Professional Documents
Culture Documents
EHV TransmissionLineDesign
EHV TransmissionLineDesign
net/publication/348620011
CITATIONS READS
0 3,187
1 author:
Demsew Teferra
Addis Ababa Science and Technology University
22 PUBLICATIONS 39 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
Power Quality and Reliability Assessment of the Distribution System of Debre Markos Town View project
All content following this page was uploaded by Demsew Teferra on 20 January 2021.
JULY 2017
Content
• Introduction
• Economic Size of Conductor
• Transmission Line Parameter Calculation
• Transmission Circuit and Bundle Conductor Calculation
• Surge Impedance Loading (SIL) of the line
• Sag-Tension Calculation of conductor
• Insulator Sizing
• Field Effect of EHV transmission line
• Environmental Criteria
Electrical Design Parameters
Introduction
• Voltage Classes:
𝑁𝑐 =0.97 ≅ 1.
𝑳𝒐𝒂𝒅 𝒊𝒏 𝑲𝑽𝑨/𝑵𝒄
𝑽 = 𝟓. 𝟓 𝑳 + 𝒌𝑽
𝟏𝟓𝟎
1111.11 ∗ 103
𝑉 = 5.5 600 + 𝑘𝑉 = 492𝑘𝑉
150
o Cost…
Economic Size of Conductor
• Kelvin’s Law represented by the following formula used to determine the economic current density conductor.
𝒂. 𝒑 𝑨𝒎𝒑𝒆𝒓𝒆
𝑪 = 𝟎. 𝟎𝟏𝟑
𝒒 𝒎𝒎𝟐
Where,
𝟏𝟑. 𝟓 ∗ 𝟒
𝐂 = 𝟎. 𝟎𝟏𝟑 = 𝟎. 𝟓𝟓 𝐀𝐦𝐩𝐞𝐫𝐞/𝒎𝒎𝟐
𝟎. 𝟎𝟑
Cont’d..
• The current I is calculated as follows:
μp
I= Ampere
3 ∗ V ∗ pf
• Where,
o µ = utility factor being (0.6 )
o pf = power factor being 0.90
o V = line voltage (500kV)
o P = Maximum Power (1000MW)
• The most economic size of the conductor is, A=I/C (mm2)
0.6 ∗ 106
𝐼= Ampere = 769.8Ampere
3 ∗ 500 ∗ 0.9
𝐼 769.8Ampere
𝐴= = 2
= 1400𝑚𝑚2
𝐶 0.55 Ampere/mm
Cont’d…
• The numbers of bundle conductors (n) if we choose 468-
1400𝑚𝑚2
𝑛= 2
= 2.99 ≈ 3
468𝑚𝑚
Cont’d…
Table 3.1: Conductor Data Sheet Aluminum Conductors Steel Reinforced (ACSR)
Cont’d…
• The following conductor specification is selected for economic and best
environmental operation of 500kV overhead transmission line. Please
refer Table 3.1.
following reason.
o To balance the magnetic field stress for each phase of a bundled conductor,
o Line Inductance
o Line Capacitance
o AC Resistance
500kV Line AC Resistance Calculation
• Determinant Parameter:
o Material Type
𝒍
o Cross Sectional Area 𝑹𝒅𝒄 = 𝝆.
𝑨
o Line Length
𝐑 𝐓 = 𝐑 𝐨 [𝟏 + 𝛂(𝐓 − 𝐓𝟎 )]
o Temperature and
Cont’d…
• From Table 3.1 the dc resistance of the chosen conductor
at 20oc is 0.0717Ω/km.
• But when the conductor is energized, it operates a
temperature of around 50oc.
𝝁. 𝒇 𝟏 ∗ 𝟓𝟎
𝑿 = 𝟎. 𝟎𝟔𝟑𝟓𝟗𝟖 = 𝟎. 𝟎𝟔𝟑𝟓𝟗𝟖 = 𝟐. 𝟏𝟔
𝑹𝒅𝒄 𝟎. 𝟎𝟒𝟑𝟒𝟓
Cont’d..
