You are on page 1of 63

Alarm Supply Pte Ltd

ARMSTRONG
TECHNICAL
MANUAL

35410R / 35411S

City & Date set at Validate review action

LPO1469036 : The document has been reviewed within


the scope of BV Rules NR566 Ch 4 & HSC Code 2000
Ch 7

System Apollo Fire Detection & Alarm System


Hull No H329, H331
Shipbuilder Penguin Shipyard International Pte Ltd
Classification BV
Vendor Alarm Supply Pte Ltd
Date 22 October 2018
Document No AS-1810-PSI01-FAMN01

Page 1 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Fire Alarm System

Scope of Supply

Page 2 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

APOLLO FIRE ALARM EQUIPMENT

Item Part Number Product Description Quantity

1 MA80162M2 Apollo, Syncro AS Marine, 2 Loops (126 Add/Loop) 1 set


Fire Control Panel - Analogue Addressable, Large LCD
Display, 3A PSU, 2 Sounder Circuits, 1000 Event Log
c/w 2x 12V 9AH SLA Battery - ABS, DNV
2 AS-PA-RLY Armstrong, PA Interface Relay Junction Box 1 no
3 58000-600MAR Apollo, Discovery Optical Smoke Detector (Add.) 17 nos
4 58000-400MAR Apollo, Discovery Heat Detector (Add.) 5 nos
5 58000-700MAR Apollo, Discovery Multisensor Detector (Add.) 2 nos
6 45681-210MAR Apollo, Marine Mounting Base c/w XPERT Card (for 24 nos
XP95 & Discovery)
7 45681-217APO Apollo, Deckhead Mounting Base, IP55, 6x M20 11 nos
Knock-Out Entries (Plastic) for S65/Orbis,
XP95/Discovery Detector
8 45681-233APO Apollo, Backplate, Dust & Moisture Protection for Base 5 nos
9 SA5900-928MAR Apollo, Intelligent Indoor Manual Call Point c/w 8 nos
Isolator (Add.)
10 58200-976MAR Apollo, Discovery Waterproof Manual Call Point c/w 8 nos
Isolator (Add.)
11 AS-624B Armstrong (HC-624B), 6” Alarm Bell, 24Vdc, Red 7 nos
Colour (UL Approved)
12 AS-624B/BB- Armstrong (HC-624B), 6” Alarm Bell, 24Vdc, Red 6 nos
2M20 Colour c/w Weatherproof Back Box (UL Approved)
13 958CHX1001 Banshee Excel Lite (CHX) Capsule Sounder & Xenon 3 nos
Beacon, 32 Selectable Sounds, 9-30Vdc, Max. 112
dBA, 90mA, Volume Control, 60fpm, Red Lens, Red
Finishing, IP66, Deep Base (For Indoor/Outdoor)
14 WR9304-SR KAC Class 9000, GA Push Button, Latch, SPDT Switch, 1 no
Red Colour & Back Box
15 PS200 KAC Plain Transparent Hinged Cover for WR9304-SR 1 no
SPARES
1 58000-600MAR Apollo Discovery Optical Smoke Detector (Add.) 1 no
2 58000-400MAR Apollo Discovery Heat Detector (Add.) 1 no
3 58000-700MAR Apollo, Discovery Multisensor Detector (Add.) 1 no
4 AERO-300001 AERO300 Smoke Canister (150ml) 1 no

