Type Test Compliance as per IEC 60076-5 Annex B

Offered Transformer Reference Of Type Tested Design


Sr. No. Description Nucon Remarks
8.34 MVA , 33/2X0.8KV 12.5 MVA , 33/4X0.63KV
1 Same Type of Operation Step Down Step Down Offered Design is Same as per Type Tested Design
2 Same Conceptual Design Oil, Core Type, Oval Coils Oil, Core Type, Oval Coils Offered Design is Same as per Type Tested Design
3 Same arrangement & geometrical sequence of winding LV1-LV2-HV LV1-LV2-LV3-LV4-HV Offered Design is Same as per Type Tested Design
4 Same type of winding conductor ALM. FOIL / S.E. COVERED ALM. STRIP ALM. FOIL / S.E. COVERED ALM. STRIP Offered Design is Same as per Type Tested Design
5 Same Type of Main Winding FOIL / LAYER FOIL / LAYER Offered Design is Same as per Type Tested Design
Absorbed Power at Short Circuit between 30% &
6 (4.17 MVA / 0.087pu =47.93MVA) (3.125 MVA / 0.07pu =44.64MVA) Offered Design is Same as per Type Tested Design
130% of that relating to reference transformer
With Respect to Base rating 4.17 MVA With Respect to Base rating 3.125 MVA
Axial Forces & winding stresses occuring at SC <
7 HOOP STRESS HOOP STRESS LV-166.43 HOOP STRESS HOOP STRESS LV-262.35 Offered Design is Same as per Type Tested Design
120% of that relating to reference transformer
Kg / Sq.cm , HV-399.86 Kg/Sq.cm Kg / Sq.cm , HV-386.2 Kg/Sq.cm
8 Same Manufacturing Process We Confirm Same Manufacturing Process We Confirm Same Manufacturing Process Offered Design is Same as per Type Tested Design
We Confirm same Clamping & Winding
9 Same clamping & winding support arrangement Provided Offered Design is Same as per Type Tested Design
Support Arrangement