You are on page 1of 19

MiCOM P443 Programmable Logic

Opto Input Mappings

CB OPEN
DDB #034

CB CLOSE
DDB #035

CB Aux 3ph(52-B)
DDB #424

CB Aux 3ph(52-A)
DDB #420

LINE VT MCB TRIP


DDB #036

MCB/VTS
DDB #438

SOTF INIT LO&REM


DDB #037

Init Close CB
DDB #440

SPARE
DDB #038

External Trips:
Initiate Breaker Fail,
and Autoreclose (if
enabled).

CB Healthy
DDB #436

WEAK FEED
DDB #040

SPRAE
DDB #041

AR Enable
DDB #1384

SPARE
DDB #042

SPARE
DDB #043

Block CB AR
DDB #448

DIST RECV
DDB #044

Aided1 Scheme Rx
DDB #493

DEF RECV
DDB #045

Aided2 Scheme Rx
DDB #507

Trip Outputs are


generated by the
internal single/thre
phase trip
conversion logic

Block Zone 1 Gnd


DDB #384
Block Zone 1 Phs
DDB #385

BLOCK DIST/DEF
DDB #039

Block Zone 2 Gnd


DDB #386
Block Zone 2 Phs
DDB #387
Block Zone 3 Gnd
DDB #388
Block Zone 3 Phs
DDB #389
Block Zone P Gnd
DDB #390
Block Zone P Phs
DDB #391
Block Zone 4 Gnd
DDB #392
Block Zone 4 Phs
DDB #393
Inhibit IN>1
DDB #467

0
SPARE
DDB #004

Pick-Up
0

Page 1

ee

MiCOM P443 Programmable Logic


Output Contacts

Zone 1 Trip
DDB #608

Aid 1 Dist Trip


DDB #503

ZONE1 OPTD
DDB #017

Straight
0

Aid 2 Dist Trip


DDB #519

0
Zone 2 Trip
DDB #613

ZONE2 OPTD
DDB #018

Straight
0

0
Zone 3 Trip
DDB #618

ZONE3 OPTD
DDB #019

Straight
0

Zone 4 Trip
DDB #628

ZONE4&P OPTD
DDB #021

Straight

Zone P Trip
DDB #623

0
Aid 1 DEF Trip
DDB #505

DEF TRIP
DDB #023

Straight
0

WEAK FEED
DDB #040
Aided 1 Receive
DDB #494

&

WEAK FEED
DDB #040
Aided 2 Receive
DDB #508

DIST WEI ECHO


DDB #026

Straight

&

DEF WEI ECHO


DDB #028

Straight
0

.
Zone P A Start
DDB #753
Zone P B Start
DDB #754

DIST REV START


DDB #030

Straight

Zone P C Start
DDB #755

Zone P N Start
DDB #756

0
DEF Reverse
DDB #997

DEF REV START


DDB #031

Straight
0

Trip Output A
DDB #523
Trip Output B
DDB #524

0
AR INITIATION
DDB #003

Straight
Trip Output C
DDB #525

AR 3pole in prog
DDB #844
AR 1pole in prog
DDB #845

CB Succ 3P AR
DDB #852
CB Succ 1P AR
DDB #1571

Latching

FnKey LED6 Red


DDB #1050
FnKey LED6 Grn
DDB #1051

1
0

A/R Lockout
DDB #306
AR Blocked
DDB #859
AR In Service
DDB #1385

AR BLOCK
DDB #006

Straight
0

Page 2

MiCOM P443 Programmable Logic


Output Contacts

SG-opto Invalid
DDB #288
Prot'n Disabled
DDB #289
Static Test Mode
DDB #290
Test Loopback
DDB #291
Test IM64
DDB #292
VT Fail Alarm
DDB #293
CT Fail Alarm
DDB #294
Power Swing
DDB #297
CB Fail Alarm
DDB #298
CB Monitor Alarm
DDB #299
CB Mon LO Alarm
DDB #300
CB Status Alarm
DDB #301
CB Trip Fail
DDB #302
CB Close Fail
DDB #303
Man CB Unhealthy
DDB #304
No C/S Man Close
DDB #305
A/R Lockout
DDB #306

