Professional Documents
Culture Documents
HEPE
Dept:
0 EN 118 HTP-ER-OM-A-3
File no.:-
OPERATION REGULATION
FOR
ELECTRIC SYSTEM
哈尔滨汇通电力工程有限公司
CONTENT
1 Unit Overall Design .....................................................................................................................4
2 General Specifications................................................................................................................4
2.1 Generator Insulation Level ..................................................................................................5
2.2 Basic Technical Parameters of the Main Transformer ........................................................7
2.3 Main Parameters of Outlet Circuit Breaker of Generator .................................................10
2.4 Parameters of 13.8kV Common Enclosed Bus ................................................................ 11
2.5 Parameters of Voltage Transformer .................................................................................. 11
2.6 Parameters of Current Transformer ..................................................................................12
2.7 Parameters of Arrester ......................................................................................................12
2.8 Parameters of Neutral Point Grounding Transformer ....................................................... 13
2.9 Parameters of Excitation System ......................................................................................13
2.10 Specifications of House-Service Equipment...................................................................14
2.11 138kV Outdoor Equipment .............................................................................................. 26
3 Start/Stop Auxiliary Equipments of Unit .................................................................................33
3.1 Operation of Transformer Cooling Device ........................................................................33
3.2 Start/Stop Operation of DC System ..................................................................................37
3.3 Start/Stop Operating UPS .................................................................................................38
3.4 Start/Stop Diesel Generator .............................................................................................. 42
3.5 Operation of 13.8kV System Grounding ...........................................................................46
3.6 138kV System Operation ..................................................................................................49
4 Start/stop of Generator .............................................................................................................53
4.1 GCB Operation of Generator before Parallel Operation...................................................53
4.2 Parallel Load-carrying of Generator..................................................................................53
4.3 Notes in the Process of Generator Startup.......................................................................54
4.4 Generator Trip and Outage ............................................................................................... 56
4.5 Operation after Unit Outage .............................................................................................. 56
5 Maintenance and Operation Mode during Unit Operation ....................................................57
5.1 Inspection during Normal Operation of Generator ........................................................... 57
5.2 Monitoring and Inspection of Transformer Normal Operation ..........................................57
5.3 Inspection during Operation of DC System ......................................................................60
5.4 Maintenance of Electric Motor during Operation .............................................................. 61
5.5 Inspection and Maintenance of UPS ................................................................................64
5.6 Inspection, Operation and Maintenance of Security Power Supply and Emergency Diesel
Engine .....................................................................................................................................64
5.7 Operation Mode of Transformer ........................................................................................ 65
5.8 Operating Mode of High-voltage Auxiliary Power System ................................................67
5.9 Operating Mode of Low-voltage Auxiliary System ............................................................ 68
5.10 Operating Mode of Security Power of Unit .....................................................................69
5.11 General Provisions of Operation and Management of Electric Motor ............................ 69
5.12 Operating Mode of Electric Motor ...................................................................................70
5.13 Operating Mode of DC System ....................................................................................... 72
5.14 Operating Mode of UPS ..................................................................................................75
5.15 Operating Mode of Generator ......................................................................................... 76
5.16 Operating Mode of Power Distribution Device................................................................ 77
5.17 Lightning Arrester ............................................................................................................81
5.18 Power Cable....................................................................................................................82
Generator and auxiliary power system are all controlled by Distributed Control System
(DCS), main transformer and 138kV transmission line are all controlled by Net Control
System (NCS), bus equipments, and utility equipments are all monitored by a network
computer monitoring system, and the computer monitoring console is set up in
centralized control room. Electrical components in unit control room are provided with
computer-based protection devices.
