You are on page 1of 9

1 2 3 4

A
04 Signal
04 Signal Properties
General
Name 04 Signal Number 4
Type FC Language LAD
Information
Title Author
Comment Family
Version 0.1 User-defined ID
B
Network 1: AUX. RELAY

Owner Project name 삼성 ENG_WQ_5.4MW_REV04 Date


2/13/2022
Project Path
C:\Users\Lenovo\Desktop\Abdullah Ali\Projects\EDG\for siemens
Operator
ENG_WQ_5.4MW_REV04_old_300718\for siemens ENG_WQ_5.4MW_REV04
Location

Designed By Description 1st

F
Checked By Description 2nd Language en-US
Approved By 1st View Version Sheet 1-1
1 2 3 4

Network 1: AUX. RELAY (1.1 / 5.1)


A

"DB10_Input". "DB20_Output".
"FAULT RESET_I" "FAULT RESET_O"

"DB40_Latch". "DB20_Output".
"GEN. HEAVY "GEN. HEAVY
FAULT" FAULT_O"

"DB10_Input".
"GEN. TIE CB
B FAULT SIGNAL_I"

"DB40_Latch". "DB20_Output".
"GEN. MEDIUM "GEN. MEDIUM
FAULT" FAULT_O"

"DB30_BZ,Lamp_ "DB20_Output".
Signal"."GEN. "GEN. LIGHT
LIGHT FAULT" FAULT_O"

C "DB10_Input". "DB10_Input".
"LOCKOUT RELAY "LOCKOUT RELAY
"DB10_Input". 86G TRIP (VCB "DB10_Input". 86E TRIP (ENGINE "DB40_Latch". "DB40_Latch".
"LOCKOUT RELAY OPEN COMMAND) "LOCKOUT RELAY STOP COMMAND)_ "GEN. HEAVY "GEN. MEDIUM
86G RESET_I" _I" 86E RESET_I" I" FAULT" FAULT"
1

"DB20_Output".
"DB10_Input". "FUEL OIL
"FUEL OIL TANK TRANSFER PUMP
LEVEL LOW_I" ON/OFF_O"

"DB20_Output".
"DB10_Input". "FUEL OIL
D "FUEL OIL TANK TRANSFER PUMP
LEVEL HIGH_I" ON/OFF_O"

"DB10_Input".
"BUS-B BREAKER "DB10_Input". "DB10_Input". "DB20_Output".
CLOSED STATUS_ "VCB CLOSE "GEN. TIE CB "VAR/PF CONTROL_
I" STATUS_I" FEEDBACK_I" O"

"DB10_Input". "DB10_Input".
"BUS-A BREAKER "BUS-TIE-CB
CLOSED STATUS_ BREAKER CLOSED
I" STATUS_I"

2.1 ( page 1 - 3)
Owner Project name 삼성 ENG_WQ_5.4MW_REV04 Date
2/13/2022
Project Path
C:\Users\Lenovo\Desktop\Abdullah Ali\Projects\EDG\for siemens
Operator
ENG_WQ_5.4MW_REV04_old_300718\for siemens ENG_WQ_5.4MW_REV04
Location

Designed By Description 1st

F
Checked By Description 2nd Language en-US
Approved By 1st View Version Sheet 1-2
1 2 3 4

Network 1: AUX. RELAY (2.1 / 5.1)


A
1.1 ( page 1 - 2)

"DB20_Output".
"DB10_Input". "DB10_Input". "DB10_Input". "DAMPER
"DAMPER OPEN_I" "FIRE ALARM_I" "CO2 RELEASE_I" CONTROL_O"
R

"DB20_Output".
"DB10_Input". "DAMPER
"FIRE ALARM_I" CONTROL_O"
S

"DB10_Input".
B "CO2 RELEASE_I"

"DB10_Input". "DB10_Input". "DB20_Output". "DB20_Output". "DB20_Output".


"DAMPER CLOSE_ "ENGINE "VENTILTATION "VENTILTATION "DAMPER
I" RUNNING_I" FAN ON/OFF 1" FAN ON/OFF 2" CONTROL_O"
S

"DB10_Input". "DB10_Input".
"DB10_Input". "DB10_Input". "DAMPER CLOSE_ "ENGINE "DB10_Input". "DB10_Input".
"DAMPER AUTO_I" "DAMPER OPEN_I" I" RUNNING_I" "FIRE ALARM_I" "CO2 RELEASE_I"
2

"DB10_Input". "DB20_Output". "DB20_Output".