Page 3 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Fire Alarm System

Calculations & Engineering Drawings

Page 4 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
SINGLE-LINE DRAWING
WR WR
ISO ISO ISO ISO ISO
UPPER DECK UPPER DECK UPPER DECK UPPER DECK UPPER DECK UPPER DECK UPPER DECK UPPER DECK MAIN DECK MAIN DECK MAIN DECK
WHEELHOUSE WHEELHOUSE WHEELHOUSE PAX. AREA PAX. AREA STBD PORT PAX. AREA PAX. AREA PAX. AREA PAX. AREA
PORT EXIT CTR STBD EXIT FWD AFT WC WC AFT EXIT FWD EXIT FWD PORT EXIT
WT WR WR WR
ISO ISO ISO
MAIN DECK MAIN DECK MAIN DECK MAIN DECK MAIN DECK MAIN DECK MAIN DECK MAIN DECK MAIN DECK MAIN DECK MAIN DECK
SWBD HANIDCAPPED CREW PAX. AREA PORT STBD PAX. AREA PAX. AREA PAX. AREA PAX. AREA PAX. AREA
ROOM WC ROOM AFT EXIT (P) WC WC AFT EXIT (S) AFT STBD CTR STBD EXIT PORT CTR
WT WT WT WT WT
WT WT WT WT
ISO ISO ISO ISO
LOWER DECK LOWER DECK LOWER DECK LOWER DECK LOWER DECK LOWER DECK MAIN DECK LOWER DECK LOWER DECK
(P) LR FUEL VOID (P) LR FUEL (P) TANK VOID (P) TANK VOID (P) ENG. RM. (P) ENG. RM. (P) ENG. RM. (P) AFT PEAK (P) AFT PEAK
ESC. HATCH VOID CTR CTR ESCAPE HATCH CTR ESCAPE HATCH ENTRANCE ESCAPE HATCH CTR
WT WT WT WT WT
WT WT WT WT
Legend:
ISO ISO ISO ISO
LOWER DECK LOWER DECK LOWER DECK LOWER DECK LOWER DECK LOWER DECK MAIN DECK LOWER DECK LOWER DECK
(S) LR FUEL VOID (S) LR FUEL (S) TANK VOID (S) TANK VOID (S) ENG. RM. (S) ENG. RM. (S) ENG. RM. (S) AFT PEAK (S) AFT PEAK
ESC. HATCH VOID CTR CTR ESCAPE HATCH CTR ESCAPE HATCH ENTRANCE ESCAPE HATCH CTR
WT
11 12 13 14 15 16
WT
WT
-
9 5 10 6 11 7 12 8
1 2 3 4
+
ISO
WT
ISO
1 2 3 4 5 6
WT
WT WT WT WT WT
Termination:
UPPER DECK UPPER DECK UPPER DECK MAIN DECK MAIN DECK MAIN DECK MAIN DECK LOWER DECK LOWER DECK LOWER DECK LOWER DECK LOWER DECK LOWER DECK LOWER DECK
PAX. AREA PAX. AREA PAX. AREA PAX. AREA PAX. AREA PAX. AREA PAX. AREA (P) LR FUEL (P) TANK (P) ENGINE (P) AFT (S) AFT (S) ENGINE (S) TANK
FWD PORT AFT CTR OUTSIDE FWD PORT CTR PORT CTR STBD AFT CTR VOID VOID ROOM PEAK PEAK ROOM VOID
WT
UPPER DECK LOWER DECK
WHEELHOUSE (S) LR FUEL
AFT VOID
ALARM SUPPLY PTE LTD 33M CATAMARAN FERRY
FIRE DETECTION & ALARM SYSTEM
18 Tuas Basin Link, Singapore 638784. www.penguin.com.sg
®
SYSTEM LAYOUT DRAWING
LEGEND:
MA80162M2 -Apollo Syncro 2 Loops
WR
58000-400MAR -Apollo Discovery Add. General Emergency Alarm (GA)
Analogue Add. Fire Alarm Panel Heat Detector + 45681-233 Backplate Push Button
58000-600MAR -Apollo Discovery Add.
WT
58000-700MAR -Apollo Discovery Add. Armstrong 150mm Dia. Alarm Bell
Optical Smoke Detector Smoke/Heat Det + 45681-217 Dkhd Box (Indoor)
WT
58000-600MAR -Apollo Discovery Add. 58200-971MAR -Apollo Discovery Add. WT
Armstrong 150mm Dia. Alarm bell
Opt. Smoke Det. + 45681-217 Dkhd Box ISO
Indoor Manual Call Point + Isolator + Weather-Proof Back Box
58000-400MAR -Apollo Discovery Add. WT 58200-976MAR -Apollo Discovery Add. Vimpex Excel 24Vdc Sounder Beacon
Heat Detector ISO
Weather-Proof Manual Call Point + Isolator + Weather-Proof Back Box.
01-008 01-007 01-005 B02-01 01-001 B01-01 GA-1
WR
ISO ISO
S OLAS LIFE RAFTS
ZODIAC SURVITEC
WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN
WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN
WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN
WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN
WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN
WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN
WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN
WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN
WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN
WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN

