analyzer designed for the Multi-Tariff TOU Capability ● Zero, Positive and Negative Sequence Components ● Ability to cross-trigger WFR, DWR, RMSR and DO between ● 16 SDR Logs of maximum 64 parameters each
compliance monitoring market as it offers un-surpassed func- ● U and I Unbalance based on Zero and Negative Sequence iTrigger-enabled devices over a network connection ● Recording of the Max., Min., Avg. and CP95 for Real-time
● Two independent sets of TOU Schedules, each supporting Components Programmable via Web Interface or Communications Measurements including U, I, P, Q, S, PF, Freq., Power, PF,
tionality by combining Class 0.2S accuracy and advanced PQ


Up to 12 Seasons Dips, Swells & Interruptions and Transients Recording Harmonics, Deviations and Unbalances
features in a 192x192x182.4mm housing with a High-Resolution, ●
90 Holidays or Alternate Days and 3 Weekdays ● Transients capture as short as 20us at 1024 samples @ 50Hz for Data and Event Recorders ● Recording interval from 0 to 60 minutes
Color Dot-Matrix LCD display. The iMeter 8 complies with such ●
20 Daily Profiles, each with 12 Periods at min. 15-minute interval sub-cycle disturbance such as capacitor switching and resonance
● 30 days @ 1-minute, 300 days @ 10-minute, 450-day @ 15-minute
8 Tariffs, each providing the following information: Non-Volatile Log Memory ● PQDIF file format, downloadable from the on-board FTP Server
standards as IEC62053-22 Class 0.2S, IEC61000-4-30 Ed. 3

phenomena
kWh/kvarh Import/Export and kVAh

● 8GB on-board non-volatile Log Memory ● Support FIFO or Stop-When-Full mode
● Dips, Swells & Interruptions detection @ 10ms (½ cycle at 50Hz)
Class A Compliant, IEC61000-4-15, IEC61000-4-7, EN50160 as P & Q Import/Export Maximum Demands with timestamp Interval Energy Recorder (IER) and Accumulative Energy
Max./Min. Recorder (MMR)

● Trigger for DO, WF Recording, Disturbance Waveform Recording, Recorder (AER)
well as IEC61850 for Substation Automation. Further, it offers a Register rollover at 100,000,000,000 kXh

RMS Recording and Alarm Email ● 4 Max./Min. Recorders of 20 parameters each
● Both IER Log and AER Log support recording of Total RMS
● 12 Historical Logs for Energy and Maximum Demand RMS/Fundamental/Harmonic/Interharmonic Measurements,
large logging capacity with 8GB of on-board memory, extensive ● Display of ITIC, SEMI F47 and RMSR (RMS Recording) as well as kWh, kvarh Import/Export/Total/Net and kVAh, Total

Demands, Deviations, Unbalances and Flicker


I/O, multiple Time Sync. methods, 2x100BaseT Ethernet and the Event Waveform on the Front Panel and Web Interface Fundamental and Total Harmonic kWh, kvarh Import/Export Setpoints Communications
2xRS-485 ports. In addition, it optionally provides 2xAO and 2xAI Power Quality Features Rapid Voltage Changes (RVC) ● Recording Interval from 1 to 65535 minutes
● Two transfer modes:

Manual: Max./Min. Since Last Reset & Before Last Reset
● Detection of a quick transition in RMS voltage between two ● Maximum Recording Depth @ 65535 records PQ Setpoints Ethernet Ports (P1, P2)
for different applications. These features likely make the iMeter 8 ●
Auto: Max./Min. of This Month & Last Month
● IEC61000-4-30 Ed. 3 Class A Compliant steady-states voltage conditions ● Support FIFO and Stop-When-Full modes ● Transients, Dips, Swells, Interruptions ● Dual 10/100BaseT Ethernet Ports with RJ45 connector
one of the most advanced PQ Analyzer for an intelligent Power IEC61000-4-15, IEC61000-4-7 Compliance Device Log SOE Log

Inrush Current Monitoring ● Rapid Voltage Changes ● Protocols supported: Modbus TCP, HTTPS, SNTP, SMTP, FTP
● 2kHz to 150kHz Conducted Emission Measurements ● 1024 FIFO entries time-stamped to ±1ms resolution ● 1024 FIFO events time-stamped to ±1ms resolution Inrush Current
Quality Monitoring System. ● Monitoring of the ½ cycle RMS Current and capturing of the ● and IEC61850
● Disturbance Direction Indicator ● Power On/Off Records, Setup changes, Time Sync., ● Setpoint events, I/O operations, Dips, Swells, Interruptions, Trigger DO, WFR, DWR, RMSR or Alarm Email
Current waveforms associated with events such as motor ● ● Built-in password protected Web Server for easy data viewing,
● Disturbance Waveform Recording Device Operations and Self-diagnostics Transients, Rapid Voltage Changes, Inrush Current, Mains
starting and transformer being energized setup configuration and firmware upgrade
RMS Recording and EN50160 Reporting Signalling Voltages, Motor Start, etc. Control Setpoints
● Data Recorder (DR) Log Simultaneous client connections for 12xModbus TCP
● PQ Monitoring at HV, MV and LV Utility Substations Disturbance Direction Indicator Record the time and characteristic data of the Setpoint and PQ event ● 256 standard and 16 High-Speed Setpoints

● Fault Capture up to 2,000V peak to peak ● 8 Standard DR Logs ●
& 12xIEC61850
● Data Centers, Semiconductor Fabs, Heavy Industries ● Determine if a Dip Event is located upstream or downstream ● Extensive monitoring sources including U, I, P, Q, S, Demand,
● Waveform Recording in COMTRADE and PQDIF file format ● Recording Interval from 1s to 40 days for Standard DR Log
7x24 Automated Manufacturing Facilities (Compatible with the PQ View software)
● Pinpoint if the cause of the event is external or internal
Time Synchronization Harmonics, Unbalances, Deviations, Flickers, Phase
Typical Up to 64 Parameters for each DR Log with programmable RS-485
● ●

Real-Time Waveform Capture (WFC) and Waveform Recorder (WFR) Reversal/Loss, AI, etc. Dual optically isolated RS-485 port with baud rate from 1.2 to
sources such as Real-time Measurements, Harmonics, ●
● Dips, Swells, Interruptions, Transients, Flickers & Harmonics Monitoring Real-time WFC @ 128 samples/cyclex4 cycles via Front Panel ● Battery-backed Real-time clock @ 6ppm (≤0.5s/day) ● Configurable thresholds and time delays
Power Quality Metering Unbalance and Demand Measurements 38.4kbps

Applications ● Mains and Critical Feeder Monitoring and Web Interface ● Configurable Depth and Recording Offset
● Time Sync. via Modbus RTU/TCP, SNTP, IEEE1588 (PTP) ● Trigger DO, DR, WFR, DWR, RMSR or Alarm Email ● Support Modbus RTU and Ethernet Gateway
WFR with maximum 128 entries ● Optional GPS/IRIG-B Input
● IEC61850 support for Substation Automation and Smart Grid PQ Parameters as per IEC61000-4-30 Ed. 3 Class A Compliant
● ● Support FIFO or Stop-When-Full recording modes
Digital Input Setpoints
● Simultaneous capture of 3-phase Voltage and Current Inputs
● Retrofit Applications with Split-Core Current Probe (SCCP) ● Power Frequency
● No. of CyclesxSamples/Cycles with programmable pre-fault
● Provides control output actions in response to changes in
Magnitude of the Supply Voltage and Current Digital Input status
System Integration

cycles: 400x1024, 800x512, 1600x256, 3200x128
● Flicker ● Trigger DO, DR, WFR, DWR, RMSR or Alarm Email
● Scheduled WFR with maximum repetition of 10,000 times and
● Transients, Dips/Swells and Interruptions
programmable schedule from 1 to 1440 mins
Supply Voltage Unbalance and Current Unbalance PecStar® iEMS
Basic Features Metering