2 General Specifications
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 5 / 118
Rated frequency fN Hz 60
2 Short circuit
3 Voltage variation
4 Reactive loading
5 Torque
The peak values of sudden short circuit air 2-phase short circuit: 585 %
gap torques: 3-phase short circuit: 415 %
6 Other
2.1.3 Current transformer is provided with a shield-type Bushing to generator for the
use of relay protection, voltage regulator and electric meter. It shall be installed onto
leading-out terminal of generator stator coil, with the secondary side lead connected
into in-situ terminal box.
500/7A PX
Short-circuit impedance: 12.5% (at rated voltage & frequency, the temperature shall
be 75 ℃)
High-voltage side: connected to 138kV SF6 using oil & gas Bushing to realize
completely closed electrical connection;
short-time power-
Full-wave of lightning Chopped wave of
frequency withstand
surge lightning surge
voltage Operation Impact
Neutral point of
140 325 325 ―
high-voltage
Withstand voltage:
(Peak, kV)
(RMS, kV) (Peak, kV)
Low-voltage 85 200 -
400/5A 0.2s 1
Cable outlet side of high-voltage
400/5A 5P20 2
Model: HVX-17-40
Number of phase: 3
Operating mechanism adopts hydraulic spring operating, remote and local operation,
three-phase linkage, with a rated control voltage of DC125V, a operating voltage for
energy storage motor of DC125V.
Opening: 85 - 110%
Reclosing: 85 - 110%
Type BGFM-13.8/3000-Z
Altitude ≤ 1000m
Site: Indoor
Model: JDZX9-15FG
Accuracy: 3P/3P
Altitude: ≤1000m
Rated frequency: 60 Hz
Model: HY5WD-17.5-40Q
2ms
Min.D.C.
Continuous Max. Rectangular
Rated reference 4/10µs
Operating residual current
voltage voltage at high
TYPE voltage voltage discharge
1mA Current
(kV) capacity
(kA)
(kV) (kV)
(kV)
(kA)
Model: DKDC-80
The main technical data and performance accord with the relevant standard.
Rated
Model SCB10-2000/13.8 2000kVA Rated voltage 13.8±2×2.5%/0.48kV
capacity
Rated Number of
60Hz 3 Linked group Dyn11
Frequency phases
Voltage
Rated Current 84/2406A regulation ±2×2.5% Cooling method AN/AF
range
Insulation Temperature
LJ105-AC46/AC3 150℃
level rise of winding
Neutral point
1000/5A
bushing CT
5-6 14490
4-6 14145
4-7 13800
3-7 13455
3-8 13110
Rated
Model SCB10-2000/4.16 2000kVA Rated voltage 4.16±2×2.5%/0.48 kV
capacity
Rated Number of
60Hz 3 Linked group Dyn11
Frequency phases
Voltage
Rated Cooling
278/2406A regulation ±2×2.5% AN/AF
Current method
range
Insulation Temperature
LI105-AC25/AC3 150℃
level rise of winding
Neutral point
1000/5A
bushing CT
5-6 4370
4-6 4265
4-7 4160
3-7 4055
3-8 3950
Model: KOHLER1600EROZM
Generator:
Model: 7M4050
Bearing number: 1
P(kW) 22
Sd (kVA) 22
Function group Motor technology data Quantity Control position Mount position
kW V A R/min
Function group Motor technology data Quantity Control position Mount position
kW V A R/min
Function group Motor technology data Quantity Control position Mount position
kW V A R/min
Function group Motor technology data Quantity Control position Mount position
kW V A R/min
17 Diesel engine leakage oil module 2.2 480 1 Local Main building
Function group Motor technology data Quantity Control position Mount position
kW V A R/min
Function group Motor technology data Quantity Control position Mount position
kW V A R/min
Function group Motor technology data Quantity Control position Mount position
kW V A R/min
30 Sewage pump (in oil treatment room) 3 480 1 Local Oil treatment room
To earth 275
Rated Power Frequency Withstand
2
Voltage(1min)
Across break 275+40
To earth 650
Rated Lightening impulse withstand kV
3
voltage
Across break 650+100
MPa
24 Creepage Distance mm
To Earth 4495
kg
DC110/4; DC220/2;
2 Open coil voltage V/A
AC220/5,DC48/4
DC110/4;DC220/1.3;
3 Close coil voltage V/A
AC220/5,DC48/4
Power W 720
To earth kV 310
2
To earth kV 735
3150 5000
5 Rated short time withstand current kA 40 50
7 Disconnector s 3
3
Earthing switch s 3
3
Rated mechanical terminal loads
Item Value
Starting Current A ≤ 5, ≤ 25
Item Value
Output Shaft Output Rotation Angle Of The Operated Mechanism 90°, 180°
3.1.2 Cooling devices of main transformer are provided with 2 ways of power supply,
of which one way is for working, the other is alternative under normal operation. When
one way of power fails, another way will be applied automatically. Power for
transformer cooler shall be regularly switched.