WEST MEKAN
B02-03 01-006 B02-02 01-004 01-003 01-002
WR
ISO
ALARM SUPPLY PTE LTD 33M CATAMARAN FERRY
FIRE DETECTION & ALARM SYSTEM
18 Tuas Basin Link, Singapore 638784. www.penguin.com.sg
®
LEGEND:
®

WT
ALARM SUPPLY PTE LTD

Heat Detector
58000-400MAR -Apollo Discovery Add.
Opt. Smoke Det. + 45681-217 Dkhd Box
58000-600MAR -Apollo Discovery Add.
Optical Smoke Detector
58000-600MAR -Apollo Discovery Add.
Analogue Add. Fire Alarm Panel
MA80162M2 -Apollo Syncro 2 Loops
18 Tuas Basin Link, Singapore 638784. www.penguin.com.sg

01-022

02-007
WT

WT
02-012

01-020
WT
01-016

01-021
ISO

WR
01-017

01-019
FIRE DETECTION & ALARM SYSTEM

ISO
WR
33M CATAMARAN FERRY

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN
B02-07

01-018
WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

ISO

ISO
WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WT

WR
WT
WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WR
WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

Weather-Proof Manual Call Point + Isolator


58200-976MAR -Apollo Discovery Add.
Indoor Manual Call Point + Isolator
58200-971MAR -Apollo Discovery Add.

Smoke/Heat Det + 45681-217 Dkhd Box


58000-700MAR -Apollo Discovery Add.
Heat Detector + 45681-233 Backplate
58000-400MAR -Apollo Discovery Add.
01-015

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN
01-012
WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN
01-014

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN
B02-05

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN
B02-06

01-011
ISO
01-013

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN
ISO

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN
01-010

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN
B02-04
01-009

WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN WEST MEKAN
WT
ISO

+ Weather-Proof Back Box.


Vimpex Excel 24Vdc Sounder Beacon
+ Weather-Proof Back Box
Armstrong 150mm Dia. Alarm bell
(Indoor)
Armstrong 150mm Dia. Alarm Bell
Push Button
General Emergency Alarm (GA)

SYSTEM LAYOUT DRAWING


SYSTEM LAYOUT DRAWING
LEGEND:
MA80162M2 -Apollo Syncro 2 Loops
WR
58000-400MAR -Apollo Discovery Add. General Emergency Alarm (GA)
Analogue Add. Fire Alarm Panel Heat Detector + 45681-233 Backplate Push Button
58000-600MAR -Apollo Discovery Add.
WT
58000-700MAR -Apollo Discovery Add. Armstrong 150mm Dia. Alarm Bell
Optical Smoke Detector Smoke/Heat Det + 45681-217 Dkhd Box (Indoor)
WT
58000-600MAR -Apollo Discovery Add. 58200-971MAR -Apollo Discovery Add. WT
Armstrong 150mm Dia. Alarm bell
Opt. Smoke Det. + 45681-217 Dkhd Box ISO
Indoor Manual Call Point + Isolator + Weather-Proof Back Box
58000-400MAR -Apollo Discovery Add. WT 58200-976MAR -Apollo Discovery Add. Vimpex Excel 24Vdc Sounder Beacon
Heat Detector ISO
Weather-Proof Manual Call Point + Isolator + Weather-Proof Back Box.
02-008 02-006 B02-10 02-005 B02-09 02-004 02-003 02-002 B02-08 02-001
WT WT WT WT WT
WT WT WT WT
ISO ISO ISO ISO
B02-11
WT
02-009
WT
02-010
B02-12
WT
02-011 02-013 B02-13 02-014 B02-14 02-015 02-016 02-017 B02-15 02-018
WT WT WT WT WT
WT WT WT WT
ISO ISO ISO ISO
ALARM SUPPLY PTE LTD 33M CATAMARAN FERRY
FIRE DETECTION & ALARM SYSTEM
18 Tuas Basin Link, Singapore 638784. www.penguin.com.sg
®
Alarm Supply Pte Ltd

