Configuration
PACiS Technical Training Level 2
CS&P – Support Team

PCL
• Content

 GHU Board Configuration


 Bitmaps configuration
 LCD configuration
 LED assignment

Schneider Electric - CS&P – C264 LHMI Configuration – E01 2


• Content

 GHU Board Configuration


 Bitmaps configuration
 LCD configuration
 LED assignment

Schneider Electric - CS&P – C264 LHMI Configuration – E01 3


• Configure the GHU board
1) C264 with or without LCD => 2 possible GHU boards

2) GHU attributes

HMI Type :
- Simple : no LCD and LED#4 is not
configurable
- Complete : LCD, LED#4 is configurable and
GHU should be linked to a graphic object
typed Computer Workspace

Schneider Electric - CS&P – C264 LHMI Configuration – E01 4


• GHU Board Sons & Relations

Board status MPS

Set of LED :
LED#4 not configurable if GHU type = Simple

Relation with graphic configuration :


Completed if GHU type = Complete

Schneider Electric - CS&P – C264 LHMI Configuration – E01 5


• Content

 GHU Board Configuration


 Bitmaps configuration
 LCD configuration
 LED assignment

Schneider Electric - CS&P – C264 LHMI Configuration – E01 6


• What for?
1) On C264 LCD, in bay panels
= > Single Line Diagrams
- static objects (lines, bitmaps)
- animated objects

2) Graphic table for bitmaps (up to 150)

Note : Starting database is containing bitmap table (IEC)

Schneider Electric - CS&P – C264 LHMI Configuration – E01 7


• Bitmap Attributes

Short Name :
Rule : put bitmap index in prefix
Bitmap index :
Bitmap index = bitmap identification used at
LCD configuration level

Bitmap type :
-5-uple = animated
-single = non-animated

Schneider Electric - CS&P – C264 LHMI Configuration – E01 8


• Bitmap Representation (1)

Default
Open*
Closed*

* associated
information in
Closed/Set or
Open/Reset state

Note : bitmap max size = 64x64 pixels


Schneider Electric - CS&P – C264 LHMI Configuration – E01 9
• Bitmap Representation (2)

Withdrawn Withdrawn
Default Open Closed
Open Closed
Note : withdrawn = combination of DPS position + withdrawn SPS
Schneider Electric - CS&P – C264 LHMI Configuration – E01 10
• Content

 GHU Board Configuration


 Bitmaps configuration
 LCD configuration
 LED assignment

Schneider Electric - CS&P – C264 LHMI Configuration – E01 11


• Add / Configure a Computer Workspace
1) Graphic Part / Computer Workspace

2) Attributes

Short Name

L/R password protection :


Operator has to enter password when
changing bay control mode (Local/Remote)

Schneider Electric - CS&P – C264 LHMI Configuration – E01 12


• Add / Configure a Bay Mimic
1) Graphic Part / Computer Workspace

2) Attributes

Short Name
MV bargraph :
Horizontal / Vertical
Advise to not use
Module Name display

3) Relations => relation with the represented bay

Mimic rank :
one bay can be represented on 1 or 2
mimics

Schneider Electric - CS&P – C264 LHMI Configuration – E01 13


• Add Graphic Objects in Bay Mimic (1)
1) Typical Bay Mimic (128x128 pixels)

Time :
optional

Mandatory :
- Bay L/R
- Interlock bypass (local activation)
- Synchrocheck bypass (local activation)

Controllable devices :
- LHMI Gen Modules
- up to 9 per mimic

Static graphics :
lines, single bitmaps

Note : no graphics outside of area => C264 failure


Schneider Electric - CS&P – C264 LHMI Configuration – E01 14
• Add Animated Objects in Bay Mimic (2)
2) Add a LHMI Gen Module

3) Configure a LHMI Gen Module

Short Name :
different from displayed name

Control availability :
Yes = controllable from LCD
4) LHMI Gen Module Sons
Graphic object with datapoint relation
is managed by SPS or DPS

Displayed name
4 characters
Representing bitmap index

Schneider Electric - CS&P – C264 LHMI Configuration – E01 15


• Add Animated Objects in Bay Mimic (3)
5) Add a LHMI Transformer

6) LHMI Transformer configuration

Graphic object with TPI relation


is managed by TPI

Minimum, Current and


Maximum TPI values
are mandatory

Bitmap index

Schneider Electric - CS&P – C264 LHMI Configuration – E01 16


• Content

 GHU Board Configuration


 Bitmaps configuration
 LCD configuration
 LED assignment

Schneider Electric - CS&P – C264 LHMI Configuration – E01 17


• Reminder
1) LED can be animated by SPS or DPS status

13 available LED for Complete HMI


12 available LED for Simple HMI (LED#4 = C264 Local/Remote)

LED can be :
- Off
- On
- Blinking fast
- Blinking slow

Schneider Electric - CS&P – C264 LHMI Configuration – E01 18


• Assign a SPS/DPS to LED
1) Under SPS, add the relation “has state displayed on LED”

2) Complete the relation

Complete the relation


by selecting LED of
the GHU board

Schneider Electric - CS&P – C264 LHMI Configuration – E01 19


• Assign a SPS/DPS to LED
3) Configure the relation for behaviour of LED :

LED Behaviour :
- For status
- For alarm

LED Behaviour per status :


Closed / OPEN / Invalid behaviour
Off / On / Blinking Slow / Blinking Fast

LED Behaviour for alarm :


Off / On / Blinking Slow / Blinking Fast

Note 1 : 1 LED represents only 1 datapoint

Note 2 : behaviour for alarm will depend on alarm


definition in datapoint profile of this DP.
Schneider Electric - CS&P – C264 LHMI Configuration – E01 20