3.1.3 When temperature of upper oil of main transformer is higher than 65℃, auxiliary
cooler will be put into operation automatically, when temperature drops down to 55℃,
it will stop running automatically. When oil temperature of main transformer rise to
85℃, it will give an alarm, in case of 100℃, it will give an ultra-high alarm.
3.1.4 Each set of high-voltage operation transformer is provided with two groups of
coolers, each of which has two fans.
3.1.5 Two groups of coolers of high-voltage operation transformer will be divided into
two operation levels: set control switch of one group of coolers to “Temperature 1”
position and that of the other group of coolers to “Temperature 2” position, operation
mode shall be shifted on a regular basis. The 1st group of coolers will start up when
temperature of upper oil of main transformer is at 55 ℃, and the 2nd group of coolers
will be enabled when temperature of upper oil of main transformer is up to 65 ℃.
When high-voltage operation transformer has loads beyond designated, the coolers
switched at both "Temperature 1” and "the temperature 2” position can be activated
automatically.
3.1.6 Under the condition that temperature rise of winding on high-voltage operation
transformer is at 65℃, the following two types of cooling can continuously operate
with load as follows:
For oil-immersed self-cooled (0NAN), it can continuously operate with 60% of rated
load.
For oil-immersed air-cooled (ONAF), it can continuously operate with 100% of rated
load.
3.2.8.2 Install control loop AC fuses F1-F4, FC1-FC4 on main transformer cooler,
close control loop small switches 5Q, 6Q on cooler. Heating / lighting small switch QA.
Close power switches Q1-Q4 on each of group of coolers of main transformer.
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 35 / 118
3.1.8.3 Check if 2-ways of power supply for transformer coolers are normal, set small
switch SL for power monitoring of main transformer cooler to "On", remote / in situ
small switch SY to "In situ", power control switch SS to cut “Power I ON” or "Power II
ON", automatic on/off switch ST to "on” position, and lighting heating small switch SH
will be turned on/off depending on ambient temperature.
3.1.8.4 Set control switch SC1-SC4 for main transformer cooler to "ON", "Standby” or
"Auxiliary” position.
3.1.8.5 After main transformer is put into operation, check if transformer fan and oil
pump are running normally.
3.1.9.1 Set control switch SC1-SC4 for main transformer cooler to "Off” position.
3.1.9.2 Set small switch SY on control box of main transformer cooler to "Off", SS to
"Off", ST to "Test” and SL to "Off” position.
3.1.9.3 Open up control loop small power switches 5Q, 6Q and small power switches
Q1-Q4 on coolers. Remove control loop AC fuse F1-F4, FC1-FC4.
3.1.9.4 Disable as the case may heater on control box of main transformer cooler.
b) Close small mains control switch Q2.1, Q2.2 on cooler, small mains control switch
Q13 on fan, temperature signal small mains switch Q22 and lighting heating small
mains switch Q12.
d) Set master power control switch S30 on cooler to "power I” or "power II".
f) Set start-up mode control switches S32.1, S32.2 on fan to the required positions
(Manual, Temperature 1, Temperature, 2), and then fans can be activated in mode as
set.
a) Set start-up mode control switches S32.1, S32.2 on fan to “Off” position.
a) Set start-up mode control switches S32.1 (or S32.2) on one group of fans s to
"Temperature 1” position.
b) Set start-up mode control switches S32.2 (or S32.1) on one group of fans s to
"Temperature 2” position.