Battery Size Calculation for Fire Alarm Panel

Project: 33M Catamaran Ferry


Hull No.: H329, H331
Project No.: AS-1810-PSI01-FADW01

Total Quiescent Current:

Fire Alarm Panel (MA80162M2) = 0.195A


Loop 1 = 0.007A
Loop 2 = 0.006A

Total = 0.208A

Total Alarm (Bell & Sounder/Beacon) Current:

Fire Alarm Panel (MA80162M2) = 0.370A


Loop 1 = 0.022A
Loop 2 = 0.020A
Bells = 0.260A (0.02A x 13 Bells)
Sounder/Beacon = 0.240A (0.08A x 3 Sounders/Beacons)

Total = 0.912A

Standby Current for 18 hours:

(0.208A x 1.25) x 18H = 4.680AH

Alarm Current for 30 min:

(0.912A x 1.75) x 0.5H = 0.798AH

Min Battery size required:

4.680AH + 0.798AH = 5.478H

The Battery Size Used on the Fire Alarm Panel is 9AH.

Page 9 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 10 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Fire Alarm System

Instruction Manuals

Page 11 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Apollo Syncro ASM


Analogue Addressable
Marine Fire Control Panel

Page 1
Page 12 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Index

Section Page

1. Introduction....................................................................................................... 3

2. Safety ............................................................................................................... 3

3. Panel Controls ................................................................................................... 4


3.1 Access Level 1 ............................................................................................ 4
3.2 Access Level 2 ....,....................................................................................... 5
4. Panel Operation ................................................................................................. 6
4.1 Fire Event .................................................................................................... 6
4.2 Fault Event .................................................................................................. 6
4.3 Pre-alarm event ........................................................................................... 6
4.4 Evacuate event ............................................................................................ 6
4.5 Alert event ................................................................................................... 7
5. Access 2 Menu ................................................................................................... 7
5.1 Disablements ............................................................................................... 7
5.2 View Devices ............................................................................................... 8
5.3 Test Zones ................................................................................................... 8
5.4 Set System Time ......................................................................................... 8
5.5 Contamination Status .................................................................................. 9
5.6 Access Level 3 ............................................................................................. 9

6. Routine Maintenance .......................................................................................... 9

Page 2

Page 13 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

1. Introduction
The Syncro ASM is a single or two loop analogue addressable fire detection and alarm control panel that
conforms to the requirements of European Standards EN54-2:1997 and EN54-4:1997.
It is capable of covering a maximum of 16 zones (500 zones on a network) with 126 devices of Apollo
protocol per loop.

Any number of devices can be allocated to any zone ensuring that any system configuration can be easily
accommodated.
Each detection device is allocated a message of up to 40 characters (including spaces) to assist in the
location of the devices.
The Syncro ASM control panel offers an extensive list of features and options for the control and monitoring
of plant, equipment and sounders.
The range of compatible devices includes optical and ionisation smoke sensors, heat sensors, multi-sensors,
flame detector, switch monitors and relay or bell controllers. Interfaces to conventional detection systems
can also be catered for using zone-monitoring devices.

2. Safety

This product should be installed, commissioned and maintained by trained service personnel in accordance
with the following:

(i) Regulations for electrical equipment


(ii) Codes of practice
(iii) Statutory requirements
(iv) Any instructions specifically advised by the manufacturer

You are therefore requested to take such steps as are necessary to ensure that you make any appropriate
information about this product available to anyone concerned with its use.
This equipment is designed to be operated from 230V 50Hz mains supplies and is of class 1 construction. As
such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a
readily accessible double pole disconnect device should be incorporated in the fixed wiring.
Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the
protective earth will render the equipment unsafe.

