IEC 61439 the standard of Low Voltage Switchgear and Controlgear
What/ Who/ Why is IEC 61439?

Who is IEC?
-The IEC or International Electrotechnical Commission (IEC) is to promote international cooperation on
electrical and electronic fields.

What’s IEC mission?


- IEC Publishes International Standards,
Technical Specifications, Technical Report,
What is IEC 61439?
Publicly Available Specification and Guilds
Publication. - IEC 61439 is a technical report for Low
Voltage Switchgear and Controlgear
Assemblies, of IEC technical committee
Why IEC 61439?
- IEC 61439 is the lasted internal standard of
LV Panel with improve from IEC 60439

Unrestricted © Siemens AG 2017


Page 2 April 2017 EM MS
History of IEC 61439.
The Original Started with Germany VDE.

Milestones of Switchboard Standards


1896 First publication of standards, rules and guidelines of the VDE
with first security rules for switching and distribution boards.

1941 VDE 0100 "Regulations on the installation of power circuits with nominal voltages below 1000V"

1958 VDE 0100 §29 N Requirements for insulation, short-circuit withstand and protection against contact with live parts.

1967 VDE 0660 part 5 factory assembled


(1973) (EN (IEC) 60439) switchgear assemblies

1973
VDE 0100 §30 b: Construction requirements for not factory
assembled switching and distribution boards

1984 VDE 0660 part 500 (TTA) type-tested switchgear and VDE 0660 part 500 (PTTA) Partially type-tested switch-
(1985) (EN (IEC) 60439-1) controlgear assemblies (EN (IEC) 60439-1) gear and controlgear assemblies
joint construction requirements

EN (IEC) 61439-1/2 New standard for power switchgear and controlgear assemblies
2009 VDE 0660-600-1/2
Unrestricted © Siemens AG 2017
Page 3 April 2017 EM MS
IEC 61439 the standard of Low Voltage Switchgear and Controlgear.
What’s New on IEC 61439 family?

IEC61439-7 Assemblies for specific IEC61439-0 Technical


applications such as Marine, Reports
Camping sites, Market squares, EV
Charging Station
IEC61439-1 General Rules

IEC61439-6 Busbar Trunking

SIVACON
System (Busways) IEC61439 IEC61439-2 Power
Switchgear and
Controlgear Assemblies

IEC61439-5 Assemblies for Power IEC61439-3 Distribution Boads


Distribution in Public Networks Intended to be Operated by
Ordinary Persons

ALPHA
IEC61439-4 Particular Requirements for
assemblies for Construction Sites (ACS)

Unrestricted © Siemens AG 2017


Page 4 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?

Reasons for the New Series of Standards EN (IEC) 61439


With the EN (IEC) 61439 the series of standards for low-voltage switchgear and controlgear assemblies
was radically revised and restructured. The main reasons for this were the following key points of criticism
about the pre norm EN (IEC) 60439:

Difficult to understand and execute.


o Grey areas leading to subjective interpretations
o Poor structured content
New Block Concept with
TTA / PTTA dilemma. Design and Routine Operate &
Verification maintain
o Misinterpreted categories
o Limited applicability
o Useless classification for end customers

EN (IEC) 60439 part 1 with double function.


o Product standard and
o General requirements for all other standards of this series Grid Electrical circuit
connection and consumers

Some manufacturer and specific market segments are ignoring the EN (IEC) 60439.

Unrestricted © Siemens AG 2017


Page 5 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
Assembly replaceability and flexible for modification.