3.1.9.9.1 Supply cooler with power, close AC power switch on control box.
3.1.9.9.2 Check if lamp light on temperature controller is normal and indications of all
parameters are normal.
3.1.9.10.1 When power of cooling device disappears completely, shall find out
reasons rapidly and try all ways to restore one way power supply as soon as possible,
meanwhile, shall be monitor closely conditions of temperature and the side-load of the
transformer, if necessary, and lower output of operation.
3.1.9.10.2 When malfunction signal is given from transformer cooling device, operator
shall find out reasons in situ immediately and address it. If cannot deal with this, shall
promptly notify the maintenance personnel to come to deal with.
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 37 / 118
3.2.1.1 Check if air input switch of this charging module of charger is located at “Off”
position.
3.2.1.2 Close air input switch of this charging module of charger, power lights “on” and
display shows that output voltage and current are normal.
3.2.2.3 Check if the display of this charging module of charger station charger
charging shows no signal.
3.2.3 Operation steps of main auxiliary DC125V charger and storage batteries (take
generator unit 125V DC as an example, same as net unit 125V DC)
3.2.3.2 Check if air input switch of each of charging module of 125V charger is set on
“Off” position.
3.2.3.5 Close air input switch of each of charging module of 125V charger
3.2.3.6 Check if output voltage of 125V charger is in line with DC voltage of bus
section.
3.2.3.7 Shift switches 1QAS1 of 125V charger from "OFF” to "Bus section” position.
3.2.3.11 Shift switches 1QAS1 of 110V charger from "Bus section” to "Normal load”
position.
3.2.4 DC 125V charger and storage battery exit operation steps: (take generator unit
125V DC as an example, same as net unit 125V DC)
3.2.4.1 Shift switches1QAS1 of 125V charger from “Bus section “to” OFF” position.
3.2.4.3 Open air input switch of each of charging module of 125V charger.
3.3.1.1 Check if UPS cabinet battery switch (DC switch), bypass power switch, 480V
AC power switch (rectifier switch), output switch (output switch) are in “off” position.
3.3.1.2 UPS 480V AC main power I (II) and the bypass power shall be sourced from
480V MCC section, UPS125V DC power supply shall be supplied from 125V unit DC
system.
3.3.1.3 Close 480V main power I (II) switch from 480V MCC section.
3.3.1.5 Check if lamps “CHARGER”, “INVERTER”“INV” turn on, check if green lamps
3.3.1.6 Close DC power switch (DC switch) on UPS cabinet, red lamp "BATTERY”
turns off, "ALARM” turns off.
3.3.1.7 Close UPS power output switch (output switch), check if UPS is working
correctly.
3.3.1.8 Close each of loading switches on UPS feeder cabinet, and check if UPS
voltage, current and frequency shown on UPS are normal.
3.3.2 Shift operation of UPS cabinet from main power to bypass power
3.3.2.1 Check if main power and bypass power of UPS device are shown normal
("CHARGER", "BYPASS” power lights turn on).
3.3.2.2 Press continuously buttons "B / P, INV” on panel of UPS cabinet twice, check if
UPS cabinet is operating normally after shifting from main power to bypass power
(lamp "INV” off, lamp "B / P” on).
3.3.3 Shift operation of UPS cabinet from bypass power to main power.
3.3.3.1 Check if main power and bypass power of UPS device are shown normal
("CHARGER", "BYPASS” power lights turn on).
3.3.3.2 Check if synchronizing lamp "SYNC” and inverter lamp "INVERTER” of UPS
device turns on.