C "ENGINE
RUNNING_I"
"VENTILTATION
FAN ON/OFF 1"
"VENTILTATION
FAN ON/OFF 2"
3

"DB10_Input".
"FIRE ALARM_I"

"DB10_Input".
"CO2 RELEASE_I"

"DB20_Output". "DB20_Output". "DB10_Input". "DB70_Timer".


"VENTILTATION "VENTILTATION "ENGINE "VENT FAN SET
FAN ON/OFF 1" FAN ON/OFF 2" RUNNING_I" ON DELAY"
D TON
T#7S

"DB70_Timer". "DB20_Output".
"VENT FAN SET "VENTILTATION
ON DELAY".Q FAN ON/OFF 1"
S

"DB20_Output".
"VENTILTATION
FAN ON/OFF 2"
S

"DB20_Output". "DB10_Input". "DB70_Timer".


E "VENTILTATION "ENGINE "VENT FAN RESET
FAN ON/OFF 1" RUNNING I" ON DELAY"

3.1 ( page 1 - 4)
Owner Project name 삼성 ENG_WQ_5.4MW_REV04 Date
2/13/2022
Project Path
C:\Users\Lenovo\Desktop\Abdullah Ali\Projects\EDG\for siemens
Operator
ENG_WQ_5.4MW_REV04_old_300718\for siemens ENG_WQ_5.4MW_REV04
Location

Designed By Description 1st

F
Checked By Description 2nd Language en-US
Approved By 1st View Version Sheet 1-3
1 2 3 4

Network 1: AUX. RELAY (3.1 / 5.1)


A
2.1 ( page 1 - 3)
FAN ON/OFF 1 RUNNING_I ON DELAY
TON
T#2M

"DB20_Output".
"VENTILTATION "DB70_Timer". "DB20_Output".
FAN ON/OFF 2" "VENT FAN RESET "VENTILTATION
ON DELAY".Q FAN ON/OFF 1"
R

"DB20_Output".
"VENTILTATION
FAN ON/OFF 2"
B R

"DB20_Output".
"DB10_Input". "VENTILTATION
"FIRE ALARM_I" FAN ON/OFF 1"
R

"DB10_Input". "DB20_Output".
"CO2 RELEASE_I" "VENTILTATION
FAN ON/OFF 2"
R

"DB10_Input".
"DB10_Input". "DB10_Input". "NO.1 DS
C "NO1 DS CLOSED "NO.1 VCB OPEN CLOSED STATUS_
STATUS_I" STATUS_I" INTERNAL"

"DB10_Input".
"DB10_Input". "DB10_Input". "NO.2 DS
"NO2 DS CLOSED "NO.2 VCB OPEN CLOSED STATUS_
STATUS_I" STATUS_I" INTERNAL"

"DB10_Input".
"DB10_Input". "NO.3 DS
"NO3 DS CLOSED CLOSED STATUS_
STATUS_I" INTERNAL"

"DB10_Input". "DB10_Input". "DB10_Input".


"NO.1 DS "NO.2 DS "NO.3 DS "DB10_Input". "DB70_Timer".
CLOSED STATUS_ CLOSED STATUS_ CLOSED STATUS_ "ENGINE "DS CLOSE
INTERNAL" INTERNAL" INTERNAL" RUNNING_I" DELAY"
TON
T#10S

"DB70_Timer". "DB70_Timer".
"DS CLOSE "DS CLOSE
DELAY".Q ORDER PLUSE"
TP
T#3S

E
"DB70 Timer" "DB20 Output"

4.1 ( page 1 - 5)
Owner Project name 삼성 ENG_WQ_5.4MW_REV04 Date
2/13/2022
Project Path
C:\Users\Lenovo\Desktop\Abdullah Ali\Projects\EDG\for siemens
Operator
ENG_WQ_5.4MW_REV04_old_300718\for siemens ENG_WQ_5.4MW_REV04
Location

Designed By Description 1st

F
Checked By Description 2nd Language en-US
Approved By 1st View Version Sheet 1-4
1 2 3 4

Network 1: AUX. RELAY (4.1 / 5.1)


A
3.1 ( page 1 - 4)
DB70_Timer . DB20_Output .
"DS CLOSE "NO1 DS CLOSE
ORDER PLUSE".Q ORDER_O"

"DB10_Input".
"NO.1 DS "DB70_Timer".
CLOSED STATUS_ "DS OPEN ORDER
INTERNAL" PLUSE"
TP
T#3S

"DB10_Input".
B "NO.2 DS
CLOSED STATUS_
INTERNAL"

"DB10_Input".
"ENGINE
RUNNING_I"

"DB70_Timer". "DB20_Output".
"DS OPEN ORDER "NO1 DS OPEN
PLUSE".Q ORDER_O"

"DB10_Input". "DB10_Input". "DB10_Input". "DB20_Output".