A/R CB Unhealthy
DDB #307
A/R No Checksync
DDB #308

General Alarm

Signalling Fail
DDB #311
IM64 SchemeFail
DDB #314
IEEE C37.94 Fail
DDB #315
Aid 1 Chan Fail
DDB #317
Aid 2 Chan Fail
DDB #318
F out of Range
DDB #319
InValid Mesg Fmt
DDB #333
Main Prot. Fail
DDB #334
Comms Changed
DDB #337
Battery Fail
DDB #352
Field Volts Fail
DDB #353
Max Prop. Alarm
DDB #338
Backup Usr Curve
DDB #371

Page 3

MiCOM P443 Programmable Logic


Output Contacts
0
Aided 1 Send
DDB #498

DIST SEND
DDB #000

Straight
0
0

Aided 2 Send
DDB #514

DEF SEND
DDB #001

Straight
0

Zone 1 Trip
DDB #608
Aid 1 Dist Trip
DDB #503

INST TRIP
DDB #002

Straight
0

Aid 1 DEF Trip


DDB #505

SOTF Trip Zone 1


DDB #709

LED6 Red
DDB #1034

Latching

LED6 Grn
DDB #1035

SOTF Trip Zone 2


DDB #710
SOTF Trip Zone 3
DDB #711

SOTF TRIP
DDB #024

Straight
0

SOTF Trip Zone 4


DDB #712
SOTF Trip Zone P
DDB #713

Zone 2 Trip
DDB #613
Zone 3 Trip
DDB #618

Zone 4 Trip
DDB #628

DELAYED TRIP
DDB #007

Straight

Zone P Trip
DDB #623

I>1 Trip
DDB #655
I>2 Trip
DDB #659
IN>1 Trip
DDB #671

1
0

IN>2 Trip
DDB #672

AIDED TRIP
DDB #022

Straight
0

Aid 1 Dist Trip


DDB #503

0
Aid 2 DEF Trip
DDB #521

CARR AIDED TRIP


DDB #015

Straight
0

0
Any Trip
DDB #522

GENERAL TRIP
DDB #020

Straight
0
0

Power Swing
DDB #297

PSB OPTD
DDB #029

Pick-Up
0

0
Aid1 WI Trip 3Ph
DDB #642

DIST WEI TRIP


DDB #025

Straight
0
0

Aid2 WI Trip 3Ph


DDB #652

DEF WEI TRIP


DDB #027

Straight
0

Page 4

MiCOM P443 Programmable Logic


LEDs

Any Trip
DDB #522

Latching

Zone 1 Trip
DDB #608

Latching

Zone 2 Trip
DDB #613
Zone 3 Trip
DDB #618

Zone P Trip
DDB #623

Zone 4 Trip
DDB #628

Latching

Latching

Aided 1 Receive
DDB #494

Latching

Aided 2 Receive
DDB #508

Latching

Aided 1 Send
DDB #498

Latching

Aided 2 Send
DDB #514

Latching

AR Blocked
DDB #859

Latching

P Swing Detector
DDB #1014

Power Swing
DDB #297
I>1 Trip
DDB #655

IN>1 Trip
DDB #671

Latching

Latching

I>2 Trip
DDB #659

LED2 Red
DDB #1026
LED2 Grn
DDB #1027
LED3 Red
DDB #1028
LED3 Grn
DDB #1029
LED4 Red
DDB #1030
LED4 Grn
DDB #1031
LED5 Red
DDB #1032
LED5 Grn
DDB #1033

FnKey LED1 Red


DDB #1040
FnKey LED1 Grn
DDB #1041

FnKey LED2 Red


DDB #1042
FnKey LED2 Grn
DDB #1043

FnKey LED3 Red


DDB #1044
FnKey LED3 Grn
DDB #1045

FnKey LED4 Red


DDB #1046
FnKey LED4 Grn
DDB #1047

FnKey LED5 Red


DDB #1048
FnKey LED5 Grn
DDB #1049

FnKey LED8 Red


DDB #1054
FnKey LED8 Grn
DDB #1055
LED7 Red
DDB #1036
LED7 Grn
DDB #1037

IN>2 Trip
DDB #672

VT Fail Alarm
DDB #293

Latching

LINE VT MCB TRIP


DDB #036

Aid1 WI Trip 3Ph


DDB #642

Non Latching

FnKey LED7 Red


DDB #1052
FnKey LED7 Grn
DDB #1053

FnKey LED9 Red


DDB #1056
FnKey LED9 Grn
DDB #1057

Aid2 WI Trip 3Ph


DDB #652

Any Trip
DDB #522

Fault REC TRIG


DDB #702

Page 5

Non Latching

FnKey LED10 Red


DDB #1058
FnKey LED10 Grn
DDB #1059

MiCOM P443 Programmable Logic


Zone 1 A Start
DDB #741

Start Phase Mappings.


