2 GENERAL NOTES 2 LEGENDS

EE-01 EE-01 3 drawing index


EE-01

1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT AND
IMMEDIATE SUPERVISION BY A COMPETENT ELECTRICAL ENGINEER OR RME
WITH SOLAR TRAINING. SHEET NO. DRAWING TITLE
SERVICE ENTRANCE, 1PHASE, 230V, 60HZ
2. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE GENERAL NOTES, LEGEND,DRAWING INDEX AND
PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE EE-01 LOCATION MAP
(PEC), LOCAL BUILDING CODES AND OFFICIAL RULINGS. M MAIN METER (KWHR METER)

3. ALL WIRING METHOD FOR DC SYSTEM SHALL BE DONE IN LIQUIDTITE, IMC OR EE-02 SOLAR PANEL LAY-OUT
RMC FOR ALL EXPOSED CONDUIT LAYOUT AND FEEDER DISTRIBUTION. 12KW
INVERTER 3 Ø

4. ALL CONDUIT, BOXES AND SUPPORT SHALL BE PAINTED WITH COLOR GRAY. INVERTER EE-03 SOLAR PANEL SINGLE LINE DIAGRAM LAY-OUT
5. SMALLEST BRANCH DC CIRCUIT WIRE SHALL BE 4 MM2 IN RACEWAY 15 MM DIA.
TRADE SIZE CONDUITS. EE-04 SOLAR PANEL CALCULATION
6. ALL EXPOSED CONDUIT RUN SHALL BE INSTALLED PARALLEL TO OR 230V, 1P, 60hz L N

PERPENDICULAR WITH THE BUILDING LINE AND SUPPORTED BY CONDUIT AUTOMATIC TRANSFER SWITCH (ATS)
CLAMPS EVERY 1.5 METERS. LOAD SIDE

7. ALL COMBINER BOX SHALL BE PROVIDED WITH MULTIPLE TERMINAL LUGS FOR
MOUNT APO GARDENS
BETTER GROUNDING. MEMORIAL PARK

DAV
8. ALL METALLIC CONDUIT, BOXES AND EQUIPMENT SHALL BE PROPERLY SOLAR PANEL

AO
GROUNDED AND BONDED.

- BUK
9. ALL MATERIALS SHALL BE NEW, FREE FROM CORROSION AND APPROVED FOR

IDNO
THE LOCATION.

N HIG
10. ALL WIRES AND CABLES SHALL BE COLOR CODED AS FOLLOWS:

HWA
FOR DC:

Y
POSITIVE ------------------ RED
NEGATIVE ------------------ BLACK THIS SITE
GREEN ------------------ GREEN
FOR AC 1P:
PHASE A ------------------ RED
PHASE B ------------------ BLACK N
GROUND ------------------ GREEN
FOR AC 3P:
PHASE A ------------------ BLUE
PHASE B ------------------ RED
PHASE C ------------------ YELLOW
NEUTRAL ------------------ WHITE
GROUND ------------------ GREEN
11. INVERTER TERMINAL INPUT VOLTAGES SHALL NOT EXCEED 500V OR BELOW BUMBLE V GAS STATION
OAD
BIAO R
280V FOR RESIDENTIAL AND UP TO 1000V FOR COMMERCIAL APPLICATIONS. CAMPO
CIECO R
OAD

12. ALL PV INSTALLATION SHALL BE AT LEAST SIGNAL NUMBER 3 OR 4 RESISTANT LOS AMIGOS LOS AMIGOS
OR 200+KPH SUSTAINED WIND SPEEDS. WET & DRY MARKET

13. ALL PV ARE ATTACH TO THE BUILDING'S ROOF AS INDICATED IN THE PLAN.

TO M
14. CONDUIT SLEEVES AND FLOOR SLOT PENETRATION THROUGH ELECTRICAL AND LOS AMIGOS
LOS AMIGOS
TELEPHONE ROOMS WALLS/ CLOSET SPACES SHALL BE PROPERLY SEALED-OF

INTA
ELEMENTARY SCHOOL
BARANGAY HALL
WITH FIRE RETARDANT MATERIAL TO MAINTAIN FIRE RESISTIVE RATINGS OF

L
THE FLOOR OPENING.
15. THE ELECTRICAL CONTRACTOR SHALL PROVIDE SHOP DRAWING IN ANY
CHANGES IN LOCATION FOR THE APPROVAL OF ARCHITECT OR ENGINEER. 4 vicinity map
EE-01 scale: nts

GENERAL NOTES, LEGEND, DRAWING INDEX AND VICINITY MAP


SCALE: NTS

FROM THE OFFICE OF: PROF. ELECTRICAL ENGINEER TITLE OF PROJECT: APPROVED AS TO PLAN AND LOCATION: IMPORTANT : REVISIONS : SHEET CONTENT: SHEET NUMBER :
DRAWING AND SPECIFICATIONS AND OTHER NO. DESCRIPTION DATE
CONTRACT DOCUMENTS DULY SIGNED, STAMPED,
PROPOSED SOLAR PANEL LAYOUT OR SEALED AS INSTRUMENTS OF SERVICE ARE

ENGR. TOMAS G. VIRTUDEZ PLAN FOR 49 UNITS SINGLE DETACHED


ENGR. RYAN VOLTAIRE G. TOLENTINO INTELLECTUAL PROPERTY AND DOCUMENTS OF
THE ARCHITECT. WHETHER THE OBJECT FOR WHICH
EE
THEY ARE MADE IS EXECUTED OR NOT. IT SHALL BE
UNLAWFUL FOR ANY PERSON TO DUPLICATE OR
HOUSING LANDKEYPERS-SIRAWAN1 TO MAKE COPIES OF SAID DOCUMENTS FOR USE IN 01
PRC NO : 0004719 VALIDITY : 10/07/2019 PTR NO : 2355817 DATE : 01/25/2023 PRC NO : 110045 VALIDITY : 06/04/2024 PTR NO : 4422047 DATE : 01/27/2023 REPETITIONS OF AN FOR OTHER PROJECTS OR
BUILDINGS. WHETHER EXECUTED PARTLY OR IN WHOLE
TIN NO : 148 - 314 - 380 ADDRESS : STA. MONICA SURIGAO DEL NORTE ADDRESS: PUROK 2, SIRAWAN, TORIL, DAVAO CITY TIN NO : 269 - 559 - 923 ADDRESS : RGL BUILDING, DOOR 3, DUMOY, DAVAO CITY WITHOUT THE WRITTEN CONSENT OF ARCHITECT
OR AUTHOR OF THE SAID DOCUMENTS.

You might also like