"VCB OPEN "ENGINE "LOCK-OUT TRIP "READY FOR
STATUS_I" RUNNING_I" RELAY_I" START_O"
E
1

5.1 ( page 1 - 6)
Owner Project name 삼성 ENG_WQ_5.4MW_REV04 Date
2/13/2022
Project Path
C:\Users\Lenovo\Desktop\Abdullah Ali\Projects\EDG\for siemens
Operator
ENG_WQ_5.4MW_REV04_old_300718\for siemens ENG_WQ_5.4MW_REV04
Location

Designed By Description 1st

F
Checked By Description 2nd Language en-US
Approved By 1st View Version Sheet 1-5
1 2 3 4

Network 1: AUX. RELAY (5.1 / 5.1)


A
4.1 ( page 1 - 5)
1

"DB20_Output".
"DAMPER
CONTROL_O"
2 R

"DB20_Output".
"DAMPER
CONTROL_O"
3 S

Owner Project name 삼성 ENG_WQ_5.4MW_REV04 Date


2/13/2022
Project Path
C:\Users\Lenovo\Desktop\Abdullah Ali\Projects\EDG\for siemens
Operator
ENG_WQ_5.4MW_REV04_old_300718\for siemens ENG_WQ_5.4MW_REV04
Location

Designed By Description 1st

F
Checked By Description 2nd Language en-US
Approved By 1st View Version Sheet 1-6
1 2 3 4

Symbol Address Type Comment


A
"DB10_Input" %DB1 Block_DB
"DB10_Input"."FAULT Bool
RESET_I"
"DB20_Output" %DB2 Block_DB
"DB20_Out‐ Bool
put"."FAULT RESET_O"
"DB10_Input"."BUS- Bool
TIE-CB BREAKER
CLOSED STATUS_I"
"DB10_Input"."LOCK‐ Bool
OUT RELAY 86G TRIP
(VCB OPEN COM‐
B MAND)_I"
"DB10_Input"."LOCK‐ Bool
OUT RELAY 86E TRIP
(ENGINE STOP COM‐
MAND)_I"
"DB10_Input"."VCB Bool
OPEN STATUS_I"
"DB10_Input"."ENGINE Bool
RUNNING_I"
"DB20_Out‐ Bool
put"."READY FOR
START_O"
C "DB10_Input"."BUS-A Bool
BREAKER CLOSED STA‐
TUS_I"
"DB10_Input"."BUS-B Bool
BREAKER CLOSED STA‐
TUS_I"
"DB10_Input"."FIRE Bool
ALARM_I"
"DB10_Input"."CO2 Bool
RELEASE_I"
"DB20_Out‐ Bool
put"."DAMPER CON‐
TROL_O"
D "DB10_Input"."FUEL Bool
OIL TANK LEVEL
LOW_I"
"DB20_Output"."FUEL Bool
OIL TRANSFER PUMP
ON/OFF_O"
"DB10_Input"."FUEL Bool
OIL TANK LEVEL
HIGH_I"
"DB30_BZ,Lamp_Sig‐ %DB3 Block_DB
nal"
"DB30_BZ,Lamp_Sig‐ Bool
E nal"."GEN. LIGHT
FAULT"
"DB20_Output"."GEN. Bool
HEAVY FAULT_O"

Owner Project name 삼성 ENG_WQ_5.4MW_REV04 Date


2/13/2022
Project Path
C:\Users\Lenovo\Desktop\Abdullah Ali\Projects\EDG\for siemens
Operator
ENG_WQ_5.4MW_REV04_old_300718\for siemens ENG_WQ_5.4MW_REV04
Location

Designed By Description 1st

F
Checked By Description 2nd Language en-US
Approved By 1st View Version Sheet 1-7
1 2 3 4