Page 3

Page 14 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd
3. Panel Controls
3.1 Access Level 1
The front panel contains controls for operating the panel.

Fig 1 – Syncro ASM Front Panel

Lamp Test
Press this button to illuminate all front panel indicators and validate correct operation.
Silence Buzzer
This button will silence the internal buzzer, and will illuminate the Buzzer Silenced panel indicator. No other
sounder outputs will be affected by this button operation.
More Fires
This button is used to view suppressed fire events. In the case of multiple fire activations, or when fire
activation information has been temporarily suppressed for menu navigation, the fire events can be quickly
restored and viewed by pressing this button.
More Events
This button is used to view all other suppressed events. In the case of multiple panel events or when any
event information has been temporarily suppressed for menu navigation, this button is used to display the
view events list.
Menu Navigation (up / down / left / right / enter / exit)
These are used to enter the password for access level 2 and are also used to navigate the Access 2 Facilities
Menu.

Help (?)
This button offers additional information relating to the current status of the control panel. e.g. if the panel is
in an alarm or fault condition then advice on the recommended action will be displayed or if a menu function
is being accessed then help relating to that function will be displayed.

Page 4

Page 15 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

3.2 Access Level 2


Access level 2 can be reached by operating the Enable control keyswitch (where fitted) or by pressing any of
the menu navigation (1, 2, 3 or 4) buttons. Pressing a menu button will then request the user to enter the
correct Access level 2 password (a 4 digit number) followed by the Enter button.

The factory default password for Access level 2 is 2222.

The Access level 2 password can be changed at commissioning to meet customer’s requirements. Enter the
Access level 2 password in the space below for future reference.
Access level 2 will be required by the end user to acknowledge alarms and reset the system.
Any persons responsible for the fire alarm system should be aware of the Access level 2 password to enable
the panel controls.
Without this password it will not be possible to acknowledge alarms or reset the system so it is most
important that the responsible person knows the password.

ACCESS 2 PASSWORD ………………………….

Silence Alarm / Acknowledge


This button is normally used to mute any fire warning sounders fitted to the Syncro ASM panel. These

sounders are installed throughout the protected premises and are used to evacuate the premises.

In some cases, the fire warning sounders may be delayed; to allow a search time before building evacuation
commences. In this case, the “Delay Active” panel indicator will be illuminated. If the Acknowledge Alarm
button is pressed during the Delay Active period, the sounders may either be permanently muted or the
delay may be extended to the second stage delay time. This will depend upon the panel configuration and
cannot be amended by the end user.

If there is a second fire activation during an Active Delay, then all delays are cancelled and outputs will
operate in accordance with the building fire strategy.
Re-sound Alarm
If any fire warning sounders have been muted using the Acknowledge Alarm button, then pressing the Re-
sound Alarm will re-energise all muted sounders.
Reset
This button is used to reset any activation that is defined as a latching input type. These will include fire and
pre-alarm events. In general, fault events are non-latching and cannot be cleared by operation of the Reset
button. These events will clear when the fault input is cleared.
Function button
This button is a software programmable input that may be used to perform customer-defined actions. The
default operation of these buttons is to perform no action (transparent input).

The operation of these buttons should be entered in the box below;

Function button ………………………..……………….


………………………..……………….

Evacuate button
Operation on the Evacuate button will cause all sounders on the system that are configured to respond to an
evacuate command (default) to sound continuously. The Evacuate button may be re-configured to sound the
abandon ship warning, 7 short bursts on the sounders followed by one long burst.