Table 2.1: Skin Effect Parameter Values
Cont’d…
• Since K is a function of X and x1<X<x2, using linear interpolation:
𝑿 − 𝒙𝟏 [𝑲 𝒙𝟐 − 𝑲 𝒙𝟏 ]
𝑲 𝑿 = 𝑲 𝒙𝟏 +
𝒙𝟐 − 𝒙𝟏
𝑲 𝑿 = 𝟐. 𝟏𝟔 = 𝟏. 𝟏𝟎𝟒𝟐𝟓𝟔
Cont’d…
• Rac=K*Rdc=1.104256*0.04345 Ω/mile=0.048 Ω/mile
• The per phase ac resistance of a 500kV transmission line having 3
bundle conductor at 50oc is 0.048 Ω/mile.
• The 3-phase 500kV power loss having the above conductor
specification at 50oc is given by:
r’=0.768r=0.768*14.055 mm =10.8mm
𝑆
𝐴= 𝜋 = 26.4𝑐𝑚
2 sin
𝑁
1
𝐺𝑀𝑅 = [𝑁𝑟′(𝐴)𝑁−1 ] 𝑁 =13.12cm
13.1𝑚
𝐿 =2∗ 10−7 ln( ) = 0.923𝜇𝐻/𝑚
0.1312𝑚
−6
0.2898𝑚Ω
𝑋𝐿 = 2𝜋𝑓𝐿 = 6.28 ∗ 50 ∗ .875 ∗ 10 = = 0.4643Ω/𝑚𝑖𝑙𝑒
𝑚
Discussion
• Discuss the line inductive reactance and inductance
value computed above with your practical exposure?
500kV Line Capacitance Calculation
1
𝑋𝐶 = = 2.64 ∗ 108 Ω − 𝑚𝑒𝑡𝑒𝑟 = 1.65 ∗ 105 Ω − 𝑚𝑖𝑙𝑒
2𝜋𝑓𝐶
Discussion
• What do you think about the result of the capacitive
reactance,
𝑋𝐶 = 0.165 ∗ 𝑀Ω − 𝑚𝑖𝑙𝑒
???
Surge Impedance of Line
• Natural impedance, or characteristic impedance of the line.
𝑽(𝒙, 𝒕)
𝒁𝟎 =
𝑰(𝒙, 𝒕)
𝑹 + 𝒋𝒘𝑳
𝒁𝟎 =
𝑮 + 𝒋𝒘𝑪
𝑳
𝒁𝟎 = = 276.6Ω
𝑪
SIL(3ϕ) = 904MW
𝑉𝑅 𝐿−𝐿
|𝐼𝐿 | = (𝐴)
3 ∗ 𝑍𝑜
Group Discussion
• The conductor low point must never violate the clearance levels
specified in Table 3.3.
Basic Clearance Data for 500kV (NESC)
Cont’d…
System Voltage, ROW Width, m TC, m Clearance, m
kV
Phase to Height of mid Average height at
phase span lowest phase
345 38m 45.7m 7.6m 8.5m 12m
𝑽 𝟎. 𝟒
𝑯𝒎𝒊𝒏 = 𝟐𝟐 + − 𝟓𝟎 ∗ (𝒇𝒆𝒆𝒕)
• 𝐻𝑚𝑖𝑛 = The minimum clearance of the 𝟏𝟐 line conductor from ground
𝟑 transmission
• V= Transmission line voltage maximum Value (550kV for example for 500kV line)
Cont’d…
• The curve shape assumed by a conductor when suspended
between towers is very close to a catenary or a parabola.
• The equation for the conductor low point (i.e. the conductor
sag at mid span, assuming suspension points at equal
elevations) using parabolic model is:
Cont’d…
𝟖𝑺𝟐
𝐋=𝐏+
𝟑𝑷
𝑿𝟐
𝐒 𝒙 =𝐖
𝟐𝑯
𝑷𝟐
𝐒=𝐖
𝟖𝑯
𝐇=𝟐∗𝒂∗𝐖
𝐖(𝟑𝑷𝟐 + 𝟖𝑺𝟐 )
𝐕=
𝟔𝑷
Cont’d…
• The average span length of 500kV line outside the city are 1200- 1500 ft (366-
457 m)
• Therefore we can take a ruling span of, P=411.5m for 500kV transmission line.
