SECTION III - GOVERNMENT REVIEW REMARKS
Code is (F)
- Fire hydrant shall have individual valve pumper connection and hose connections with independent nozzle gate valves, section 33
11 00 Para. 2.1.3.1.1
- Detailed project external fire water network was not part of 100% design package, if fire protection water will be utilized in any of
potable water usages, then fire hydrant shall comply with lead content requirements of potable water section 33 11 00 Para. 1.4.1
The Contracting Officer's approval or acceptance of submittals is not to be construed as a complete check, and indicates only that the
general method of construction, materials, detailing and other information are satisfactory. This does not relieve the Contractor from
the obligation to furnish material conforming to the plans and specifications; will not prevent the Contracting Officer from requiring
removal and replacement of nonconforming material incorporated in the work; and does not relieve the Contractor of the requirement
to furnish samples for testing by the Government laboratory or for check testing by the Government in those instances where the
technical specifications so prescribe.
Narratives:
Specification 33 11 00 Page 8 & 9 clause 2.1.3.1.1
Complies with UL, FM & AWWA C502 as per the project specs.
Attachments:
1. Narratives.
2. IFC Drawing.
3. Project Specifications.
FIRE
HYDRANT
A
CU-522
1660
APPR.
830
BOLLARD (TYP)
CL WATER
DATE
3050 3050
D 830
920 150
MIN CONCRETE ENCASEMENT CL SEWER TYP
1660
SEWER
FIRE HYDRANT
DESCRIPTION
SEWER
CONCRETE
BOLLARD PLAN ENCASEMENT (SEE
1
MIN
MIN
450
450
SCALE = NTS NOTES)
PVC PIPE
BELL JOINT
WATER
830
WATER
APPR. MARK
610 1660
WATER CROSSING
SEP
FIRE HYDRANT
BOLLARD (TYP)
UNDER SEWER SECTION
12-19-19
A
DATE
3 SCALE = NTS CU-522 SCALE = NTS
DESCRIPTION
C NOTE:
1. REFER TO PLANS FOR LOCATION OF HYDRANTS. 2. REFER TO SPECIFICATION 33 11 00 WATER DISTRIBUTION AND 33 30 00 SANITARY SEWER FOR ADDITIONAL INFORMATION.
2. FIRE HYDRANT SHALL BE PLACED AT LEAST 1m FROM EDGE OF PAVEMENT. 3. WATER MAINS SHALL BE INSTALLED A MINIMUM 305 ABOVE SANITARY SEWER MAINS WHEN IT CROSSES OVER THE SEWER.
3. REFER TO PLANS FOR QUANTITY AND LOCATION OF BOLLARDS. 4. DI PIPE MAY BE USED IN LIEU OF PVC CONCRETE ENCASED PIPE
5. NO JOINT SHALL BE CLOSER THAN 920 FROM CENTERLINE OF WATER MAIN REGARDLESS OF WHETHER DI CONCRETE
FIRE HYDRANT
MARK
100%
ENCASED PVC IS USED.
BOLLARD ELEVATION
12-19-19
DECEMBER 19, 2019
SCALE = NTS
SOLICITATION NO.:
CONTRACT NO.:
1:2
SA-459583--CU521DT
DATE:
0.5 m
PAVEMENT OR FIRE
FILE NAME:
CKD BY:
FINISH GRADE HYDRANT
BET
JSR
(PAINT RED) FROM FIRE
S. PAVLOWICH
SUBMITTED BY:
PUMP HOUSE
DESIGNED BY:
FINISH GRADE
VALVE BOX FLOOR DRAIN
22 X 34
DWN BY:
& COVER
SCJ
SIZE:
B CONCRETE FINISH
GRADE
150
GEOTEXTILE FABRIC
US Army Corps
3000 (ON TOP AND SIDES)
of Engineers
MIN
1 m³ WASHED
p:\269162\127-269162-19001\cad\cad drawings\01_site design\civil\03_utilities\sa-459583--cu521dt brandon.goold 12/19/2019 5:41 PM
TETRA TECH
D.I. FIRE 150 D.I. ANGULAR STONE
PROTECTION MAIN TEE PLACE 31 m³ OF ANGULAR
HYDRANT
1. TRENCH DIMENSIONS ARE 1m x 1m x 1m
SERVICE WASHED STONE FOR
2. SEE SPECIFICATION "33 30 00 - SANITARY SEWER"
RISER DRAINHOLES
FOR GEOTEXTILE INFORMATION
CONCRETE THRUST
BLOCK (SEE DETAILS)
FIRE PUMP HOUSE
NOTES:
INFILTRATION TRENCH DETAIL
WATER DETAILS
SHEET 2 OF 6
SITE DESIGN
SA-459583
WATER / SEWER MAIN HYDRANT 1. ALL BURIED OR PARTIALLY BURIED CONCRETE STRUCTURES
SHALL HAVE THAT PORTION OF THE CONCRETE IN CONTACT
SEPARATION DETAIL CONNECTION DETAIL WITH SOIL SHALL WATERPROOFED PER SPECIFICATION 07 13 53 -
A 4 SCALE = NTS
5 SCALE = NTS
SHEET WATERPROOFING WHICH CONSISTS OF A COAT OF
BITUMEN PRIMER, SHEET MEMBRANE AND PROTECTION BOARD.