Enclosure
1 Roof plate 6 Base
2 Rear wall 7 Base compartment cover, ventilated
3 Design side wall 8 Cubicle door, ventilated 1
Technical data
4 Frame 9 Compartment door
11 2 Structure
5 Base cover 10 Head room door
21 Door opening angle 125°,180° with
Busbars 10 stand-alone
installation
11 Main busbar (L1 ... L3, N) – top
12
12 Main busbar (L1 ... L3, N) – rear top 9 Frame height (without 2,000, 2,200 mm
13 Main busbar (L1 ... L3, N) – rear bottom base)
14 Main busbar (PE) – bottom
Base height (optional) 100, 200 mm
15 Distribution busbar (L1 ... L3, N) – device compartment 20 17
16 Distribution busbar (PE) – cable compartment 3 Degree of protection In accordance
19 16 13 with IEC 60529:
17 Distribution busbar (N) – cable compartment
18 IP30, IP31, IP40,
8 15 IP41, IP43, IP54
Internal separation
18 Device compartment/busbar compartment
Main busbars
14
19 Cubicle to cubicle 4 Rated currents up to 7,000 A
20 Compartment to compartment 7
6 Rated peak withstand up to 330 kA
21 Cross-wiring compartment
current (Ipk)
Unrestricted © Siemens AG 2017 5 Rated short-time up to 150 kA
Page 6 April 2017 withstand current (Icw) EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439-0 Technical Reports.

With the EN (IEC) 61439 the series of


standards for low-voltage switchgear and
controlgear assemblies was radically
revised and restructured.

The Purposes of IEC61439-0 are to


reduce additional technical clarification by
integrated other related standard and
closed the topic of original manufacture
certificated by “User may be original
manufacture or other manufacture on
behalf (licenses or delegated
manufacturers)”

- The IEC 61439-0 Technical Reports are identify scope of test area, definition of the
testing, Type of Installation, Storage and Handling, Maintenancee and Upgrade,
Current capability, ASSEMBLY design and routine verification processes .

Unrestricted © Siemens AG 2017


Page 7 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439-1 General Rules.

The IEC 61439-1 General Rules are


combination of over than 50 international
standard, which refer to the standards
which related to total product life cycle of
Low Voltage Switchgear and Controlgear.

The purpose of the standard to avoid the


verification to other standard with new
condition are “Tests Verifications”,
“Derivation” and “Assessment by
engineering rules”

- The IEC 61439-1 General Rules is a back bone of IEC 61439 standard, because it
have identify term and definitions of Low Voltage Switchgear and Controlgear,
Symbols and abbreviations, Test Limitation, Definition of Tests Verification,
Derivation and Assessment.
Unrestricted © Siemens AG 2017
Page 8 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439-1 General Rules.
Forms of internal separation

Unrestricted © Siemens AG 2017


Page 9 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439-1 General Rules.
Forms of internal separation

Unrestricted © Siemens AG 2017


Page 10 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439-1 General Rules.
Forms of internal separation

Unrestricted © Siemens AG 2017


Page 11 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439-1 General Rules.
Forms of internal separation

Unrestricted © Siemens AG 2017


Page 12 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439-1 General Rules.
Forms of internal separation

Unrestricted © Siemens AG 2017


Page 13 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
Black Box Concept.
Design and Routine Verification

Design verification
“Verification made on a sample of an assembly or on parts of assemblies to show that the design meets the requirements of the relevant assembly standard”
[EN (IEC) 61439-1; 3.9.1].

Design verifications can be provided by the following equal methods:

Testing Derivation Assessment


Electrical, mechanical comparison with a tested Checking calculation and
and thermal reference design design rules

⇓ The manufacturer is in charge to choose the allowed verification options

“Design verifications” are replacing and extending “type tests”.

Routine verification
Verification about the compliance to the relevant assembly standard which has to be performed for every completed assembly.

“Routine verifications” are replacing “routine tests” without significant changes.