COMTRADE file format, downloadable from the on-board
Inputs and Outputs

● Mains Signalling Voltage on the Supply Voltage ● The iMeter 8 is supported by CET’s PecStar® iEMS
Web Server or FTP Server
● Rapid Voltage Changes ● In addition, the iMeter 8 can be easily integrated into other 3rd
● IEC62053-22 Class 0.2S kWh metering with Multi-Tariff TOU Basic Measurements (1-second update) ● Measurement of Over and Under Deviation parameters Disturbance Waveform Recorder (DWR) party systems because of its support of multiple communications
Digital Inputs
● True RMS @ 1024 samples/cycle sampling ● 3-phase U, I, P, Q, S, and PF as well as U4, I4 and I5 ● Harmonic and Interharmonics Measurements for Voltage ● 128 entries ports as well as different industry standard protocols such as
● Standard 8 or optional 16 channels
● 8GB on-board log memory ● kWh, kvarh Import/Export/Net/Total and kVAh Total and Current ● Simultaneous recording of all Voltage (U1-U4) and Current (I1-I5) Modbus and IEC61850
● Standard volt free dry contact with 24VDC Internal Excitation
● 7” High-Resolution Color Dot-Matrix Display @ 800x480 ● Frequency ● 2 to 150kHz Conducted Emission Measurements Inputs
● Optional 110VAC/DC or 220VAC/DC External Excitation DiagSys
● Time Sync. via SNTP, IEEE 1588 (PTP), IRIG-B or GPS 1PPS output ●
Initial Fault: 35 cycles @ 512 samples/cycle
Harmonic and Interharmonic Measurements ● 1000Hz sampling for status monitoring with programmable
● 256 Standard Setpoints and 16 High-Speed Setpoints ●
Extended Fault: Up to 150 cycles @ 16 samples/cycle
● Display of Real-time Measurements, PQ Events, Waveforms and
High-Speed Measurements
● K-Factor for Current, Crest Factor for Current and Voltage debounce Statistical Trend Charts
● Dual 100BaseT Ethernet and two RS-485 ports ●
Steady State: Up to 360s of 1-cycle absolute peak values
● U and I THD, TOHD, TEHD, TIHD, TOIHD, TEIHD and TH (RMS) ● External status monitoring with programmable debounce Export of IER, AER and SDR Logs as well as EN50160 Reports
● 3-phase U, I, P, Q, S, and PF as well as U4, I4 and I5 @ ½ cycle ●
Post Fault: 15 cycles @ 512 samples/cycle

● U and I Individual Harmonics (%HD and RMS) from 2nd to 63rd # ● Pulse counting with programmable weight for each channel for Generation and Export of Self-defined PQ Analysis Reports
● Frequency @ 1 cycle ●
● U and I Individual Interharmonics (%IHD and RMS) from 1st to 63rd # RMS Recorder (RMSR) collecting WAGES (Water, Air, Gas, Electricity, Steam) information
Display & Web Servers ● Total Harmonic P, Q, S and PF ● 128 entries ● Demand Synchronization and Tariff Switch based on DI Status 3rd Party System Integration
Demands ● Harmonic P, Q, S and PF from 2nd to 63rd in RMS ● 16 parameters maximum, selectable U, I, P, Q, S, PF, Frequency, ● Easy integration into Substation Automation or Utility SCADA
Freq. Deviation Digital Outputs systems via Modbus RTU, Modbus TCP or IEC61850
● True RMS Real-time, Harmonics, Power and Energy Measurements ● Present and Predicted Demand for 3-phase U, I, P, Q, S, and PF ● Harmonic Phase Angle from 2nd to 63rd #
Recording Interval from 0.5 to 60 cycles
● Standard 4 or optional 8 channels Form A Mechanical Relays for The on-board, password-protected Web Server provides
● Demands and Multi-Tariff TOU as well as U4, I4, I5, Frequency ● U and I DC Components ● ●

Recording Depth @ 7200 samples per parameter general purpose control or alarming user-friendly access to its data and supports the configuration for
● Max. & Min. Logs ● Present Demand of 4-phase U & I THD/TOHD/TEHD, 4-phase ● Total Harmonic kWh, kvarh Import/Export/Net/Total ●

Configurable pre-fault samples from 100 to 500


● Standard 4 SS Relays for Energy pulsing applications most Setup parameters via a web browser without the use of
● Sequence & Unbalance Current K-Factor, U/I Unbalance, Over & Under Deviation of ● Total Harmonic kWh, kvarh Import/Export from 2nd to 63rd ●

● Real-time WF Capture of 3-phase Voltages and Currents Voltage and Frequency, 4-phase Fundamental Current
#
%HD and %IHD can be configured as % of Fundamental, % of U/I nominal or % of RMS ● 72 seconds of ½ cycle RMS Recording @ 50Hz or 60 seconds @ 60 Hz Analog Inputs (Optional) proprietary software
● Event Waveforms and ITIC/SEMI F47 Curves ● Max./Min. values per Demand Interval Conducted Emissions in the 2kHz to 150kHz range ● Display of Ua/Ub/Uc/Uab/Ubc/Uca/Ia/Ib/Ic RMSR on the Web Interface ● Two channels 0/4-20mA DC input with programmable zero and
● The on-board, password protected FTP Server allows logged data
● Harmonics & Interharmonics Histogram and Phasor diagrams ● Maximum Demands for This Month & Last Month (or Since ● Real-time amplitude (150/180-Cycle) and the Max., Min., Avg. PQ Event Counters full scales that can be used to measure external transducer signal in CSV format and waveform records in PQDIF or COMTRADE
● Device and SOE Logs, PQ Counters and I/O Status Last Reset & Before Last Reset) and CP95 (in 1-minute interval) for a total of 106 frequency ● Dips, Swells, Interruptions, Transients, Rapid Voltage Changes, format to be downloaded without any special software. The
Analog Output (Optional) downloaded files can be subsequently viewed using software that
● Device Configuration and Diagnostics ● Demand Synchronization with DI segments for the 2-9kHz (Urms and Irms) and 9-150kHz (Urms) range Inrush Current, Mains Signalling Voltages and Total PQ Event Counters
● One or two channels 0/4-20mA DC output with programmable supports the industry standard PQDIF and COMTRADE file formats
zero and full scales
Sequence and Unbalance iTrigger Statistical Data Recorder (SDR)
The iMeter 8 is CET’s Advanced PQ Analyzer designed for the Multi-Tariff TOU Capability ● Zero, Positive and Negative Sequence Components ● Ability to cross-trigger WFR, DWR, RMSR and DO between ● 16 SDR Logs of maximum 64 parameters each
compliance monitoring market as it offers un-surpassed func- ● U and I Unbalance based on Zero and Negative Sequence iTrigger-enabled devices over a network connection ● Recording of the Max., Min., Avg. and CP95 for Real-time
● Two independent sets of TOU Schedules, each supporting Components Programmable via Web Interface or Communications Measurements including U, I, P, Q, S, PF, Freq., Power, PF,
tionality by combining Class 0.2S accuracy and advanced PQ