Used in Fault Record &
on LCD Display

Zone 2 A Start
DDB #745

Zone 3 A Start
DDB #749

Zone P A Start
DDB #753

Zone 4 A Start
DDB #757

Started Phase A
DDB #956

I>1 Start A
DDB #762

DIST PH-A START


DDB #008

Pick-Up
0

I>2 Start A
DDB #766

Caution: Do Not
remove "Started
Phase" DDB
signals

I>3 Start A
DDB #770

I>4 Start A
DDB #774

Zone 1 B Start
DDB #742

Any Phase Start >> page7

Zone 2 B Start
DDB #746

Zone 3 B Start
DDB #750

Zone P B Start
DDB #754

Zone 4 B Start
DDB #758

Started Phase B
DDB #957

I>1 Start B
DDB #763

DIST PH-B START


DDB #009

Pick-Up
0

I>2 Start B
DDB #767

I>3 Start B
DDB #771

I>4 Start B
DDB #775

Zone 1 C Start
DDB #743

Zone 2 C Start
DDB #747

Zone 3 C Start
DDB #751

Zone P C Start
DDB #755

Zone 4 C Start
DDB #759

I>1 Start C
DDB #764

Started Phase C
DDB #958

0
DIST PH-C START
DDB #010

Pick-Up
I>2 Start C
DDB #768

I>3 Start C
DDB #772

I>4 Start C
DDB #776

Page 6

MiCOM P443 Programmable Logic


Zone 1 N Start
DDB #744

Any Ground Start >> page8

Zone 2 N Start
DDB #748

Zone 3 N Start
DDB #752

>>

>>

Zone P N Start
DDB #756

Zone 4 N Start
DDB #760

IN>1 Start
DDB #777

IN>2 Start
DDB #778

IN>3 Start
DDB #779

Started Phase N
DDB #959

IN>4 Start
DDB #780

ISEF>1 Start
DDB #781

ISEF>2 Start
DDB #782

ISEF>3 Start
DDB #783

ISEF>4 Start
DDB #784

Phase Select N
DDB #1013

&

Any Trip
DDB #522

>> page6 Any Phase Start

Any Phase Start >> page8

Phase Select N
DDB #1013

&
10

Any Trip
DDB #522

Pulse
0

This logic ensures correct N


indications for faults involving
ground. The pulse prevents pole
scatter affecting the N indication.

AR In Service
DDB #1385

N Phase Start >> page8 then page 9 then page 10

&

Reset Relays/LED
DDB #444

This reset controls:


Reset latched relays,
Reset latched LEDs,
Reset A/R Lockout.
This logic clears all latched indications at the
start of Any Trip

>
Page 7

MiCOM P443 Programmable Logic

> page7 Any Ground Start

> page7 Any Phase Start

>> page 7 N Phase Start

LED1 Red
DDB #1024

Latching

LED1 Grn
DDB #1025

Any Trip
DDB #522
I2>1 Start
DDB #567
I2>2 Start
DDB #568

Any Start
DDB #736

I2>3 Start
DDB #569

Used in Fault Record


initiation

I2>4 Start
DDB #570
V<1 Start
DDB #788

Caution: Do Not
remove "Any Start"
DDB signal

V<2 Start
DDB #792
V>1 Start
DDB #796
V>2 Start
DDB #800
VN>1 Start
DDB #804
VN>2 Start
DDB #805

F<1 Start
DDB #1155
F<2 Start
DDB #1156
F<3 Start
DDB #1157
F<4 Start
DDB #1158
F>1 Start
DDB #1159
F>2 Start
DDB #1160
V1>1 Cmp Start
DDB #923
V1>2 Cmp Start
DDB #924
df/dt>1 Start
DDB #597
df/dt>2 Start
DDB #598
df/dt>3 Start
DDB #599
df/dt>4 Start
DDB #600

N Phase Start >>page 9 then page 10


Page 8

>> pag

MiCOM P443 Programmable Logic

Zone 1 A Trip
DDB #609
Zone 2 A Trip
DDB #614
Zone 3 A Trip
DDB #619
Zone P A Trip
DDB #624
Zone 4 A Trip
DDB #629
Aided 1 Trip A
DDB #633
Aid 1 WI Trip A
DDB #637

Aided 2 Trip A
DDB #643

Faulted Phase A
DDB #952

Aid 2 WI Trip A
DDB #647
I>1 Trip A
DDB #656
I>2 Trip A
DDB #660
I>3 Trip A
DDB #664
I>4 Trip A
DDB #668
AR Trip Test A
DDB #577

Faulted Phase Flag, Used in


Fault record and on LCD
display.