Symbol Address Type Comment


A
"DB20_Output"."GEN. Bool
MEDIUM FAULT_O"
"DB20_Output"."GEN. Bool
LIGHT FAULT_O"
"DB10_Input"."VCB Bool
CLOSE STATUS_I"
"DB10_Input"."GEN. Bool
TIE CB FEEDBACK_I"
"DB20_Output"."VAR/P Bool
F CONTROL_O"
"DB10_Input"."LOCK‐ Bool
OUT RELAY 86G RE‐
B SET_I"
"DB10_Input"."LOCK‐ Bool
OUT RELAY 86E RE‐
SET_I"
"DB40_Latch" %DB4 Block_DB
"DB40_Latch"."GEN. Bool
HEAVY FAULT"
"DB40_Latch"."GEN. Bool
MEDIUM FAULT"
"DB20_Output"."VEN‐ Bool
TILTATION FAN
ON/OFF 1"
C "DB20_Output"."VEN‐ Bool
TILTATION FAN
ON/OFF 2"
"DB70_Timer" %DB7 Block_DB
"DB70_Timer"."VENT IEC_Timer
FAN SET ON DELAY"
"DB70_Timer"."VENT Bool
FAN SET ON DELAY".Q
"DB70_Timer"."VENT IEC_Timer
FAN RESET ON DELAY"
"DB70_Timer"."VENT Bool
FAN RESET ON DE‐
LAY".Q
D
"DB10_Input"."DAMP‐ Bool
ER OPEN_I"
"DB10_Input"."DAMP‐ Bool
ER CLOSE_I"
T#2M T#2M Time
"DB10_Input"."DAMP‐ Bool
ER AUTO_I"
"DB10_Input"."NO1 Bool
DS CLOSED STATUS_I"
"DB10_Input"."NO2 Bool
DS CLOSED STATUS_I"
"DB10_Input"."NO3 Bool
E DS CLOSED STATUS_I"
"DB70_Timer"."DS IEC_Timer
CLOSE ORDER PLUSE"
T#3S T#3S Time

Owner Project name 삼성 ENG_WQ_5.4MW_REV04 Date


2/13/2022
Project Path
C:\Users\Lenovo\Desktop\Abdullah Ali\Projects\EDG\for siemens
Operator
ENG_WQ_5.4MW_REV04_old_300718\for siemens ENG_WQ_5.4MW_REV04
Location

Designed By Description 1st

F
Checked By Description 2nd Language en-US
Approved By 1st View Version Sheet 1-8
1 2 3 4

Symbol Address Type Comment


A
"DB70_Timer"."DS Bool
CLOSE ORDER
PLUSE".Q
"DB20_Output"."NO1 Bool
DS CLOSE ORDER_O"
"DB70_Timer"."DS IEC_Timer
OPEN ORDER PLUSE"
"DB70_Timer"."DS Bool
OPEN ORDER
PLUSE".Q
"DB20_Output"."NO1 Bool
DS OPEN ORDER_O"
B "DB70_Timer"."DS IEC_Timer
CLOSE DELAY"
T#10S T#10S Time
"DB10_Input"."GEN. Bool
TIE CB FAULT SIG‐
NAL_I"
"DB10_Input"."LOCK- Bool
OUT TRIP RELAY_I"
T#7S T#7S Time
"DB70_Timer"."DS Bool
CLOSE DELAY".Q
"DB10_Input"."NO.1 Bool
C DS CLOSED STA‐
TUS_INTERNAL"
"DB10_Input"."NO.2 Bool
DS CLOSED STA‐
TUS_INTERNAL"
"DB10_Input"."NO.3 Bool
DS CLOSED STA‐
TUS_INTERNAL"
"DB10_Input"."NO.1 Bool
VCB OPEN STATUS_I"
"DB10_Input"."NO.2 Bool
VCB OPEN STATUS_I"

Owner Project name 삼성 ENG_WQ_5.4MW_REV04 Date


2/13/2022
Project Path
C:\Users\Lenovo\Desktop\Abdullah Ali\Projects\EDG\for siemens
Operator
ENG_WQ_5.4MW_REV04_old_300718\for siemens ENG_WQ_5.4MW_REV04
Location

Designed By Description 1st

F
Checked By Description 2nd Language en-US
Approved By 1st View Version Sheet 1-9