SHOULD PROTECTION BOARD NOT BE PRACTICAL TO INSTALL,
ALTERNATIVE PROTECTION FOR THE INSTALLED MEMBRANE
WILL BE ALLOWED IF APPROVED BY CO.
1.2 DEFINITIONS
Water mains include water piping having diameters 100 through 350 mm,
specific materials, methods of joining and any appurtenances deemed
necessary for a satisfactory system.
Water service lines include water piping from a water main to a building
service at a point approximately 1.5 m from building or the point
indicated on the drawings, specific materials, methods of joining and any
appurtenances deemed necessary for a satisfactory system.
1.3 SUBMITTALS
Connections; G M/R
Valves
Valve Boxes
SECTION 33 11 00 Page 4
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
Fire Hydrants
Pipe Restraint
Tapping Sleeves
Bacteriological Samples; G M
Leakage Test; G M
Hydrostatic Test; G M
SD-07 Certificates
Lining
Valves
Fire Hydrants
Comply with NSF/ANSI 14 or NSF/ANSI 61 and NSF 372 for materials for
potable water systems; comply with lead content requirements for
"lead-free" plumbing as defined by the U.S. Safe Drinking Water Act
effective January 2014. Provide materials bearing the seal of the
National Sanitation Foundation (NSF) for potable water service.
Comply with NFPA 24 for materials, installation, and testing of fire main
piping and components.
Inspect materials delivered to site for damage. Unload and store with
minimum handling and in accordance with manufacturer's instructions.
Store materials on site in enclosures or under protective covering. Store
plastic piping, jointing materials and rubber gaskets under cover out of
direct sunlight. Do not store materials directly on the ground. Keep
inside of pipes, fittings, valves, fire hydrants, and other accessories
free of dirt and debris.
SECTION 33 11 00 Page 5
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
flange for AWWA C500, AWWA C509, or AWWA C515 gate valves conforming to
the requirements of UL 262. Gate valves shall have ends compatible with
joining to the pipe used; push-on joint ends or mechanical-joint ends for
joining to ductile-iron pipe.
2.1.2.2 Gate Valves 75 mm Size and Larger in Valve Pit(s) and Aboveground
Locations
Construct the bodies of bronze, cast iron or cast steel with lead-free
bronze trim; the valve stem of stainless steel; the seat of lead-free
bronze; and the valve discs and diaphragms of synthetic rubber. Provide
flanged ends.
Provide a valve box for each gate valve on buried piping, except where
indicator post is shown. Construct adjustable valve boxes manufactured
from cast iron or precast concrete of a size compatible for the valve on
which it is used. Provide cast iron valve boxes with a minimum cover and
wall thickness of 5 mm and conforming to ASTM A48/A48M, Class 35B. Coat
the cast-iron box with a heavy coat of bituminous paint. Provide a round
head lid with the word "water" cast in the top. The minimum diameter of
the shaft of the box is 135 mm. Provide ASTM C1433 precast concrete valve
box. Provide precast concrete boxes installed in locations subjected to
vehicular traffic to withstand AASHTO H-20 loading. Manufacture precast
concrete boxes in accordance with Section 03 40 00.00 10 PLANT-PRECAST
CONCRETE PRODUCTS FOR BELOW GRADE CONSTRUCTION.
Provide fire hydrants where indicated. Paint fire hydrants with at least
one coat of primer and two coats of enamel paint. Paint barrel and bonnet
SECTION 33 11 00 Page 8
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
colors in accordance with UFC 3-600-01. Stencil fire hydrant number and
main size on the fire hydrant barrel using black stencil paint.
