Professional Documents
Culture Documents
5150 300
A DOWN PIPE
5140
HEATING, VENT.AND
AIRCONDITIONING
12300
AIRCONDITIONING
4385
WATER TANK
C
AIR CONDITIONER WILL BE LOCATED
BASE TO THE MECHANICAL
ENGINEER
3325
GREEN AREA
D
FROM THE OFFICE OF: PROF. ELECTRICAL ENGINEER TITLE OF PROJECT: APPROVED AS TO PLAN AND LOCATION: IMPORTANT : REVISIONS : SHEET CONTENT: SHEET NUMBER :
DRAWING AND SPECIFICATIONS AND OTHER NO. DESCRIPTION DATE
CONTRACT DOCUMENTS DULY SIGNED, STAMPED,
OR SEALED AS INSTRUMENTS OF SERVICE ARE
ENGR. TOMAS G. VIRTUDEZ PROPOSED SOLAR PANEL LAYOUT ENGR. RYAN VOLTAIRE G. TOLENTINO INTELLECTUAL PROPERTY AND DOCUMENTS OF
8.0mm2 bcw in
25mm dia. PVC
GP CT CLAMP (SOLIS) PV CABLE
TO GEN. SET TO LP
PV CABLE
20 AT
DC SPD
DC BREAKER
FROM THE OFFICE OF: PROF. ELECTRICAL ENGINEER TITLE OF PROJECT: APPROVED AS TO PLAN AND LOCATION: IMPORTANT : REVISIONS : SHEET CONTENT: SHEET NUMBER :
DRAWING AND SPECIFICATIONS AND OTHER NO. DESCRIPTION DATE
CONTRACT DOCUMENTS DULY SIGNED, STAMPED,
OR SEALED AS INSTRUMENTS OF SERVICE ARE
ENGR. TOMAS G. VIRTUDEZ PROPOSED SOLAR PANEL LAYOUT ENGR. RYAN VOLTAIRE G. TOLENTINO INTELLECTUAL PROPERTY AND DOCUMENTS OF
DC INPUT 1:
CURRENT 1: (SOLAR POWER x NO. OF PANEL)/(SOLAR VOLTAGE x SOLAR IN SERIES) = 13.22 A
VD CALCULATION: (CURRENT OF SOLAR x DISTANCE)/(%VD x VOLTAGE) = 1.59 V
FROM SOLAR TO DC BREAKER USE: 2-4MM2 + 1-4MM2 (GW)
DC BREAKER: TOTAL AMP x 1.25 x 1.25 = 20.65805288 AMP
DC BREAKER SIZE: 20 AT
DC INPUT 2:
CURRENT 2: (SOLAR POWER x NO. OF PANEL)/(SOLAR VOLTAGE x SOLAR IN SERIES) = 13.22 A
VD CALCULATION: (CURRENT OF SOLAR x DISTANCE)/(%VD x VOLTAGE) = 1.59 V
FROM SOLAR TO DC BREAKER USE: 2-4MM2 + 1-4MM2 (GW)
DC BREAKER: TOTAL AMP x 1.25 x 1.25 = 20.65805288 AMP
DC BREAKER SIZE: 20 AT
INVERTER:
MAXIMUM TOTAL POWER OUTPUT: (NO. OF PANELS x WATTAGE x 4hrs.)/(1.3 *8hrs.) = 4230.77 W
TOTAL SURGE POWER: 5500 W
INVERTER SIZE: 8000 W
MODEL: S5-GR3P(3-20)K
AC OUTPUT:
MAX OUTPUT CURRENT: (INVERTER WATTAGE x 125%)/(AC VOLTAGE) = 26.32 A
AC BREAKER SIZE: 30AT
WIRE SIZE: 4-5.5MM2 THHN/THWN + 1-5.5MM2 THHN/THWN (G)
FROM THE OFFICE OF: PROF. ELECTRICAL ENGINEER TITLE OF PROJECT: APPROVED AS TO PLAN AND LOCATION: IMPORTANT : REVISIONS : SHEET CONTENT: SHEET NUMBER :
DRAWING AND SPECIFICATIONS AND OTHER NO. DESCRIPTION DATE
CONTRACT DOCUMENTS DULY SIGNED, STAMPED,
OR SEALED AS INSTRUMENTS OF SERVICE ARE
ENGR. TOMAS G. VIRTUDEZ PROPOSED SOLAR PANEL LAYOUT ENGR. RYAN VOLTAIRE G. TOLENTINO INTELLECTUAL PROPERTY AND DOCUMENTS OF