Page 5
Page 16 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd
4. Panel Operation
4.1 Fire Event
In the event of a fire, the red FIRE lamp and the appropriate Fire Zone indicator will flash. Details of the fire
activation (address and location text) will be given in the LCD Status display.
The fire warning sounders will sound throughout the vessel and the panel fire contact, alarm contact and fire
routing outputs will be energised.
The panel buzzer will be pulsing, but can be silenced by pressing the Silence Buzzer button.
To silence the fire warning sounders, press any of the menu navigation buttons and enter the Access 2
password (given in section 3.2) then press the Enter button.
The panel controls will now be enabled and will remain enabled for about 1 minute after the last key has
been pressed.
Pressing the Silence Alarm / Acknowledge button will now silence the sounders. The sounders can be
started again if required by pressing the Re-Sound Alarm button
The system can be reset by pressing the Reset button.
If there are more than two zones in fire on the system then these may be viewed in the text display by
pressing the More Fires button.

4.2 Fault Event


If there is a fault on the system, the yellow General Fault indicator will be flashing and there may be other
fault LED indications which identify the nature of the fault.
The Fault Contact will be energised and the panel buzzer will be sounding continuously.

Details of the fault will be described in the text display.

The panel buzzer can be silenced at any time by pressing the Silence Buzzer button.

If there are more than two fault events on the system then these may be viewed in the text display by
pressing the More Events button.

4.3 Pre-alarm event


Sensors or inputs can generate a pre-alarm. A pre-alarm is used to warn of a slow change in the analogue
level from detection devices, typically due to a smouldering fire. When a pre-alarm is generated, the control
panel will illuminate the pre-alarm LED and will sound the internal buzzer continuously. The address and
location of the source of the pre-alarm will be indicated in the LCD status display.

The source of the pre-alarm input should be investigated.

The panel buzzer can be silenced at any time by pressing the Silence Buzzer button.

If there are more than two fault events on the system then these may be viewed in the text display by
pressing the More Events button.

4.4 Evacuate event

An input on the system can be configured to create an Evacuate or abandon ship event. Operation of an
evacuation input or the Evacuate button will cause the red FIRE lamp to illuminate and all sounder devices to
be operated continuously or if configured as an abandon ship signal, the abandon ship signal to be sounded.
The panel buzzer will sound continuously and the source of the evacuation event will be shown in the LCD
status display.
The panel buzzer can be silenced at any time by pressing the Silence Buzzer button.
To silence the fire warning or abandon ship sounders, press any of the menu navigation buttons and enter
the Access 2 password (given in section 3.2) then press the Enter button.
The panel controls will now be enabled and will remain enabled for about 1 minute after the last key has
been pressed.
Pressing the Acknowledge Alarm button will now silence the sounders
If the source of the event is a latching input, then pressing the Reset button will reset the system.

Page 6
Page 17 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd
4.5 Alert event
An input on the system can be configured to create an Alert event. Operation of an Alert input will cause all
sounder devices to be pulsed on a 1 second cycle.
The panel buzzer will sound continuously and the source of the alert event will be shown in the LCD status
display.
The panel buzzer can be silenced at any time by pressing the Silence Buzzer button.

To silence the fire warning sounders, press any of the menu navigation buttons and enter the Access 2
password (given in section 3.2) then press the Enter button.

The panel controls will now be enabled and will remain enabled for about 1 minute after the last key has
been pressed.
Pressing the Acknowledge Alarm button will now silence the sounders
If the source of the event is a latching input, then pressing the Reset button will reset the system.

5. Access 2 Menu
There are a number of menu options available at access level 2. To view this menu, press the Right (2)
pointing arrow key and enter the Access 2 password (given in section 3.2) then press the Enter button or
operate the Enable controls keyswitch if fitted.

The panel controls will now be enabled and will remain enabled for about 120 seconds after the last key has
been pressed.
When in Access 2, press any of the four navigation buttons to view the Access 2 menu.
To navigate the menu, use the Up (1) and Down (3) buttons to move the cursor to the required menu
option. Use the Right (2) button to select the highlighted menu option. Use the Left (4) button to exit back
to the main menu. Use the Enter button to input the required information and the Exit button to cancel any
data selection. Pressing the Help (?) button will display the help screen appropriate to the current menu
selection.