Provide the same hydrants as those provided for under paragraph Fire
Hydrants where flushing hydrants are indicated.
2.1.4 Disinfection
2.2 ACCESSORIES
SECTION 33 11 00 Page 9
100% Site and Facility Design Submittal
Pillar Type Dry Barrel Fire Hydrant
KENNEDY GUARDIAN K81D
Kennedy Fire hydrants have been used in fire protection for over 100 years. A.W.W.A. C502 was developed in 1913 as a
standard for the manufacture and use of dry barrel hydrants. Kennedy Valves U.S.A. has established itself as a leader in
the industry with manufacturing experience dating back to 1905. Many of the early hydrants are in use today.
Kennedy’s Guardian fire hydrant is reliable, simply design, easy to install and easy to maintain.
SPECIFICATIONS
SIZES: Flanged 6” ANSI 150 FF / DN150 PN 16
Working Pressure: 250 PSIG
UL Listed and FM approved. Meets or exceeds AWWA
C 502 standards
Meeting NFPA connection requirements
Traffic Breakable Flange, 360 Degree Adjustable upper Barrel
Cast Iron / Ductile Iron Barrels with Bronze Nozzles and Plug
Coating: Fusion Bonded Epoxy and Polyester
Models
K81D: UL/FM AWWA 502
K81A: AWWA 502
K81AM: UL/FM AWWA Monitor Flanged
Upper Barrel Configurations
Standard : 1 Pumper & 2 Hose Nozzles
Options : 2 Hose Nozzles
: 2 Pumper Nozzles
: 1 Pumper & 3 Hose Nozzles
Inlet Connections
Standard : Flanged 6” ANSI 150 or DN 150 PN 16 FF
Options : 6" Mechanical Joint, Push-on or
Tyton Ring Type
6" 250# Raised Face Elbow
4"Flanged , Mechanical Joint,
Push-on or Tyton Ring Type
8" Mechanical Joint or Flanged
Listed
Remarks: Options are limited to UL/FM models. Please check with us prior to ordering.
Kennedy , Clow and MH trade marks shown are belonging to Mcwane Inc in USA
and these companies are divisions of McWane USA. All copy rights reserved.
GUARDIAN K81D FEATURES
Weather shield
to protect exposed
operating area from
freezing rain and dirt.
One Piece Bonnet Thrust Washer
Designed for easier For easy turning
operation and maintenance. operation
Two O-Rings
To protect operating
Sealed Grease Cavity threads from corrosion.
For easier operation O-Ring
and maintenance. To seal between brass
ferrule and stem.
Nozzle
Tamper Resistant.
Traffic Flange Breakable Coupling
Full 360° adjustment. Minimizes damage from
New Breaking Ring on traffic impacts. Design
top for easy replacement makes repairs more efficient
and interchangeability on
all K-81 models. O-Ring
For ease of repair
and 360° rotation of parts
FEATURES
Kennedy Guardian Fire hydrants have many additional features as indicated below:
• Easy to use and easy to maintain
• Traffic flange features avoiding any leakage in case of impact without damaging the main valve
• Antifriction bearing at thrust collar for smooth operation and low operating torque
• All K81 hydrants exceed the flow requirements of AWWA C502, UL246 and FM1510
• Optional Extension kit to increase trench length by 6” increment
• Number of turns for fully open the hydrant is 15 ½ only
• Proven main valve design offering bubble tight shut-off
• Unique pressure activated drain valve assures positive shut off; Higher the pressure tighter the seat
Automatically compensates for wear due to usage and does not rely on interference fit
• Drain ports to drain all water after the operation preventing any possible corrosion and cold weather freeze up
• Anticorrosion protection by internal and external fusion bonded epoxy coating and polyester coatings
• NSF certified epoxy coating on wetted DI parts
• Optional trim for salt water application on request
• Optional warranty up to 10 years on standard design upon request
GUARDIAN K81D PART LIST
.
. .
.
.
.
.
.
.
.
.
.
.
. .
.
.5
.
.
. .
. .
.
. .
. .
.