AR Trip Test 3Ph


DDB #576

ge 7 then page 8 N Phase Start

Caution: Do Not remove


"Faulted Phase" DDB signals

Zone 1 B Trip
DDB #610
Zone 2 B Trip
DDB #615
Zone 3 B Trip
DDB #620
Zone P B Trip
DDB #625
Zone 4 B Trip
DDB #630
Aided 1 Trip B
DDB #634
Aid 1 WI Trip B
DDB #638
Aided 2 Trip B
DDB #644

Faulted Phase B
DDB #953

Aid 2 WI Trip B
DDB #648
I>1 Trip B
DDB #657
I>2 Trip B
DDB #661
I>3 Trip B
DDB #665
I>4 Trip B
DDB #669
AR Trip Test B
DDB #578
AR Trip Test 3Ph
DDB #576

N Phase Start >> page 10


Page 9

>> page 7

MiCOM P443 Programmable Logic

Zone 1 C Trip
DDB #611
Zone 2 C Trip
DDB #616
Zone 3 C Trip
DDB #621
Zone P C Trip
DDB #626
Zone 4 C Trip
DDB #631
Aided 1 Trip C
DDB #635
Aid 1 WI Trip C
DDB #639
Aided 2 Trip C
DDB #645

Faulted Phase
DDB #954

Aid 2 WI Trip C
DDB #649
I>1 Trip C
DDB #658
I>2 Trip C
DDB #662
I>3 Trip C
DDB #666
I>4 Trip C
DDB #670
AR Trip Test C
DDB #579

Faulted Phase Flag, Used in


Fault record and on LCD
display.

AR Trip Test 3Ph


DDB #576

Caution: Do Not remove


"Faulted Phase" DDB signals

Zone 1 N Trip
DDB #612
Zone 2 N Trip
DDB #617
Zone 3 N Trip
DDB #622
Zone P N Trip
DDB #627
Zone 4 N Trip
DDB #632
Aided 1 Trip N
DDB #636
Aided 2 Trip N
DDB #646
IN>1 Trip
DDB #671
IN>2 Trip
DDB #672

IN>3 Trip
DDB #673
IN>4 Trip
DDB #674
VN>1 Trip
DDB #700
VN>2 Trip
DDB #701
ISEF>1 Trip
DDB #675
ISEF>2 Trip
DDB #676
ISEF>3 Trip
DDB #677
ISEF>4 Trip
DDB #678

7 then page 8 the page 9 N Phase Start


Page 10

Faulted P
DDB

Phase N
#955

MiCOM P443 Programmable Logic


Inputs to Trip Conversion
Logic:These Raw trip signals
are then processed in relay fixed
logic, to obtain the correct
single, or three pole trip
response.

Zone 1 A Trip
DDB #609

Aided 1 Trip A
DDB #633

Aid 1 WI Trip A
DDB #637

Trip Inputs A
DDB #530

Aided 2 Trip A
DDB #643

Aid 2 WI Trip A
DDB #647

Caution: Do Not
remove "Trip Inputs"
DDB signals

AR Trip Test A
DDB #577

Zone 1 B Trip
DDB #610

Aided 1 Trip B
DDB #634

Aid 1 WI Trip B
DDB #638

Trip Inputs B
DDB #531

Trip Inputs C
DDB #532

Aided 2 Trip B
DDB #644

Aid 2 WI Trip B
DDB #648

AR Trip Test B
DDB #578

Zone 1 C Trip
DDB #611

Aided 1 Trip C
DDB #635

Aid 1 WI Trip C
DDB #639

Aided 2 Trip C
DDB #645

Aid 2 WI Trip C
DDB #649

AR Trip Test C
DDB #579

Page 11

MiCOM P443 Programmable Logic

pa

V<1 Trip
DDB #683
V<2 Trip
DDB #687
V>1 Trip
DDB #691
V>2 Trip
DDB #695
VN>1 Trip
DDB #700