ACCESS LEVEL 2
Disablements
View devices
Test Zones
Set system time
Contamination Status
Access level 3

Main menu items available at access levels 2:

5.1 Disablements
Any disablements made using this menu will remain active until the disablement is cleared by manual
intervention at the panel.
Disable Immediate Output Response
If any outputs are configured to be delayed (an Access Level 3 configuration operation), then EN54 requires
that these outputs are not delayed, unless set to do so at Access Level 2. This menu option allows delays to
outputs to be activated, by disabling the immediate response facility.
Disable Zones
All detection devices, including manual call points, are disabled in the selected zone.

Disable Addresses
Any loop device can be disabled using this menu option. In devices with more than one input or output, then
each sub-address may be individually disabled.

Page 7
Page 18 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Disable Sounders
This menu option is used to disable all sounder outputs fitted to the control panel. A sounder output is
defined as any output that has been set to respond to the Silence and Evacuate panel commands. Sounder
outputs may be directly wired to the control panel (Sounder circuits 1 and 2) or loop driven devices.

The Sounder Fault / Disabled LED indicator will be illuminated, as well as the General Disablement Indicator.
Disable Panel Outputs
This menu option allows the following panel outputs to be independently disabled;

• Fire Contact
• Alarm Contact
• Fault Contact

When the Fire Routing output is disabled, the front panel Fire Routing Fault / Disabled indicator and General
Disablement indicator will be permanently illuminated.
View / Restore Disablements
To cancel any disablements, there are two options. The first is to scroll through each individual menu option,
then toggle any disablements to the normal condition. The second, preferred option, is to use the View /
Restore Disablements option. This menu option will allow the user to scroll through all active disablements
and individually enable each disablement by pressing the Enter button.

5.2 View Devices


This menu option permits the user to view all addresses connected to the detection circuit. For each address
& sub-address, the LCD status display will give the device type, zone and location text. In addition, analogue
devices will give an indication of the analogue value of the current device.
For digital input devices (Manual call points, switch monitor units etc) the input state is given, either as
Normal or Activated. For output devices, the output state will be shown as either Normal, Intermittent of
Continuous.

This menu is used by experienced personnel to investigate the current status of the system and may help in
fault finding techniques.

5.3 Test Zones

Test Zones
Each zone may be individually put in to a Test Mode condition. When test mode is selected, the devices in
the zone may be tested and the Syncro ASM panel will automatically reset after 3 seconds. This is used for
one man testing of the fire system.

When a zone is put in to test mode, the user is prompted to select the sounder response behaviour for the
selected zone. When set to the ON position, all sounder outputs will sound for the duration of the fire event.
The sounders will be muted when the panel automatically resets.

NOTE: On systems with a high number of Loop powered sounders fitted, all sounders may not be able to
activate within the 3 second fire period and therefore loop sounder confirmation may be intermittent.

View & Restore Zones in Test


To cancel any zones in test, there are two options. The first is to scroll through each zone in the Test Zone
menu, then toggle any active zones to the normal condition. The second is to use the View / Restore Zones
in Test option. This menu option will allow the user to scroll through all active zones in test and individually
enable each disablement by pressing the Enter button.

5.4 Set System Time


This menu option is used to set the panel date and time. This is necessary so that any events are accurately
logged in the event log and on the panel printer (if fitted). The panel automatically compensates for daylight
saving time.

Page 8
Page 19 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

5.5 Contamination Status


Any detection devices that exceed 85% of the limit for the manufacturers working range during the daily
calibration sequence are added to a contaminated device menu. At this stage, the panel will not notify the
user of a fault for the contaminated devices.
This menu option allows the user to see any devices approaching their maintenance fault limits and to
prevent unnecessary faults being reported from dirty detection devices.

This menu is typically used as a preventative maintenance feature.

5.6 Access Level 3


This menu option is used to enter the access 3 password for the engineering function menu.
Details of the options available at Access level 3 can be found in the Syncro ASM Product manual.

6. Routine Maintenance
Syncro ASM control panels do not require any specific maintenance but should the control panel become
dirty it can be wiped over with a barely damp cloth. Detergents or solvents should not be used to clean the
panel and care must be taken that water does not enter the enclosure.