• Rated conductor Strength 139.7kN (Refer Table 3.1)
• Stringing the conductor with a maximum tension force, T=70kN (50% 0f the
material rated strength to avoid mechanical stress)
Cont’d…
• The maximum sag developed for a span length of 411.5m is given by:
𝑃2
𝑆= 8𝑇 2
=4.925m
−16
𝑊𝑃
𝑃2 411.52
𝐻= 𝑊 = 16.27 ∗ = 69.924𝑘𝑁
8𝑆 8∗4.925
𝑇= 𝐻2 + 𝑉 2 = 70𝑘𝑁
Cont’d…
Therefore the minimum clearance of the lowest phase
from ground at pole point is:
Tension.
a) 140kN
b) 35kN
Insulator Sizing
• The insulation capacity of the insulator is the measure of the power
frequency and lightning with stand voltage gradient to provide proper
insulation between tower and live part of the conductor.
𝟐 𝐕𝐬𝐲𝐬𝐭𝐞𝐦 (𝐊𝐕)
𝐈𝐧𝐬𝐮𝐥𝐚𝐭𝐨𝐫 𝐰𝐢𝐭𝐡𝐬𝐭𝐚𝐧𝐝 𝐯𝐨𝐥𝐭𝐚𝐠𝐞 = ∗ [𝐒𝐚𝐟𝐞𝐭𝐲 𝐌𝐚𝐫𝐠𝐢𝐧]
𝟑
• Safety margin=1.2 (Switching Pulse)-1.4(Lightning Pulse)
500 2
• 𝑀𝑎𝑥𝑖𝑚𝑢𝑚 𝑤𝑖𝑡ℎ𝑠𝑡𝑎𝑛𝑑 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 = ∗ 1.2 = 490𝑘𝑉
3
insulators).
o Corona Discharge
o Radio interference,
o Random noise.
Conductor Surface Gradients
• Mean conductor surface gradient (g), kV/cm
1.4055
1+ ∗288.68
45.72
g= 1310 = 20.775kV/cm
(2∗1.4055) log𝑒
1.4055∗45.72
Cont’d…
• The critical visual corona gradient is calculated
through (go), kV/cm
0.301
𝑔𝑜 = 21.1 ∗ 0.88 ∗ 1 1 + = 23.3𝑘𝑉/𝑐𝑚
1.4055
Corona Discharge
• The power loss due to corona discharge, in kW/km at 50 Hz (per
phase)
2 2
𝑔 20.775
𝑃𝑘 = 𝑛 𝑟 ∗ 𝑓 ∗ = 32 0.014055𝑚 2
∗ 50𝐻𝑧 ∗
𝑔𝑜 23.3
= 0.0793𝑘𝑊/𝑘𝑚
𝑃𝑘 3𝜙 = 0.2379𝑘𝑊/𝑘𝑚
Group Discussion
• Why the power loss due to corona discharge
becomes very small?
Audible Noise of Corona
• The average value of AN in rainy weather for any phase
of the transmission line is given as:
𝐴𝑁𝑖 = 120 log g + 𝑘 log 𝑛 + 55 log 2𝑟 − 11.4 log 𝑅 + 𝐴𝑁𝑜
𝐴𝑁𝑖 = 120 log 20.775 + 26.6 log(3) + 55 log 2.811 − 11.4 log 100 − 128.4
345 55 55
500 55 55
745 55 55
Mechanical Design Parameters
CHAPTER FIVE
LINE LIGHTNING PROTECTION
THEORIES OF THUNDER CLOUD
“When atmosphere near the earth surface or ocean surface containing a large
amount of water vapor warms up by the heat from the sun and other sources, it
expands and ascends. When it reaches a high altitude, it is cooled down, resulting
the vapor in the atmosphere becomes water droplets and then a cloud. When it
ascends even higher, water droplets in the cloud becomes ice grains and some of
them concentrate and grow to hailstones. At that time, these ice grains and
hailstones are decomposed by electric current. Then, ice grains are charged
positively and hailstones are charged negatively. Ice grains ascend even higher by
riding updraft and hailstones grow bigger and fall by the gravity. Charge separation
continues by the coulomb force. Before long, top of the cloud is positively charged
and the bottom negatively. A cloud accumulates electrical energy, which is when a
Cont’d…
• If the space charge densities, which happen to be present in a
thundercloud, produce local field strengths of several100
kV/m, leader discharges are formed which initiate a lightning
discharge.