Unrestricted © Siemens AG 2017


Page 14 April 2017 EM MS
EN (IEC) 61439-1/2
The new standard for
low-voltage power switchgear and controlgear assemblies

Allowed Alternatives for Design Verifications


Chapter Characteristic to be verified Verification options available
Testing Derivation Assessment
10.2 Strength of material and parts
10.2.2 Resistance to corrosion Yes No No
10.2.3 Properties of insulating materials
10.2.3.1 Thermal stability Yes No No
10.2.3.2 Resistance to abnormal heat and fire due to internal electric effects Yes No Yes
10.2.4 Resistance to ultra-violet (UV) radiation Yes No Yes
a) Construction

10.2.5 Lifting Yes No No


10.2.6 Mechanical impact Yes No No
10.2.7 Marking Yes No No
10.3 Degree of protection ofenclosures Yes No Yes
10.4 Clearance and Creepage distances Yes No No
10.5 Protection against electric shock and integrity of protective circuits
10.5.2 Effective continuity between the exposed conductive parts of the assembly and the protective circuit Yes No No
10.5.3 Short-circuit withstand strength of the protective circuit Yes Yes No
10.6 Incorporation of switching devices and components No No Yes
10.7 Internal electrical circuits and connections No No Yes
10.8 Terminals for external conductors No No Yes
10.9
b) Performance

Dielectric properties
10.9.2 Power-frequency withstand voltage Yes No No
10.9.3 Impulse withstand voltage Yes No Yes
10.10 Temperature-rise limits Yes Yes Yes /No
10.11 Short-circuit withstand strength Yes Yes/No No
10.12 Electromagnetic compatibility (EMC) Yes No Yes
10.13 Mechanical operation Yes No No

Unrestricted © Siemens AG 2017


Page 15 April 2017 EM MS
EN (IEC) 61439-1/2
The new standard for
low-voltage power switchgear and controlgear assemblies

Allowed Alternatives for Design Verifications


Temperature-rise limits

Testing Derivation Assessment


Derivation from similar Assessment via calculation allowed for InA ≤ 1600A.
variants of tested designs.
[EN (IEC) 61439-1; 10.10.3]

For InA > 1600A temperature-rise verifications according to EN (IEC) 61439 have to be provided by testing and derivations; assessments via
calculation are only allowed for assemblies up to 1600A.

Short-circuit withstand strength

Testing Derivation

Only if the worst variant of an assembly was tested, the results of these tests can
be used for verification of favorably variants by derivation.

The short-circuit withstand strength according to EN (IEC) 61439 can be certificated by derivation for parts of an assembly if the worst variant
was tested before.
Unrestricted © Siemens AG 2017
Page 16 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439 Black Box Concept.

Installation and ambient conditions


o Existing grid system (TN-C, TN-C-S, ‚TN-S, TT, IT)
o Degree of pollution
Installation and ambient
o Indoor and / or outdoor installation
conditions
o Stationary or non-stationary switchgear and controlgear
assemblies
o Degree of protection (IP)
o Electromagnetic compatibility (EMC)
Operate & o Special operating conditions
maintain (e.g. extreme thermal, atmospheric und climatic impacts, ...)

o External design
(open / closed design, panel design, cubicle design, ...)

o Protection against mechanical impacts (IK code)


o Structural type (Inserts or removable components)
o Total mass and if required masses of components (Transport)
Grid Electrical circuit
connection and consumers o Dimensions and type of installation
(free standing, wall installation, side by side, …)

Unrestricted © Siemens AG 2017


Page 17 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439 Black Box Concept.

Grid connection
o Rated voltage of the assembly Un
Installation and ambient
o Rated frequency fn
conditions
o Rated operating voltage Ue
o Measures for protection against electric shock
(Protection class)

o Rated Current of the Assembly InA


Operate &
maintain o Rated impulse withstand voltage Uimp
o Rated peak withstand current Ipk
o Rated short-time withstand current Icw
o Rated conditional short-circuit current Icc
o Amount and Type of supply lines
Grid Electrical circuit (Single-conductor or multi-conductor cables , cross-section, conductor
connection and consumers
material, connection type)

Unrestricted © Siemens AG 2017


Page 18 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439 Black Box Concept.

