5 6 5 6 Isolating switching
Switching status 1 2 1 2 amplifier
Power Pwr Pwr MK1-22UP-Ex0/24VDC
Selector switch for NC NC
MK1-22UN-Ex0/24VDC
output function NO NO
MK1-22UP-Ex0 MK1-22UN-Ex0 2-channel
24VDC 24VDC
3 4 3 4
1 2 1 2
• 2-channel isolating switching The MK1-22UN-Ex0 and MK1-22UP-Ex0 These units do not feature input circuit
amplifier are dual channel devices with intrinsically monitoring (wire-break and short-circuit).
safe input circuits. They can be used in If input circuit monitoring is required, the
• Intrinsically safe input circuits conjunction with sensors conforming to switching amplifiers MK13-22UN-Ex0 or
EEx ia EN 60947-5-6 (NAMUR), variable resistors MK13-22UP-Ex0 should be used.
or potential-free contacts.
• Area of application acc. to ATEX: A green LED indicates that the device is
II (1) GD Each device is equipped with two short- powered. The switching status of the
circuit protected transistor outputs. There outputs is signalled by two yellow LEDs.
• GaIvanic isolation between are pnp versions (MK1-22UP-Ex0) and
input circuit, output circuit npn versions (MK1-22UN-Ex0) available.
and supply voltage
The output function of both channels is
• 2 short-circuit protected selected by a switch located on the front
transistor outputs: cover. Switch positions NO and NC
– pnp represent normally open mode (NO) and
(MK1-22UP-Ex0) normally closed (NC) mode, respectively.
– npn
(MK1-22UN-Ex0)
2 50 mA ö
2 +2 5 1
8,2 V YE
3 3 YE 7 +
1 GN Power
1 +1 8
MK1-22UN-Ex0/...
4 4 6 2
2 50 mA ö
2 +2 5 1
8,2 V YE
3 3 YE 7 +
1 GN Power
1 +1 8
Isolating switching amplifier MK1-22UP-Ex0/MK1-22UN-Ex0
Ex-Approval acc. to Certificate of Conformity TÜV 03 ATEX 2031 TÜV 03 ATEX 2031
Maximum nominal values
– No load voltage U0 12 V 12 V
– Short-circuit current I0 36 mA 36 mA
– Power P0 ≤ 108 mW ≤ 108 mW
Maximum external inductances/capacitances
– [EEx ia] IIC 1 mH/610 nF (alt. 2/5 mH / 520/430 nF) 1 mH/610 nF (alt. 2/5 mH / 520/430 nF)
– [EEx ia] IIB 5 mH/2,4 µF 5 mH/2,4 µF
Marking of device I (1) GD [EEx ia] IIC II (1) GD [EEx ia] IIC
LED Indications
– Power "ON" green green
– Switching status 2 x yellow 2 x yellow
Subject to change without notice • Edition 02.04 • © Hans Turck GmbH & Co.KG 2004