• Depending on the cause, a surge voltage can last a few hundred microseconds,
• The amplitude can range from a few millivolts to ten thousand volts.
• Lightning strikes are a special cause of surge voltages. Direct and indirect strikes
can result not only in high surge voltage amplitudes, but also high and sometimes
I. Expulsion Arrester
during spark-over.
• The arc across the gap is reduced and blown-off by the force of the
• Moreover, these types of arresters are for low system voltage and of
specific ratings and an excessive surge than the rated may result in its
Spark Gap Arrester
• These have a pair of conducting rods with an adjustable gap,
depending upon the spark over-voltage of the arrester.
• These arresters are also now obsolete for the same reasons as
the previous one.
Valve or non Linear Resistor Arrester
• A non-linear SiC resistor-type gapped surge arrester may generally consist of
three non-linear resistors (NR) in series with the three spark gap assemblies.
Cont’d…
• The resistance has an extremely low value on surge voltages and a very
high one during normal operations to cause a near-open circuit. It is now
easier to interrupt the flow currents.
• Across the spark gaps, known as current limiting gaps, are provided high-
value resistors (HR) backed up with HRC fuses.
• The non-linear resistors have a very flat V-I curve, i.e. they maintain a
near-constant voltage at different discharge currents.
• The flatness of the curve provides a small residual voltage and a low
Cont’d…
Cont’d…
• When the switching or lightning surge voltage exceeds the breakdown
voltage of the spark gap, a spark-over takes place and permits the current
• Due to the nonlinear nature of the resistor, the voltage across the line is
• It may be noted that the use of resistor across the spark gap stabilizes the
Gapless Surge Arresters
• The high resistive component of the previous system results
high power loss which generates heat is the limitation.
the arrester.
Cont’d
ZnO Arrester for various Rating
Group Discussion
𝐼 = 𝐾 · 𝑉∞
• K, represents its geometrical configuration, cross-sectional area and length, and is
a measure of its current-carrying capacity.
• The lower this current, lower will be the loss and the heat
generated during an over-voltage and hence better energy
absorption capability.
Discharge or Residual Voltage, Vres
• It is the voltage that appears across the arrester
during the passage of discharge current – that flows
through the arrester due to a surge.
• Vres is the conducting voltage of an arrester during an over-
voltage or transient condition and defines its protective
level.
Temporary Over-Voltage (TOV)
• It is determined by its low current region (d) that is usually
less than 1 A and for prospective transient voltages it is
determined by its high current region (e) (2.5–20 kA, 8/20𝜇s
current impulse).
• Mechanical soundness:
Example:
Determine the rating of a surge arrester to protect a solid ground fault stay for 3 second and load
rejection of 1 second simultaneously for a 400 kV system.
400kV Arrester Rating at Different TOV
Protective Distance of the Arrester
• If the arrester and the equipment to be protected at
different location:
𝒍 ∗ 𝟏𝟎−𝟑 𝑽𝒔 − 𝑽𝒓𝒆𝒔
Vs = Vres + 2.S.T 𝑻= 𝝁𝒔 𝒍 = 𝟏𝟓𝟎 (𝒎)
𝟎. 𝟑 𝑺
o T = travelling time of the surge to reach the equipment from the arrester terminals.
• If we consider the lightning surge with a steepness of 2000 kV/𝜇s, then for a total distance
of, say, 8 m from the arrester to the equipment please determine the actual surge voltage at
the equipment and BIL of the equipment If we maintain a protective margin of 20%.
8
𝑉𝑠 = 844𝑘𝑉 + 2 ∗ 2000 ∗ ∗ 10−3 𝑘𝑉 = 951𝑘𝑉
0.3
• Then the minimum BIL that the equipment under protection must have