Installation and ambient


conditions
Electrical circuit and consumers
o Rated insulation voltage Ui
o Rated current of a circuit InC
o Rated diversity factor RDF
Operate &
maintain Operate & maintain
o Intended operating personal
(Expert, layperson)

o Device operation
(e.g. behind the door, from outside, …)

o Door locking system


Grid Electrical circuit (Locking handle, knob, with or without lock, …)
connection and consumers

Unrestricted © Siemens AG 2017


Page 19 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439 Black Box Concept.
Constructional and Performance Requirements

Partition of the previous chapter “constructional requirements” in the chapters “constructional requirements“
and “performance requirements“ with single changes.

“7 Constructional requirements“

“8 Constructional requirements“ “9 Performance requirements“


8.1 Strength of materials and parts 9.1 Dielectric properties
8.2 Degree of protection provided by an assembly 9.2 Temperature rise limits
enclosure 9.3 Short-circuit protection and
8.3 Clearances and creepage distances short-circuit withstand strength
8.4 Protection against electric shock 9.4 Electromagnetic compatibility (EMC)
8.5 Incorporation of switching devices and components
8.6 Internal electrical circuits and connections
8.7 Cooling
8.8 Terminals for external conductors

Requirements for strength of materials and parts adopted from the standard for empty enclosures
EN (IEC) 62208.

Unrestricted © Siemens AG 2017


Page 20 April 2017 EM MS
EN (IEC) 61439-1/2
The new standard for
low-voltage power switchgear and controlgear assemblies

Constructional Requirements
Changes
8.1 Strength of materials and parts
Adopted requirements from the standard for empty enclosures EN (IEC) 62208
o Corrosion resistance o UV Resistance of enclosure parts made of insulating material for outdoor
o Thermal resistance of enclosure parts installation
made of insulating material o Protection against mechanical impacts (IK code)
o Ability for transportation (lifting)

8.2.2 Protection against contact with live parts, ingress of solid foreign bodies and water
IPX2 is not applicable for fixed mounted assemblies which are not tilted in normal operation conditions.

8.4 Protection against electric shock


Adoption of new terminologies and requirements from the Previous terms Replaced by
fundamental safety standards:
“Protection against direct contact“ “Basic protection“
“Protection against indirect contact“ “Fault protection“

8.6.1 Main circuits


Minimum cross-section for neutral conductor: 50% of phase cross-sections and not smaller than 16 mm².

Unrestricted © Siemens AG 2017


Page 21 April 2017 EM MS
EN (IEC) 61439-1/2
The new standard for
low-voltage power switchgear and controlgear assemblies

Routine Verifications
Dielectric test
New test voltage versus EN (IEC) 60439-1.

Test period 1s Test voltage


Rated insulation voltage Ui Test voltage
Voltage source 500VA, AC, 45-65Hz, ≥ 200 mA (line to line) a.c. - r.m.s.
[V] [V]
Ui ≤ 60 1000
60 < Ui ≤ 300 1500
300 < Ui ≤ 690 1890
690 < Ui ≤ 800 2000
800 < Ui ≤ 1000 2200

⇓ Please check the setting possibilities of your test equipment according to the new test parameters for routine verifications.

Unrestricted © Siemens AG 2017


Page 22 April 2017 EM MS
EN (IEC) 61439-1/2
The new standard for
low-voltage power switchgear and controlgear assemblies

Assembly Designation Marking


Type label Type label example of the Siemens AG
The assembly manufacturer has to provide each assembly with at least one
durable label, which is visible when the assembly is installed and in operation.
These labels have to include at least the following information:

Assembly manufacturer's name or trade mark

Type designation or other identification


For requesting information about the assembly from the assembly
manufacturer.

Designation to identify the date of manufacturing

Relevant assembly standard


EN (IEC) 61439-2

Unrestricted © Siemens AG 2017


Page 23 April 2017 EM MS
SIVACON IEC 61439 Low Voltage and Switchgear and Control Panel.
Original Manufacture and Partner Program.
Product and Verification Responsibility

Distinction between „original manufacturer“ and „assembly manufacturer“

Original manufacturer (Siemens AG) Assembly manufacturer (Partner)


„Organization that has carried out the original design and the „Organization taking the responsibility for the completed
associated verification of an assembly in accordance with the assembly“ [EN (IEC) 61439-1; 3.10.2].
relevant assembly standard“ [EN (IEC) 61439-1; 3.10.1].