Up to 12 Seasons Dips, Swells & Interruptions and Transients Recording Harmonics, Deviations and Unbalances
features in a 192x192x182.4mm housing with a High-Resolution, ●
90 Holidays or Alternate Days and 3 Weekdays ● Transients capture as short as 20us at 1024 samples @ 50Hz for Data and Event Recorders ● Recording interval from 0 to 60 minutes
Color Dot-Matrix LCD display. The iMeter 8 complies with such ●
20 Daily Profiles, each with 12 Periods at min. 15-minute interval sub-cycle disturbance such as capacitor switching and resonance
● 30 days @ 1-minute, 300 days @ 10-minute, 450-day @ 15-minute
8 Tariffs, each providing the following information: Non-Volatile Log Memory ● PQDIF file format, downloadable from the on-board FTP Server
standards as IEC62053-22 Class 0.2S, IEC61000-4-30 Ed. 3

phenomena
kWh/kvarh Import/Export and kVAh

● 8GB on-board non-volatile Log Memory ● Support FIFO or Stop-When-Full mode
● Dips, Swells & Interruptions detection @ 10ms (½ cycle at 50Hz)
Class A Compliant, IEC61000-4-15, IEC61000-4-7, EN50160 as P & Q Import/Export Maximum Demands with timestamp Interval Energy Recorder (IER) and Accumulative Energy
Max./Min. Recorder (MMR)

● Trigger for DO, WF Recording, Disturbance Waveform Recording, Recorder (AER)
well as IEC61850 for Substation Automation. Further, it offers a Register rollover at 100,000,000,000 kXh

RMS Recording and Alarm Email ● 4 Max./Min. Recorders of 20 parameters each
● Both IER Log and AER Log support recording of Total RMS
● 12 Historical Logs for Energy and Maximum Demand RMS/Fundamental/Harmonic/Interharmonic Measurements,
large logging capacity with 8GB of on-board memory, extensive ● Display of ITIC, SEMI F47 and RMSR (RMS Recording) as well as kWh, kvarh Import/Export/Total/Net and kVAh, Total

Demands, Deviations, Unbalances and Flicker


I/O, multiple Time Sync. methods, 2x100BaseT Ethernet and the Event Waveform on the Front Panel and Web Interface Fundamental and Total Harmonic kWh, kvarh Import/Export Setpoints Communications
2xRS-485 ports. In addition, it optionally provides 2xAO and 2xAI Power Quality Features Rapid Voltage Changes (RVC) ● Recording Interval from 1 to 65535 minutes
● Two transfer modes:

Manual: Max./Min. Since Last Reset & Before Last Reset
● Detection of a quick transition in RMS voltage between two ● Maximum Recording Depth @ 65535 records PQ Setpoints Ethernet Ports (P1, P2)
for different applications. These features likely make the iMeter 8 ●
Auto: Max./Min. of This Month & Last Month
● IEC61000-4-30 Ed. 3 Class A Compliant steady-states voltage conditions ● Support FIFO and Stop-When-Full modes ● Transients, Dips, Swells, Interruptions ● Dual 10/100BaseT Ethernet Ports with RJ45 connector
one of the most advanced PQ Analyzer for an intelligent Power IEC61000-4-15, IEC61000-4-7 Compliance Device Log SOE Log

Inrush Current Monitoring ● Rapid Voltage Changes ● Protocols supported: Modbus TCP, HTTPS, SNTP, SMTP, FTP
● 2kHz to 150kHz Conducted Emission Measurements ● 1024 FIFO entries time-stamped to ±1ms resolution ● 1024 FIFO events time-stamped to ±1ms resolution Inrush Current
Quality Monitoring System. ● Monitoring of the ½ cycle RMS Current and capturing of the ● and IEC61850
● Disturbance Direction Indicator ● Power On/Off Records, Setup changes, Time Sync., ● Setpoint events, I/O operations, Dips, Swells, Interruptions, Trigger DO, WFR, DWR, RMSR or Alarm Email
Current waveforms associated with events such as motor ● ● Built-in password protected Web Server for easy data viewing,
● Disturbance Waveform Recording Device Operations and Self-diagnostics Transients, Rapid Voltage Changes, Inrush Current, Mains Signalling
starting and transformer being energized setup configuration and firmware upgrade
RMS Recording and EN50160 Reporting Voltages, Motor Start, etc. Control Setpoints
● Data Recorder (DR) Log Simultaneous client connections for 12xModbus TCP
● PQ Monitoring at HV, MV and LV Utility Substations Disturbance Direction Indicator Record the time and characteristic data of the Setpoint and PQ event ● 256 standard and 16 High-Speed Setpoints

● Fault Capture up to 2,000V peak to peak ● 8 Standard DR Logs ●
& 12xIEC61850
● Data Centers, Semiconductor Fabs, Heavy Industries ● Determine if a Dip Event is located upstream or downstream ● Extensive monitoring sources including U, I, P, Q, S, Demand,
● Waveform Recording in COMTRADE and PQDIF file format ● Recording Interval from 1s to 40 days for Standard DR Log
7x24 Automated Manufacturing Facilities (Compatible with the PQ View software)
● Pinpoint if the cause of the event is external or internal
Time Synchronization Harmonics, Unbalances, Deviations, Flickers, Phase
Typical Up to 64 Parameters for each DR Log with programmable RS-485
● ●

Real-Time Waveform Capture (WFC) and Waveform Recorder (WFR) Reversal/Loss, AI, etc. Dual optically isolated RS-485 port with baud rate from 1.2 to
sources such as Real-time Measurements, Harmonics, ●
● Dips, Swells, Interruptions, Transients, Flickers & Harmonics Monitoring Real-time WFC @ 128 samples/cyclex4 cycles via Front Panel ● Battery-backed Real-time clock @ 6ppm (≤0.5s/day) ● Configurable thresholds and time delays
Power Quality Metering Unbalance and Demand Measurements 38.4kbps

Applications ● Mains and Critical Feeder Monitoring and Web Interface ● Configurable Depth and Recording Offset
● Time Sync. via Modbus RTU/TCP, SNTP, IEEE1588 (PTP) ● Trigger DO, DR, WFR, DWR, RMSR or Alarm Email ● Support Modbus RTU and Ethernet Gateway
WFR with maximum 128 entries ● Optional GPS/IRIG-B Input
● IEC61850 support for Substation Automation and Smart Grid PQ Parameters as per IEC61000-4-30 Ed. 3 Class A Compliant
● ● Support FIFO or Stop-When-Full recording modes
Digital Input Setpoints
● Simultaneous capture of 3-phase Voltage and Current Inputs
● Retrofit Applications with Split-Core Current Probe (SCCP) ● Power Frequency
● No. of CyclesxSamples/Cycles with programmable pre-fault
● Provides control output actions in response to changes in
Magnitude of the Supply Voltage and Current Digital Input status
System Integration

cycles: 400x1024, 800x512, 1600x256, 3200x128
● Flicker ● Trigger DO, DR, WFR, DWR, RMSR or Alarm Email
● Scheduled WFR with maximum repetition of 10,000 times and
● Transients, Dips/Swells and Interruptions
programmable schedule from 1 to 1440 mins
Supply Voltage Unbalance and Current Unbalance PecStar® iEMS
Basic Features Metering