),/(&$7+<
*XDUGLDQ.'Z)ODQJHG(OERZ
ITEM NO. DESCRIPTION ':*+< .(11('<9$/9(
MATERIAL ASTM SPEC
7HFKLQLFDO'DWD (/0,5$1<
8101 ALEMITE FITTING'$7( STAINLESS STEEL A276 (304)
8102 OPERATING STEM NUT BRONZE
7+(,1)250$7,21&217$,1(',17+,6'5$:,1*,67+(3523(57<2).(11('<9$/9($1<5(352'8&7,21,13$5725$6$:+2/(:,7+2877+(:5,77(13(50,66,212).(11('<9$/9(,6352+,%,7(' B584 C84400/AWWA GRADE A
8103 DIRT SHIELD CAST IRON A126 CLASS B
8104 STEM LOCK NUT BRONZE B584 C84400/AWWA GRADE A
8105 O-RING RUBBER D2000
8106 THRUST WASHER NYLATRON GS MIL LP-410
8107 HYDRANT CAP CAST IRON A126 CLASS B
8108 CAP BOLTS & NUTS STEEL (ZINC PLATED A307/SAE GRADE 2
8109 BONNET O-RING RUBBER D2000
8110 STEM FERRULE BRASS B135 C26000
8111 O-RING BUNA-N (SYN.RUBBER) D2000
8112 O-RING BUNA-N (SYN. RUBBER) D2000
8114 UPPER STEM COLD DRAWN STEEL A108 C1018/C1020
8115 UPPER BARREL CAST IRON/DUCTILE IRON A125 CLASS B/ASTM 536 70-50-5
8116 STEMBREAKER COUPLING CAST IORN A126 CLASS B
8118 BOLTS & NUTS STEEL (ZINC PLAETD) A307/SAE GRADE 2
8119 BREAKING RING CAST IORN A126 CLASS B
8120 O-RING BUNA-N (SYN. RUBBER) D2000
8122R COUPLING PINS STAINLESS STEEL 302 HQ
8123 LOWER STEM COLD DRAWN STEEL A108 C1018/C1020
8124 LOWER BARREL DUCTILE IRON (OR C.I.) ANSI/AWWA C151/A21.5
8125 ELBOW O-RING BUNA-N (SYN. RUBBER) D2000
8126 O-RING BUNA-N (SYN. RUBBER) D2000
8127 SEAT RING INSERT BRONZE B584 C84400/AWWA GRADE A
8128 SEAT RING BRONZE B584 C83600
8129 DRAIN TUBE BRASS B135 C 33000
8130 O-RING BUNA-N (SYN. RUBBER) D2000
8131 MAIN VALVE EPDM W/STL. INSERT D2000
8132 BOTTOM PLATE CAST IRON A126 CLASS B
8133 DRAIN VALVE PIN STAINLESS STEEL 410/416
8134 ELBOW CAST IRON A126 CLASS B
8135 ELBOW NUTS AND BOLTS STAINLESS STEEL F593C/F594
8136 DRAIN VALVE BRONZE B806 C95400/95500
8137 DRAIN VALVE VACING W/INSERT BUNA-N W/STAINLESS STEEL D2000/A2276 (304)
8139 NOZZLE CAP CHAIN STEEL A108
8140 NOZZLE CHAIN BAND STEEL A108
8141 NOZZLE RETAINING SCREW STAINLESS STEEL A276 (304)
8142 NOZZLE (STROZ OPTIONAL) BRONZE B584 C8400/AWWA GRADE A
8143 NOZZLE CAP GASKET NEOPRENE D2000
8144 NOZZLE CAP CAST IRON A125 CLASS B
8145 O-RING BUNA-N (SYN. RUBBER) D2000
8146 ALLEN HEAD SET SCREW STAINLESS STEEL A276 (410)
8147 SEAT REMOVAL TOOL
8148 NOZZLE REMOVAL TOOLS
8149 COLLISION REPAIR KIT
8150 GRADE EXTENSION KIT
Model A B C D Weight
GROUND LINE
D
www.mcwaneinternational.com
McWane International, 1201 Vanderbilt Road, Birmingham AL 35234, USA,
Ph.: 205-716-6600, Fax: 205-324-7250, email: inquiries@mcwaneintl.com
Kennedy Valve: Clow Valve:
1021 East Water Street Elmira, NY 14902 USA 902 South Second Street Oskaloosa, IA 52577 USA
M & H Valve: McWane International FZE
605 West 23rd Street Anniston, AL 36201 USA P O Box 263362, Jebel Ali , Dubai UAE
Kennedy, Clow and MH trade marks shown are belonging to Mcwane Inc in USA and
these companies are divisions of McWane USA. All copy rights reserved
MGULF/SP/12/2012