Design verification Changes on the original system


Testing Derivation Assessment Design verifications for changes

Routine verification

Assembly / original system Ready-for-use assembly


SIVACON

SIVACON
S8 / 8PT

S8 / 8PT

Unrestricted © Siemens AG 2017


Page 24 April 2017 EM MS
IEC 61439-3, 4, 5, 7.
-3 DB Panel, -4 ACS, -5 PENDA and -7 Specific Application.

Unrestricted © Siemens AG 2017 siemens.com/sivacon-S8


IEC 61439-3 Distribution boards intended to be operated by ordinary
persons (DBO)
LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR ASSEMBLIES,
Part 3.

o Rated voltage to earth does not exceed 300 V a.c.


o Rated current (Inc) of the outgoing circuits does not exceed 125 A
and the rated current (InA) of the DBO does not exceed 250 A.
o DBO ASSEMBLY used to distribute electrical energy in domestic
(household) applications and other places where operation is
intended by ordinary persons.
o Single Pole (Type A) or Multi Poles (Type B).
o The DBO shall comply IK05 for indoor and IK07 for out door.
o Rated diversity factor (RDF) for testing pocedure.

Unrestricted © Siemens AG 2017


Page 26 April 2017 EM MS
IEC 61439-4 Part 4: Assemblies for Construction Sites (ACS)

Part 4: Particular requirements for assemblies for


construction sites (ACS)

o ASSEMBLIES intended for use on construction sites,


both indoors and outdoors
o Transportable (semi-fixed) or mobile ASSEMBLIES
with enclosure.
o Requirements for protection provided by equipment
manufactured, following IEC 60364-7-704.
o ACS designation marking
o Protection against corrosion, ultra-violet radiation,
Mechanical strength and mechanical impact.
o Minimum IP rating at IP44. Operation in side door
minimum IP 21.
o Rated diversity factor (RDF) for testing procedure.
o

Unrestricted © Siemens AG 2017


Page 27 April 2017 EM MS
IEC 61439-4 Part 4: Assemblies for Construction Sites (ACS)

Part 4: Particular requirements for assemblies for


construction sites (ACS)
o Verification of resistance to corrosion in a heavily
polluted atmosphere.
o 6 cycles of 24h damp heat (40C) with 95%
humidity following IEC 60068-2-30 and 2 cycles
of salt mist test accounting to IEC60068-2-11, for
Indoor.
o 5 cycles of 24h damp heat (40C) with 95%
humidity following IEC 60068-2-30 and 7 cycles
of salt mist test accounting to IEC60068-2-11, for
Indoor.

o Verification of mechanical strength.


o Impact Test of 6 joules apply to enclose.
o Shock test at 500m/sq.S (50g) with duration
11ms.
o Metering Devices, SPD compatibility.

Unrestricted © Siemens AG 2017


Page 28 April 2017 EM MS
IEC 61439-5 Part 5: Assemblies for power distribution in public
networks.

Part 5: Assemblies for power distribution in public networks

o Minimum IP 34D for out door location, other IP 33 and above.


o Individual components, such as fuses and switching devices that
are in compliance with others standards, shall also comply with
the supplementary requirements of this standard.
o Marking as an obstacle to snow clearance
o Damp Heat, Dry heat test (100C over period 2-3h)
o Mechanical strength resistant of shock load, static load and torsional
load but no impact tested.
o Verification of Impact Force withstand.
o Impact energy 20J (2kg mass at 1 m).
o PENDA-O having a door(s) hinge with load of 50 N shall be
applied at the top edge of the door at a distance 300 mm from
the hinged edge and maintained for 3 s.

The object of this standard is to state the definitions and to specify the
service conditions, construction requirements, technical characteristics
and tests for PENDAs. Network parameters may require tests at higher
performance levels.
Unrestricted © Siemens AG 2017
Page 29 April 2017 EM MS
IEC 61439-5 Part 5: Assemblies for power distribution in public
networks.