COMTRADE file format, downloadable from the on-board
Inputs and Outputs

● Mains Signalling Voltage on the Supply Voltage ● The iMeter 8 is supported by CET’s PecStar® iEMS
Web Server or FTP Server
● Rapid Voltage Changes ● In addition, the iMeter 8 can be easily integrated into other 3rd
● IEC62053-22 Class 0.2S kWh metering with Multi-Tariff TOU Basic Measurements (1-second update) ● Measurement of Over and Under Deviation parameters Disturbance Waveform Recorder (DWR) party systems because of its support of multiple communications
Digital Inputs
● True RMS @ 1024 samples/cycle sampling ● 3-phase U, I, P, Q, S, and PF as well as U4, I4 and I5 ● Harmonic and Interharmonics Measurements for Voltage ● 128 entries ports as well as different industry standard protocols such as
● Standard 8 or optional 16 channels
● 8GB on-board log memory ● kWh, kvarh Import/Export/Net/Total and kVAh Total and Current ● Simultaneous recording of all Voltage (U1-U4) and Current (I1-I5) Modbus and IEC61850
● Standard volt free dry contact with 24VDC Internal Excitation
● 7” High-Resolution Color Dot-Matrix Display @ 800x480 ● Frequency ● 2 to 150kHz Conducted Emission Measurements Inputs
● Optional 110VAC/DC or 220VAC/DC External Excitation DiagSys
● Time Sync. via SNTP, IEEE 1588 (PTP), IRIG-B or GPS 1PPS output ●
Initial Fault: 35 cycles @ 512 samples/cycle
Harmonic and Interharmonic Measurements ● 1000Hz sampling for status monitoring with programmable
● 256 Standard Setpoints and 16 High-Speed Setpoints ●
Extended Fault: Up to 150 cycles @ 16 samples/cycle
● Display of Real-time Measurements, PQ Events, Waveforms and
High-Speed Measurements
● K-Factor for Current, Crest Factor for Current and Voltage debounce Statistical Trend Charts
● Dual 100BaseT Ethernet and two RS-485 ports ●
Steady State: Up to 360s of 1-cycle absolute peak values
● U and I THD, TOHD, TEHD, TIHD, TOIHD, TEIHD and TH (RMS) ● External status monitoring with programmable debounce Export of IER, AER and SDR Logs as well as EN50160 Reports
● 3-phase U, I, P, Q, S, and PF as well as U4, I4 and I5 @ ½ cycle ●
Post Fault: 15 cycles @ 512 samples/cycle

● U and I Individual Harmonics (%HD and RMS) from 2nd to 63rd # ● Pulse counting with programmable weight for each channel for Generation and Export of Self-defined PQ Analysis Reports
● Frequency @ 1 cycle ●
● U and I Individual Interharmonics (%IHD and RMS) from 1st to 63rd # RMS Recorder (RMSR) collecting WAGES (Water, Air, Gas, Electricity, Steam) information
Display & Web Servers ● Total Harmonic P, Q, S and PF ● 128 entries ● Demand Synchronization and Tariff Switch based on DI Status 3rd Party System Integration
Demands ● Harmonic P, Q, S and PF from 2nd to 63rd in RMS ● 16 parameters maximum, selectable U, I, P, Q, S, PF, Frequency, ● Easy integration into Substation Automation or Utility SCADA
Freq. Deviation Digital Outputs systems via Modbus RTU, Modbus TCP or IEC61850
● True RMS Real-time, Harmonics, Power and Energy Measurements ● Present and Predicted Demand for 3-phase U, I, P, Q, S, and PF ● Harmonic Phase Angle from 2nd to 63rd #
Recording Interval from 0.5 to 60 cycles
● Standard 4 or optional 8 channels Form A Mechanical Relays for The on-board, password-protected Web Server provides
● Demands and Multi-Tariff TOU as well as U4, I4, I5, Frequency ● U and I DC Components ● ●

Recording Depth @ 7200 samples per parameter general purpose control or alarming user-friendly access to its data and supports the configuration for
● Max. & Min. Logs ● Present Demand of 4-phase U & I THD/TOHD/TEHD, 4-phase ● Total Harmonic kWh, kvarh Import/Export/Net/Total ●

Configurable pre-fault samples from 100 to 500


● Standard 4 SS Relays for Energy pulsing applications most Setup parameters via a web browser without the use of
● Sequence & Unbalance Current K-Factor, U/I Unbalance, Over & Under Deviation of ● Total Harmonic kWh, kvarh Import/Export from 2nd to 63rd ●

● Real-time WF Capture of 3-phase Voltages and Currents Voltage and Frequency, 4-phase Fundamental Current
#
%HD and %IHD can be configured as % of Fundamental, % of U/I nominal or % of RMS ● 72 seconds of ½ cycle RMS Recording @ 50Hz or 60 seconds @ 60 Hz Analog Inputs (Optional) proprietary software
● Event Waveforms and ITIC/SEMI F47 Curves ● Max./Min. values per Demand Interval Conducted Emissions in the 2kHz to 150kHz range ● Display of Ua/Ub/Uc/Uab/Ubc/Uca/Ia/Ib/Ic RMSR on the Web Interface ● Two channels 0/4-20mA DC input with programmable zero and
● The on-board, password protected FTP Server allows logged data
● Harmonics & Interharmonics Histogram and Phasor diagrams ● Maximum Demands for This Month & Last Month (or Since ● Real-time amplitude (150/180-Cycle) and the Max., Min., Avg. PQ Event Counters full scales that can be used to measure external transducer signal in CSV format and waveform records in PQDIF or COMTRADE
● Device and SOE Logs, PQ Counters and I/O Status Last Reset & Before Last Reset) and CP95 (in 1-minute interval) for a total of 106 frequency ● Dips, Swells, Interruptions, Transients, Rapid Voltage Changes, format to be downloaded without any special software. The
Analog Output (Optional) downloaded files can be subsequently viewed using software that
● Device Configuration and Diagnostics ● Demand Synchronization with DI segments for the 2-9kHz (Urms and Irms) and 9-150kHz (Urms) range Inrush Current, Mains Signalling Voltages and Total PQ Event Counters
● One or two channels 0/4-20mA DC output with programmable supports the industry standard PQDIF and COMTRADE file formats
zero and full scales
Ordering Guide Accuracy EMC Compatibility Device Dimensions
Product Code Description Unit: mm
iMeter 8 Advanced Power Quality Analyzer Parameters Accuracy Resolution Power Supply (L+, N-) CE EMC Directive 2014/30/EU (EN61326: 2013)
A 1024 samples/cycle, 8GB On-Board Memory, IEC61000-4-30 Ed. 3 Class A Compliant Voltage (U) ±0.1% 0.001V Standard 95-250VAC/VDC ± 10%, 47-440Hz
Basic Feature ±0.1% Burden < 12W Immunity (EN50082-2)
1024 samples/cycle, 8GB On-Board Memory,
B*~ I1, I2, I3
IEC61000-4-30 Ed. 3 Class A Compliant with 2-150kHz C.E. Measurement SCCPA Option: ±01%+Error of SCCP Overvoltage Category CATIII 300V Electrostatic Discharge EN61000-4-2: 2009
0.001A
5 5A I4 ±0.1% Radiated Fields EN61000-4-3: 2006 +A1: 2008 +A2: 2010
Input Current 1 1A I5 ±0.5% Fast Transients EN61000-4-4: 2012
SCCPA^ SCCP Option for use with CT Clamps with max. 500mV output ±0.2% Surges EN61000-4-5: 2014 +A1: 2017
P, Q, S 0.001kX Digital Inputs ( DIC, DI1 to DI8 or DI16) Conducted Disturbances
VN