Caution: Do Not
remove "Trip Inputs"
DDB signals

VN>2 Trip
DDB #701
F<1 Trip
DDB #1161
F<2 Trip
DDB #1162
F<3 Trip
DDB #1163

CBF Non I Trip


DDB #874

F<4 Trip
DDB #1164

Caution: Non
Current Protections
required to Initiate
CB Fail

F>1 Trip
DDB #1165
F>2 Trip
DDB #1166
df/dt>1 Trip
DDB #601
df/dt>2 Trip
DDB #602
df/dt>3 Trip
DDB #603
df/dt>4 Trip
DDB #604
V1>1 Cmp Trip
DDB #925
V1>2 Cmp Trip
DDB #926

AR Trip Test 3Ph


DDB #576
Broken Line Trip
DDB #679
Thermal Trip
DDB #680
I2>1 Trip
DDB #571
I2>2 Trip
DDB #572
I2>3 Trip
DDB #573
I2>4 Trip
DDB #574
ISEF>1 Trip
DDB #675

Trip Inputs 3Ph >> page 13


Caution: Do Not
remove "Trip Inputs"
DDB signals

ISEF>2 Trip
DDB #676
ISEF>3 Trip
DDB #677
ISEF>4 Trip
DDB #678
IREF> Trip
DDB #682

Page 12

MiCOM P443 Programmable Logic

age 12 >> Trip Inputs 3Ph


Stub Bus Trip
DDB #591
Pred. OST
DDB #551
OST
DDB #553
Zone 2 Trip
DDB #613
Zone 3 Trip
DDB #618
Zone P Trip
DDB #623
Zone 4 Trip
DDB #628
I>1 Trip
DDB #655
I>2 Trip
DDB #659
I>3 Trip
DDB #663
I>4 Trip
DDB #667
IN>1 Trip
DDB #671
IN>2 Trip
DDB #672
IN>3 Trip
DDB #673
IN>4 Trip
DDB #674
Aid1 Delta Tr3Ph
DDB #640
Aid1 DEF Trip3Ph
DDB #641
Aid1 WI Trip 3Ph
DDB #642
Aid2 Delta Tr3Ph
DDB #650
Aid2 DEF Trip3Ph
DDB #651
Aid2 WI Trip 3Ph
DDB #652

Trip Inputs 3Ph


DDB #529

Caution: Do Not
remove "Trip Inputs"
DDB signals

Loss ofLoad Trip


DDB #654
Pole Discrepancy
DDB #699
TOR Trip Zone 1
DDB #704
TOR Trip Zone 2
DDB #705
TOR Trip Zone 3
DDB #706
TOR Trip Zone P
DDB #708
TOR Trip Zone 4
DDB #707
TOR Trip CNV
DDB #557
SOTF Trip CNV
DDB #558
SOTF Trip Zone 1
DDB #709
SOTF Trip Zone 2
DDB #710
SOTF Trip Zone 3
DDB #711
SOTF Trip Zone P
DDB #713
SOTF Trip Zone 4
DDB #712

Page 13

Aid 1 Dist Trip


DDB #503
Aid 2 Dist Trip
DDB #519

Aid 1 DEF Trip


DDB #505
Aid 2 DEF Trip
DDB #521

CB Open A ph
DDB #904
CB Closed A ph
DDB #908

CB Open B ph
DDB #905
CB Closed B ph
DDB #909

CB Open C ph
DDB #906
CB Closed C ph
DDB #910

A/R Lockout
DDB #306

AR In Service
DDB #1385

CB ARIP
DDB #1544
CB Succ 3P AR
DDB #852
CB Succ 1P AR
DDB #1571

DIST PH-A START


DDB #008
DIST PH-B START
DDB #009

DIST PH-B START


DDB #009
DIST PH-C START
DDB #010

DIST PH-C START


DDB #010
DIST PH-A START
DDB #008

DIST 3PH START


DDB #014

Pick-Up

&

0
DIST PH AB START
DDB #011

Pick-Up

&

0
0

&

DIST PH BC START
DDB #012

Pick-Up

&

0
DIST PH CA START
DDB #013

Pick-Up
0

You might also like