Unrestricted © Siemens AG 2017


Page 30 April 2017 EM MS
IEC 61439-5 Part 5: Assemblies for power distribution in public
networks.

Unrestricted © Siemens AG 2017


Page 31 April 2017 EM MS
IEC 61439-5 Part 5: Assemblies for power distribution in public
networks.

Part 5: Assemblies for power distribution in public networks

Verification of resistance to mechanical


shock impacts induced by sharpedged
objects (only PENDA-O)

o Impact energy of 20 from 5kg load at


0.4m height drop. Compliance is
checked by inspection that cracks
resulting from the blows are contained
within a circle of diameter not
exceeding 15 mm.

Test of mechanical strength of a base


intended to be embedded in the
ground.

Verification of resistance to static load

Unrestricted © Siemens AG 2017


Page 32 April 2017 EM MS
IEC 61439-7 Assemblies for specific applications such as marinas,
camping sites, market squares, electric vehicles charging stations.

LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR ASSEMBLIES,


Part 7: Spacific Applications.

Respectively in marinas and similar locations (AMHS), camping sites and similar Typical of application:
locations (ACCS), market squares and other similar external public sites (AMPS), o ASSEMBLY for Marinas and harbors sites (AMHS).
charging stations (ACSEV). The term ASSEMBLIES is used for indicating all the
boards. o ASSEMBLY for Camping and Caravan Sites (ACCS).
o Stationary or movable with enclosure which operated by ordinary persons. o ASSEMBLY for Markets and other external public sites
o Combination test requirements as IEC 61439-5 PENA-O. (AMPS)
Protection against electric shock o ASSEMBLY for Electric Vehicles Charging Station
(ACSEV), EV conductive charging system in IEC 61851-
o Electrical separation 1 are included.
o Protection against overcurrent
o Protection against electric shocks. Installation Condition:
o Socket-outlets general. o AMHS, IEC 60364-7-709.
Supports and securing devices of ASSEMBLY o ACCS, IEC 60364-7-708.
o Protection against electric shocks. o AMPS , IEC 60364-7-740.
o Socket-outlets. o ACSEV , IEC 60364-7-722.
o Water and other fluid systems

Unrestricted © Siemens AG 2017


Page 33 April 2017 EM MS
SIVACON S8 low-voltage switchboard –
The solution for high seismic requirements and vibrations

Safe solution even for regions at risk from


earthquakes, or areas of application with high
mechanical stress, e.g. due to large (ship) drives.
Protection for people and plant

Your benefit
• Safety for people and plant by means of tests according
to IEC 61439-2/ -7
• Safe power supply with earthquake-tested version for
seismic requirements
• Certifications for application on ships and offshore
platforms

Unrestricted © Siemens AG 2017


Page 34 April 2017 EM MS
SIVACON S8‘s answers to today‘s and tomorrow‘s challenges

SIVACON S8 switchboards for …

… an intelligent data and process management

… a safe power distribution

… a flexible and scalable power distribution

Unrestricted © Siemens AG 2017


Page 35 April 2017 EM MS
SIVACON S8‘s answers to today‘s and tomorrow‘s challenges –
Power monitoring and condition monitoring

Communication-capable components
SIMARIS control –
• Future-proof integration into building Control system central switchboard operating
and industrial automation systems and monitoring system

• Increased operational transparency


• Monitoring of energy flows
• Remote control
• Identifying potential savings

Unrestricted © Siemens AG 2017


Page 36 April 2017 EM MS
SIVACON S8‘s answers to today‘s and tomorrow‘s challenges –
SIMARIS control – The digital twin

SIMARIS control – the diagnostics station,


for reliable and transparent operation

• Uniform operation, monitoring, parameterization


• Continuous monitoring and preventive maintenance by
means of diagnostics data
• Identification of saving potentials thanks
Intelligent switchboard
to transparency of power flows
SIMARIS control
• Integration in higher-level automation systems and PROFINET
Power
cloud based solutions like MindSphere Visualization
management PROFIBUS DP
Modbus RTU