Input Voltage 9 400ULN/690ULL + 20% SCCPA Option: ±0.5% EN61000-4-6: 2014


V4

95-250VAC/DC ± 10%, 47-440Hz


Standard Dry contact, 24VDC internally wetted
Magnetic Fields EN61000-4-8: 2010
2 IEC62053-22 Class 0.2S V4N

Power Supply kWh, kVAh 0.1kXh Optional 110V/220V AC/DC externally wetted
3*# 20-60VDC SCCPA Option: IEC62053-21 Class 1 Voltage Dips and Interruptions EN61000-4-11: 2004+A1: 2017
50Hz
Sampling 1000Hz
Ring Wave EN61000-4-12: 2017
5 IEC62053-24 Class 0.5S
System Frequency kvarh IEC62053-23 Class 2 Hysteresis 1ms minimum
6 60Hz 0.1kvarh
A 8xDI + 4xDO + 4xSS Pulse Outputs SCCPA Option: IEC62053-24 Class 1 1

Emission (EN50081-2) 2

B*~ 8xDI + 4xDO + 2xAI + 1xAO + 4xSS Pulse Outputs ±0.2% 3

I/O PF 0.001
C* 16xDI + 8xDO + 4xSS Pulse Outputs SCCPA Option: ±0.5% Limits and Methods of Measurement of
Form A Relay Outputs (DO1 to DO3 or optional DO1 to DO7)
D*~ 8xDI + 4xDO + 2xAI + 2xAO + 2xSS Pulse Outputs Frequency ±0.003Hz 0.001Hz Electromagnetic Disturbance
Type Form A Mechanical Relay Characteristics of Industrial, Scientific EN55011: 2016
N Dry Contact (@24VDC Self-Excitation) Harmonics IEC61000-4-7 Class A 0.001
16xDI+8xDO+2xAI+1xAO
Loading 5A @ 250VAC/30VDC and Medical (ISM) Radio-Frequency
DI Excitation 1# 110V AC/DC External Excitation K-Factor IEC61000-4-7 Class A 0.001 Equipment
Rear Panel
2# 220V AC/DC External Excitation ±0.2°

Communications A 2x100BaseT + 2xRS-485 Phase Angle SCCPA Option: 0.1° Limits and Methods of Measurement of
±0.2°+ Phase Error of SCCP Radio Disturbance Characteristics of EN55032: 2015
Time Sync. A GPS, IRIG-B Form C Relay Outputs (Alarm 1, 2, 3) Information Technology Equipment
U Unbalance ±0.1% 0.01%
Display Language E English Type Form C Mechanical Relay
I Unbalance ±0.5% 0.01% Limits for Harmonic Current Emissions
iMeter 8 - A 5 9 2 5 A N A A E iMeter 8-A5925ANAAE (Standard Model) Loading 8A @ 250VAC/24VDC EN61000-3-2: 2014
Pst, Plt 0.01% for Equipment with Rated Current ≤16 A
±5%
* Additional charges apply.
~ The I/O options "B" and "D" are not supported when the Basic Feature option "B" is selected. Limitation of Voltage Fluctuations and
^ The SCCPA option is compatible with the SCCP models listed in the "SCCP Option" sheet. This option does not come with any Current Clamp. Flicker in Low-Voltage Supply Systems EN61000-3-3: 2013
Please refer to the "SCCP Option" sheet for more information and order the desired model and quantity as a separate item. for Equipment with Rated Current ≤16 A
#
The DI Excitation options “1” and “2” are not supported when the Power Supply option “3” with 20-60VDC is selected. Pulse Outputs (E1+, E1-, E2+, E2-, E3+, E3-, E4+, E4-)
Type Form A Solid State Relay Emission Standard for Industrial
EN61000-6-4: 2007 +A1: 2011

Optional SCCPs Technical Specifications Isolation


Max. Load Voltage
Optical
30VDC
Environments

Standards of Compliance
Max. Forward Current 4mA
Voltage Inputs (V1, V2, V3, VN, V4, V4N)
Standard (Un) 400ULN/690ULL +20%
Range 1% to 200% Un for 400ULN nominal Safety Requirements
* PMC-SCCP-5kA-500mV-B-C-C- Overload 2xUn continuous, 4xUn for 1s Optional Analog Input (AI1+, AI1-, AI2+, AI2-)
Model No. PMC-SCCP-50A-500mV-B-A-B PMC-SCCP-200A-200mV-B-B-B PMC-SCCP-500A-500mV-B-B-B EN61010-1: 2010
CE LVD 2014/35/EU

iMeter 8
371/254/150/100
Burden < 0.5VA/per phase Type 0-20/4-20 mA DC EN61010-2-030: 2010
5A 20A/200A 500A 500A/5000A Rogowski Coil
Measurement Range Primary 1-1,000,000V Overload 24 mA maximum
(50A Imax) (200A Imax) (500A Imax) (5000A Imax) Electrical Safety in Low Voltage
Secondary 1-1,500V Distribution Systems up to 1000Vac IEC61557-12: 2018 (PMD)
Max. Allowable Current 50A 260A 500A 10, 000A PT Ratio
AC 10mV/A @ 20A AC 1mV/A @ 500A
V4 Primary 1-1,000,000V and 1500Vdc Side view
AC 10mV/A AC 1mV/A V4 Secondary 1-1,500V
Output Voltage AC 1mV/A @ 200A AC 0.1mV/A @ 5000A
(Max. 500mV) (Max. 500mV) Insulation
(Max. 200mV) (Max. 500mV) Frequency 40Hz-60Hz @ 50Hz, 48Hz-72Hz @ 60Hz Optional Analog Output (AO1+, AO1-, AO2+, AO2-) IEC62052-11: 2003
AC Voltage: 2kV @ 1 minute
±0.3% rdg. ±0.3% rdg. ±0.3% rdg. ±2.0% rdg. IEC62053-22: 2003
Accuracy Type 0-20/4-20 mA DC Insulation Resistance: >100MΩ
±0.02% f.s. ±0.02% f.s. ±0.02% f.s. (1% - 200%) In EN61010-1: 2010
Loading 500Ω maximum Impulse Voltage: 6kV, 1.2/50µs
CAT III 1000V
Protection CAT III 300V CAT III 600V CAT III 600V Overload 24 mA maximum
CAT IV 600V Current Inputs (I11, I12, I21, I22, I31, I32, I41, I42, I51, I52)
Diameter 15mm 24mm 50mm 371/254/150/100mm
Standard (In) 5A (Standard), 1A (Optional) Mechanical Tests
Cable Length 3m 3m 3m 3m
Range 1% to 400% In Response IEC255-2-1: 1989
Termination BNC BNC BNC BNC Vibration Test
Starting Current 0.1% In Endurance IEC255-2-1: 1989
Environmental Conditions
* The Rogowski Coil SCCP comes with an external Universal Power Supply and an integrator. Overload 4xIn continuous, 20xIn for 1s Response IEC255-2-2
Operating Temperature -25°C to 70°C Shock Test
< 0.5VA/per phase @ 5A Endurance IEC255-2-2
Burden Storage Temperature -40°C to 85°C
< 0.1VA/per phase @ 1A Bump Test IEC255-2-2
Humidity 5% to 95% non-condensing
5A/50A (In/Imax),
SCCP-50A-500mV
Atmospheric Pressure
Your Local Representative

max. 500mV Output 63 kPa to 110 kPa

20A/200A (In/Imax), Pollution Degree 2 Power Quality


SCCP-200A-200mV
SCCP Options max. 200mV Output Measurement Category CATIII 1000V
Voltage Characteristics of Electricity Supplied
SCCP-500A-500mV 500A Imax, max. 500mV Output EN50160
by Public Distribution Systems
V.00 05.07.2022