The control panel contains sealed lead acid batteries to provide standby power in the event of mains failure.
These batteries have a life expectancy of around 4 years. It is recommended that these batteries be
annually tested in accordance with the battery manufacturer’s recommendations to determine their
suitability for continued standby applications.

Routine testing of the fire alarm system will identify any malfunction of the control panel and any
malfunction should be reported to the fire alarm maintenance company immediately.

Detection devices are automatically calibrated on a daily basis and any devices that fail the detector
manufacturer requirements will be notified as a maintenance fault. The contamination status menu is also
useful in determining detection devices that are approaching their working range limits (see 5.5 above).

Page 9
Page 20 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

APOLLO ADDRESSABLE FIRE DETECTION & ALARM SYSTEM


COMMON FAULT LIST
No. Faults Action
1. Mains Fault Check Mains Power Supply (220VAC) or
AC Fuse in the Panel.
2. Battery Low Voltage Check Battery Voltage (must be >24Vdc).
Replace Batteries if necessary.
3. Battery Disconnected Check Battery Connection or Battery Fuse
(located back of display panel).
4. NODE = Z System Reset, System fault Press the ‘Reset’ button.
(Z denotes node number)
5. AD=XXX, LP=Y, ND=Z Internal Fault Replace the Detector at the Address XXX.
(X denotes device address)
(Y denotes loop number)
(Z denotes node number)
6. AD=XXX, LP=Y, ND=Z Double Address Check the Panel for ‘Disconnected Fault’
(X denotes device address) under ‘MORE EVENTS’; Rectify the
(Y denotes loop number) Devices with the ‘Disconnected Fault’ (refer
(Z denotes node number) to No.7).
7. AD=XXX, LP=Y, ND=Z Disconnected fault For detector, unplug the device. For MCP,
(X denotes device address) unplug the cable connector. Check the
(Y denotes loop number) voltage and address setting. If voltage is less
(Z denotes node number) than 20Vdc, check wiring. Plug back the
detector or MCP cable connector properly.
Press the ‘Reset’ button.
8. AD=XXX, LP=Y, ND=Z Wrong Device Type Check the single line drawing in the manual.
(X denotes device address) Replace with the correct device type.
(Y denotes loop number)
(Z denotes node number)
9. FAULT : SOUNDER CIRCUIT X Remove ‘+ve’ & ‘-ve‘ cables for Sounder
Monitored Output fault Circuit X. Measure for resistance between
(X denotes 1 or 2 ) ‘+ve’ & ‘-ve‘ cables. (Condition: ≈10KΩ is
normal, ‘infinity’ is open circuit, 1KΩ and
below is short circuit). Rectify cable
accordingly.
10. LOOP=X, Loop short circuit Check Loop X wiring for short circuit. Reset
(X denotes 1 or 2 ) after rectification.
11. LOOP=X, Loop open circuit Check Loop X wiring for open circuit. Reset
(X denotes 1 or 2 ) after rectification.
12. Earth fault Check all the field cables for Low Resistance
(ohm) - leakage to Earth. Reset after
rectification.
Please contact us @ +65 62583445 or ask@alarmsupply.com.sg for other faults.

Page 21 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Fire Alarm System


System

Product Catalogue & Data Sheets

Page 22 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 23 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 24 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 25 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 26 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 27 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 28 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 29 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 30 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 31 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 32 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 33 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 34 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 35 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 36 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 37 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 38 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 39 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 40 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 41 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 42 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Fire Alarm System

Product Certificates

Page 43 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 44 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 45 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 46 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 47 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 48 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 49 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 50 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 51 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 52 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 53 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 54 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 55 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 56 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 57 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 58 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 59 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 60 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 61 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 62 of 63
63 Jalan Pemimpin #03-07 Pemimpin Industrial Building, Singapore 577219
Tel: (65) 6258 3445 Fax: (65) 6258 6428 Email: sales@alarmsupply.com.sg
Alarm Supply Pte Ltd

Page 63 of 63