Control Maintenance 3VA-line

Intelligent switching, protection, Additional sensors


control and measuring devices e.g. temperature

Unrestricted © Siemens AG 2017


Page 37 April 2017 EM MS
IEC 61641 Low-voltage switchboard –
Safety as an integral part – Arc resistance

The arc barrier restricts the effects to Insulated main busbars prevent the Tests under conditions of arcing in
one cubicle in case of arcing occurrence of arcing accordance with IEC/TR 61641

Unrestricted © Siemens AG 2017


Page 38 April 2017 EM MS
The special feature package directly from Siemens –
Safe power distribution

Erweiterter
Extended Störlichtbogenschutz
protection against internal arcing Höhere Leistungen
Real Time Temperature Monitoring to ensure
for increased personnelund
für erhöhte Personen- and switchboard durch energieeffiziente Kühlung
high plant availability with intelligent
Anlagensicherheit
safety technology

• Short-circuit strength of 100 kA • Infrared temperature sensor


up to 690 V • Temperature sensor for
• Continuous self-supervising condition contact-free temperature
monitoring of the system acquisition
• No explosive substances needed; • No voltage supply required
activation via Thomson Coil for the sensor
• Reusability – two full-load operations at • Maintenance-free sensor with
fault conditions with easy reset life-long calibration
mechanism • Data cards for several
• Testable – up to 100 test cycles sensors with communication
• Special arcing schemes interface

Unrestricted © Siemens AG 2017


Page 39 April 2017 EM MS
SIVACON S8 low-voltage switchboard –
Proven technology goes digital

High level of safety and reliability

High level of cost-efficiency due to high system flexibility

Efficient planning support with the SIMARIS software tools and the new BIM models

Condition monitoring and high level of transparency

Future-proof diagnostics station with SIMARIS control

Basis for asset management and cloud services like MindSphere

Unrestricted © Siemens AG 2017


Page 40 April 2017 EM MS
SIVACON S8 low-voltage switchboard –
Competitive, flexible and fast planning

Efficient planning with the SIMARIS tools


including Building Information Modeling data (BIM))

SIMARIS design

SIMARIS project

SIMARIS configuration

Data for Building Information Modeling BIM

Unrestricted © Siemens AG 2017


Page 41 April 2017 EM MS
SIVACON S8 low-voltage switchboard –
Support – Optimize your time with Siemens

Broad offering for SIVACON S8 low-voltage switchboard


www.siemens.com/sivacon-S8

Comfortable planning with the SIMARIS tools


www.siemens.com/simaris

Comprehensive range of specification texts


www.siemens.com/specifications

Technical documentation on the Internet


www.siemens.com/lowvoltage/product-support

TIP Consultant Support for planning and conception of electrical power distribution
systems www.siemens.com/siemens.de/tip-cs
Customer Support Center, e-mail: support.energy@siemens.com

Courses for a sound basis


www.siemens.com/lowvoltage/training

Unrestricted © Siemens AG 2017


Page 42 April 2017 EM MS
SIVACON S8 low-voltage switchboard –
Thank you very much for your attention!

Thank you.
Mr. Passapong Vidhyarkorn
Siemens EM LP, Thailand.
Email : PassapongV@siemens.com
Call : +66-91-576-0958.
+66-81-544-5536.
Subject to changes and errors. The information given in this document only contains general descriptions and/or performance features which may
not always specifically reflect those described, or which may undergo modification in the course of further development of the products. The requested
performance features are binding only when they are expressly agreed upon in the concluded contract.
All product designations, product names, etc. may contain trademarks or other rights of Siemens AG, its affiliated companies or third parties.
Their unauthorized use may infringe the rights of the respective owner.

siemens.com/sivacon-S8

Unrestricted © Siemens AG 2017


Page 43 April 2017 EM MS

You might also like