Selectable 500A/5000A (Imax)


SCCP-5000A-500mV General Guide on Harmonic and Interharmonic
Rogowski Coil, max. 500mV Output
Measurements and Instrumentation, for Power IEC61000-4-7
Primary 1-30,000A Mechanical Characteristics Supply Systems and Equipment Connected Thereto
Email: sales@cet-global.com
Secondary 1-50A
Website: www.cet-global.com CT Ratio Panel Cutout 186x186mm Flicker Meter - Functional and Design Specifications IEC61000-4-15
I4 Primary 1-30,000A
Unit Dimensions 192x192x182.4mm Testing and Measurement Techniques-Power IEC61000-4-30 Ed. 3
Copyright © CET Inc. All rights reserved.
I4 Secondary 1-50A
IP Rating 52 Quality Measurement Methods Class A Compliant Installation
www.cet-global.com
NO TIENE PUERTO USB
Ordering Guide Accuracy EMC Compatibility Device Dimensions
Product Code Description Unit: mm
iMeter 8 Advanced Power Quality Analyzer Parameters Accuracy Resolution Power Supply (L+, N-) CE EMC Directive 2014/30/EU (EN61326: 2013)
A 1024 samples/cycle, 8GB On-Board Memory, IEC61000-4-30 Ed. 3 Class A Compliant Voltage (U) ±0.1% 0.001V Standard 95-250VAC/VDC ± 10%, 47-440Hz
Basic Feature ±0.1% Burden < 12W Immunity (EN50082-2)
1024 samples/cycle, 8GB On-Board Memory,
B*~ I1, I2, I3
IEC61000-4-30 Ed. 3 Class A Compliant with 2-150kHz C.E. Measurement SCCPA Option: ±01%+Error of SCCP Overvoltage Category CATIII 300V Electrostatic Discharge EN61000-4-2: 2009
0.001A
5 5A I4 ±0.1% Radiated Fields EN61000-4-3: 2006 +A1: 2008 +A2: 2010
Input Current 1 1A I5 ±0.5% Fast Transients EN61000-4-4: 2012
SCCPA^ SCCP Option for use with CT Clamps with max. 500mV output ±0.2% Surges EN61000-4-5: 2014 +A1: 2017
P, Q, S 0.001kX Digital Inputs ( DIC, DI1 to DI8 or DI16) Conducted Disturbances
VN

Input Voltage 9 400ULN/690ULL + 20% SCCPA Option: ±0.5% EN61000-4-6: 2014


V4

95-250VAC/DC ± 10%, 47-440Hz


Standard Dry contact, 24VDC internally wetted
Magnetic Fields EN61000-4-8: 2010
2 IEC62053-22 Class 0.2S V4N

Power Supply kWh, kVAh 0.1kXh Optional 110V/220V AC/DC externally wetted
3*# 20-60VDC SCCPA Option: IEC62053-21 Class 1 Voltage Dips and Interruptions EN61000-4-11: 2004+A1: 2017
50Hz
Sampling 1000Hz
Ring Wave EN61000-4-12: 2017
5 IEC62053-24 Class 0.5S
System Frequency kvarh IEC62053-23 Class 2 Hysteresis 1ms minimum
6 60Hz 0.1kvarh
A 8xDI + 4xDO + 4xSS Pulse Outputs SCCPA Option: IEC62053-24 Class 1 1

Emission (EN50081-2) 2

B*~ 8xDI + 4xDO + 2xAI + 1xAO + 4xSS Pulse Outputs ±0.2% 3

I/O PF 0.001
C* 16xDI + 8xDO + 4xSS Pulse Outputs SCCPA Option: ±0.5% Limits and Methods of Measurement of
Form A Relay Outputs (DO1 to DO3 or optional DO1 to DO7)
D*~ 8xDI + 4xDO + 2xAI + 2xAO + 2xSS Pulse Outputs Frequency ±0.003Hz 0.001Hz Electromagnetic Disturbance
Type Form A Mechanical Relay Characteristics of Industrial, Scientific EN55011: 2016
N Dry Contact (@24VDC Self-Excitation) Harmonics IEC61000-4-7 Class A 0.001
16xDI+8xDO+2xAI+1xAO
Loading 5A @ 250VAC/30VDC and Medical (ISM) Radio-Frequency
DI Excitation 1# 110V AC/DC External Excitation K-Factor IEC61000-4-7 Class A 0.001 Equipment
Rear Panel
2# 220V AC/DC External Excitation ±0.2°

Communications A 2x100BaseT + 2xRS-485 Phase Angle SCCPA Option: 0.1° Limits and Methods of Measurement of
±0.2°+ Phase Error of SCCP Radio Disturbance Characteristics of EN55032: 2015
Time Sync. A GPS, IRIG-B Form C Relay Outputs (Alarm 1, 2, 3) Information Technology Equipment
U Unbalance ±0.1% 0.01%
Display Language E English Type Form C Mechanical Relay
I Unbalance ±0.5% 0.01% Limits for Harmonic Current Emissions
iMeter 8 - A 5 9 2 5 A N A A E iMeter 8-A5925ANAAE (Standard Model) Loading 8A @ 250VAC/24VDC EN61000-3-2: 2014
Pst, Plt 0.01% for Equipment with Rated Current ≤16 A
±5%
* Additional charges apply.
~ The I/O options "B" and "D" are not supported when the Basic Feature option "B" is selected. Limitation of Voltage Fluctuations and
^ The SCCPA option is compatible with the SCCP models listed in the "SCCP Option" sheet. This option does not come with any Current Clamp. Flicker in Low-Voltage Supply Systems EN61000-3-3: 2013
Please refer to the "SCCP Option" sheet for more information and order the desired model and quantity as a separate item. for Equipment with Rated Current ≤16 A
#
The DI Excitation options “1” and “2” are not supported when the Power Supply option “3” with 20-60VDC is selected. Pulse Outputs (E1+, E1-, E2+, E2-, E3+, E3-, E4+, E4-)
Type Form A Solid State Relay Emission Standard for Industrial
EN61000-6-4: 2007 +A1: 2011

Optional SCCPs Technical Specifications Isolation


Max. Load Voltage
Optical
30VDC
Environments

Standards of Compliance
Max. Forward Current 4mA
Voltage Inputs (V1, V2, V3, VN, V4, V4N)
Standard (Un) 400ULN/690ULL +20%
Range 1% to 200% Un for 400ULN nominal Safety Requirements
* PMC-SCCP-5kA-500mV-B-C-C- Overload 2xUn continuous, 4xUn for 1s Optional Analog Input (AI1+, AI1-, AI2+, AI2-)
Model No. PMC-SCCP-50A-500mV-B-A-B PMC-SCCP-200A-200mV-B-B-B PMC-SCCP-500A-500mV-B-B-B EN61010-1: 2010
CE LVD 2014/35/EU

iMeter 8
371/254/150/100
Burden < 0.5VA/per phase Type 0-20/4-20 mA DC EN61010-2-030: 2010
5A 20A/200A 500A 500A/5000A Rogowski Coil
Measurement Range Primary 1-1,000,000V Overload 24 mA maximum
(50A Imax) (200A Imax) (500A Imax) (5000A Imax) Electrical Safety in Low Voltage
Secondary 1-1,500V Distribution Systems up to 1000Vac IEC61557-12: 2018 (PMD)
Max. Allowable Current 50A 260A 500A 10, 000A PT Ratio
AC 10mV/A @ 20A AC 1mV/A @ 500A
V4 Primary 1-1,000,000V and 1500Vdc Side view
AC 10mV/A AC 1mV/A V4 Secondary 1-1,500V
Output Voltage AC 1mV/A @ 200A AC 0.1mV/A @ 5000A
(Max. 500mV) (Max. 500mV) Insulation
(Max. 200mV) (Max. 500mV) Frequency 40Hz-60Hz @ 50Hz, 48Hz-72Hz @ 60Hz Optional Analog Output (AO1+, AO1-, AO2+, AO2-) IEC62052-11: 2003
AC Voltage: 2kV @ 1 minute
±0.3% rdg. ±0.3% rdg. ±0.3% rdg. ±2.0% rdg. IEC62053-22: 2003
Accuracy Type 0-20/4-20 mA DC Insulation Resistance: >100MΩ
±0.02% f.s. ±0.02% f.s. ±0.02% f.s. (1% - 200%) In EN61010-1: 2010
Loading 500Ω maximum Impulse Voltage: 6kV, 1.2/50µs
CAT III 1000V
Protection CAT III 300V CAT III 600V CAT III 600V Overload 24 mA maximum
CAT IV 600V Current Inputs (I11, I12, I21, I22, I31, I32, I41, I42, I51, I52)
Diameter 15mm 24mm 50mm 371/254/150/100mm
Standard (In) 5A (Standard), 1A (Optional) Mechanical Tests
Cable Length 3m 3m 3m 3m
Range 1% to 400% In Response IEC255-2-1: 1989
Termination BNC BNC BNC BNC Vibration Test
Starting Current 0.1% In Endurance IEC255-2-1: 1989
Environmental Conditions
* The Rogowski Coil SCCP comes with an external Universal Power Supply and an integrator. Overload 4xIn continuous, 20xIn for 1s Response IEC255-2-2
Operating Temperature -25°C to 70°C Shock Test
< 0.5VA/per phase @ 5A Endurance IEC255-2-2
Burden Storage Temperature -40°C to 85°C
< 0.1VA/per phase @ 1A Bump Test IEC255-2-2
Humidity 5% to 95% non-condensing
5A/50A (In/Imax),
SCCP-50A-500mV
Atmospheric Pressure
Your Local Representative

max. 500mV Output 63 kPa to 110 kPa

20A/200A (In/Imax), Pollution Degree 2 Power Quality


SCCP-200A-200mV
SCCP Options max. 200mV Output Measurement Category CATIII 1000V
Voltage Characteristics of Electricity Supplied
SCCP-500A-500mV 500A Imax, max. 500mV Output EN50160
by Public Distribution Systems
V.00 05.07.2022

Selectable 500A/5000A (Imax)


SCCP-5000A-500mV General Guide on Harmonic and Interharmonic
Rogowski Coil, max. 500mV Output
Measurements and Instrumentation, for Power IEC61000-4-7
Primary 1-30,000A Mechanical Characteristics Supply Systems and Equipment Connected Thereto
Email: sales@cet-global.com
Secondary 1-50A
Website: www.cet-global.com CT Ratio Panel Cutout 186x186 mm Flicker Meter - Functional and Design Specifications IEC61000-4-15
I4 Primary 1-30,000A
Unit Dimensions 192x192x182.4mm Testing and Measurement Techniques-Power IEC61000-4-30 Ed. 3
Copyright © CET Inc. All rights reserved.
I4 Secondary 1-50A
IP Rating 52 Quality Measurement Methods Class A Compliant Installation
www.cet-global.com
Ordering Guide Accuracy EMC Compatibility Device Dimensions
Product Code Description Unit: mm
iMeter 8 Advanced Power Quality Analyzer Parameters Accuracy Resolution Power Supply (L+, N-) CE EMC Directive 2014/30/EU (EN61326: 2013)
A 1024 samples/cycle, 8GB On-Board Memory, IEC61000-4-30 Ed. 3 Class A Compliant Voltage (U) ±0.1% 0.001V Standard 95-250VAC/VDC ± 10%, 47-440Hz
Basic Feature ±0.1% Burden < 12W Immunity (EN50082-2)
1024 samples/cycle, 8GB On-Board Memory,
B*~ I1, I2, I3
IEC61000-4-30 Ed. 3 Class A Compliant with 2-150kHz C.E. Measurement SCCPA Option: ±01%+Error of SCCP Overvoltage Category CATIII 300V Electrostatic Discharge EN61000-4-2: 2009
0.001A
5 5A I4 ±0.1% Radiated Fields EN61000-4-3: 2006 +A1: 2008 +A2: 2010
Input Current 1 1A I5 ±0.5% Fast Transients EN61000-4-4: 2012
SCCPA^ SCCP Option for use with CT Clamps with max. 500mV output ±0.2% Surges EN61000-4-5: 2014 +A1: 2017
P, Q, S 0.001kX Digital Inputs ( DIC, DI1 to DI8 or DI16) Conducted Disturbances
VN

Input Voltage 9 400ULN/690ULL + 20% SCCPA Option: ±0.5% EN61000-4-6: 2014


V4

95-250VAC/DC ± 10%, 47-440Hz


Standard Dry contact, 24VDC internally wetted
Magnetic Fields EN61000-4-8: 2010
2 IEC62053-22 Class 0.2S V4N

Power Supply kWh, kVAh 0.1kXh Optional 110V/220V AC/DC externally wetted
3*# 20-60VDC SCCPA Option: IEC62053-21 Class 1 Voltage Dips and Interruptions EN61000-4-11: 2004+A1: 2017
50Hz
Sampling 1000Hz
Ring Wave EN61000-4-12: 2017
5 IEC62053-24 Class 0.5S
System Frequency kvarh IEC62053-23 Class 2 Hysteresis 1ms minimum
6 60Hz 0.1kvarh
A 8xDI + 4xDO + 4xSS Pulse Outputs SCCPA Option: IEC62053-24 Class 1 1

Emission (EN50081-2) 2

B*~ 8xDI + 4xDO + 2xAI + 1xAO + 4xSS Pulse Outputs ±0.2% 3

I/O PF 0.001
C* 16xDI + 8xDO + 4xSS Pulse Outputs SCCPA Option: ±0.5% Limits and Methods of Measurement of
Form A Relay Outputs (DO1 to DO3 or optional DO1 to DO7)
D*~ 8xDI + 4xDO + 2xAI + 2xAO + 2xSS Pulse Outputs Frequency ±0.003Hz 0.001Hz Electromagnetic Disturbance
Type Form A Mechanical Relay Characteristics of Industrial, Scientific EN55011: 2016
N Dry Contact (@24VDC Self-Excitation) Harmonics IEC61000-4-7 Class A 0.001
16xDI+8xDO+2xAI+1xAO
Loading 5A @ 250VAC/30VDC and Medical (ISM) Radio-Frequency
DI Excitation 1# 110V AC/DC External Excitation K-Factor IEC61000-4-7 Class A 0.001 Equipment
Rear Panel
2# 220V AC/DC External Excitation ±0.2°

Communications A 2x100BaseT + 2xRS-485 Phase Angle SCCPA Option: 0.1° Limits and Methods of Measurement of
±0.2°+ Phase Error of SCCP Radio Disturbance Characteristics of EN55032: 2015
Time Sync. A GPS, IRIG-B Form C Relay Outputs (Alarm 1, 2, 3) Information Technology Equipment
U Unbalance ±0.1% 0.01%
Display Language E English Type Form C Mechanical Relay
I Unbalance ±0.5% 0.01% Limits for Harmonic Current Emissions
iMeter 8 - A 5 9 2 5 A N A A E iMeter 8-A5925ANAAE (Standard Model) Loading 8A @ 250VAC/24VDC EN61000-3-2: 2014
Pst, Plt 0.01% for Equipment with Rated Current ≤16 A
±5%
* Additional charges apply.
~ The I/O options "B" and "D" are not supported when the Basic Feature option "B" is selected. Limitation of Voltage Fluctuations and
^ The SCCPA option is compatible with the SCCP models listed in the "SCCP Option" sheet. This option does not come with any Current Clamp. Flicker in Low-Voltage Supply Systems EN61000-3-3: 2013
Please refer to the "SCCP Option" sheet for more information and order the desired model and quantity as a separate item. for Equipment with Rated Current ≤16 A
#
The DI Excitation options “1” and “2” are not supported when the Power Supply option “3” with 20-60VDC is selected. Pulse Outputs (E1+, E1-, E2+, E2-, E3+, E3-, E4+, E4-)
Type Form A Solid State Relay Emission Standard for Industrial
EN61000-6-4: 2007 +A1: 2011

Optional SCCPs Technical Specifications Isolation


Max. Load Voltage
Optical
30VDC
Environments

Standards of Compliance
Max. Forward Current 4mA
Voltage Inputs (V1, V2, V3, VN, V4, V4N)
Standard (Un) 400ULN/690ULL +20%
Range 1% to 200% Un for 400ULN nominal Safety Requirements
* PMC-SCCP-5kA-500mV-B-C-C- Overload 2xUn continuous, 4xUn for 1s Optional Analog Input (AI1+, AI1-, AI2+, AI2-)
Model No. PMC-SCCP-50A-500mV-B-A-B PMC-SCCP-200A-200mV-B-B-B PMC-SCCP-500A-500mV-B-B-B EN61010-1: 2010
CE LVD 2014/35/EU

iMeter 8
371/254/150/100
Burden < 0.5VA/per phase Type 0-20/4-20 mA DC EN61010-2-030: 2010
5A 20A/200A 500A 500A/5000A Rogowski Coil
Measurement Range Primary 1-1,000,000V Overload 24 mA maximum
(50A Imax) (200A Imax) (500A Imax) (5000A Imax) Electrical Safety in Low Voltage
Secondary 1-1,500V Distribution Systems up to 1000Vac IEC61557-12: 2018 (PMD)
Max. Allowable Current 50A 260A 500A 10, 000A PT Ratio
AC 10mV/A @ 20A AC 1mV/A @ 500A
V4 Primary 1-1,000,000V and 1500Vdc Side view
AC 10mV/A AC 1mV/A V4 Secondary 1-1,500V
Output Voltage AC 1mV/A @ 200A AC 0.1mV/A @ 5000A
(Max. 500mV) (Max. 500mV) Insulation
(Max. 200mV) (Max. 500mV) Frequency 40Hz-60Hz @ 50Hz, 48Hz-72Hz @ 60Hz Optional Analog Output (AO1+, AO1-, AO2+, AO2-) IEC62052-11: 2003
AC Voltage: 2kV @ 1 minute
±0.3% rdg. ±0.3% rdg. ±0.3% rdg. ±2.0% rdg. IEC62053-22: 2003
Accuracy Type 0-20/4-20 mA DC Insulation Resistance: >100MΩ
±0.02% f.s. ±0.02% f.s. ±0.02% f.s. (1% - 200%) In EN61010-1: 2010
Loading 500Ω maximum Impulse Voltage: 6kV, 1.2/50µs
CAT III 1000V
Protection CAT III 300V CAT III 600V CAT III 600V Overload 24 mA maximum
CAT IV 600V Current Inputs (I11, I12, I21, I22, I31, I32, I41, I42, I51, I52)
Diameter 15mm 24mm 50mm 371/254/150/100mm
Standard (In) 5A (Standard), 1A (Optional) Mechanical Tests
Cable Length 3m 3m 3m 3m
Range 1% to 400% In Response IEC255-2-1: 1989
Termination BNC BNC BNC BNC Vibration Test
Starting Current 0.1% In Endurance IEC255-2-1: 1989
Environmental Conditions
* The Rogowski Coil SCCP comes with an external Universal Power Supply and an integrator. Overload 4xIn continuous, 20xIn for 1s Response IEC255-2-2
Operating Temperature -25°C to 70°C Shock Test
< 0.5VA/per phase @ 5A Endurance IEC255-2-2
Burden Storage Temperature -40°C to 85°C
< 0.1VA/per phase @ 1A Bump Test IEC255-2-2
Humidity 5% to 95% non-condensing
5A/50A (In/Imax),
SCCP-50A-500mV
Atmospheric Pressure
Your Local Representative

max. 500mV Output 63 kPa to 110 kPa

20A/200A (In/Imax), Pollution Degree 2 Power Quality


SCCP-200A-200mV
SCCP Options max. 200mV Output Measurement Category CATIII 1000V
Voltage Characteristics of Electricity Supplied
SCCP-500A-500mV 500A Imax, max. 500mV Output EN50160
by Public Distribution Systems
V.00 05.07.2022

Selectable 500A/5000A (Imax)


SCCP-5000A-500mV General Guide on Harmonic and Interharmonic
Rogowski Coil, max. 500mV Output
Measurements and Instrumentation, for Power IEC61000-4-7
Primary 1-30,000A Mechanical Characteristics Supply Systems and Equipment Connected Thereto
Email: sales@cet-global.com
Secondary 1-50A
Website: www.cet-global.com CT Ratio Panel Cutout 186x186 mm Flicker Meter - Functional and Design Specifications IEC61000-4-15
I4 Primary 1-30,000A
Unit Dimensions 192x192x182.4mm Testing and Measurement Techniques-Power IEC61000-4-30 Ed. 3
Copyright © CET Inc. All rights reserved.
I4 Secondary 1-50A
IP Rating 52 Quality Measurement Methods Class A Compliant Installation