3.3.3.3 Press continuously buttons "B / P, INV” on panel of UPS cabinet twice, check if
UPS cabinet is operating normally after shifting from bypass power to main power
(lamp "INV” on, lamp "B / P” off).
3.3.4 Shift operation of UPS cabinet from main power to maintenance bypass power.
3.3.4.1 Check if main power and bypass power of UPS device are shown normal
("CHARGER", "BYPASS” power lights turn on).
3.3.4.3 Press continuously buttons "B / P, INV” on panel of UPS cabinet twice, check
if UPS cabinet is operating normally after shifting from main power to bypass power
3.3.4.7 Press continuously buttons "Start / Stop” on panel of UPS cabinet twice, check
if UPS cabinet is operating normally.
3.3.4.8 Turn off DC power switch of storage battery of UPS cabinet (BATTERY CB).
3.3.4.10 Turn off main power input switch of UPS cabinet (CHARGER CB).
3.3.5 Shift operation of UPS cabinet from maintenance bypass power to main power.
3.3.5.5 Close main power input switch of UPS cabinet (CHARGER CB).
3.3.5.7 Check if main power and bypass power synchronizing lamp "SYNC” of UPS
cabinet turns on.
3.3.5.8 Press continuously buttons "B/P, INV” on panel of UPS cabinet twice to switch
from bypass power to main power.
3.3.6.1 Check if battery switch UPS cabinet to be carried out parallel operation,
bypass power switch, 480V AC power switch, output switches are in “OFF” position.
Check if maintenance bypass switch is in “OFF” position.
3.3.6.2 AC power supply for UPS cabinet to be carried out parallel operation shall be
sourced from 480V MCC section, and power supply for UPS to be carried out parallel
operation shall be supplied from 125V DC system.
3.3.6.3 Close 480V AC main power switch of UPS cabinet to be carried out parallel
operation.
3.3.6.4 Check if UPS bypass power cabinet has been supplied electrified, and close
bypass power switch of UPS cabinet to be carried out parallel operation.
3.3.6.5 Check if lamps "CHARGER", "INVERTER” "INV” turn on. Check if lamp
"BYPASS” on.
3.3.6.6 Check if main power and bypass power synchronizing lamp "SYNC” of UPS
cabinet turns on.
3.3.6.7 Close DC power switch, alarm red light "BATTERY” off, and red lamp "ALARM”
off.
3.3.6.8 Measure and check if voltage difference, between output voltage of cabinet to
be carried out parallel operation and output voltage of cabinet being carried out
parallel operation, is less than 4V, then close output switch of cabinet to be carried out
parallel operation.
3.3.7.1 Check if both input and output switches of UPS bypass cabinet are set at “OFF”
position, bypass switch of automatic voltage regulator is in the middle position, and
small switch of voltage regulating mode (automatic transfer) in the automatic (on)
position.
3.3.7.2 Check if 480V AC power has been supplied to UPS bypass cabinet
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 42 / 118
3.3.7.3 Install fuse to control loop of UPS bypass automatic voltage regulator.
3.3.7.4 Close bypass switch of UPS automatic voltage regulator to the "run” position
(up).
3.3.8.1 Shall check if fan runs normally before put inverter into use.
3.3.8.2 Maintenance bypass switch can be used only if UPS stops operation for
repairing.
3.3.8.3 It is strictly prohibited to press button “start/stop” on UPS panel when UPS
device is running, or may result in serious consequences of outage.
3.3.8.5 Before main circuit and bypass shift each other, shall check if both of 2
inverters are synchronized with bypass.
3.3.8.6 It is strictly prohibited to press "STOP BUTTON” on bypass cabinet when UPS
device is running.
3.3.8.7 When UPS device is supplied power and start operation, storage battery
switch shall be closed only after turn on main loop power and output green lamps
"INVERTER", "INV” of charger & inverter turn on.
3.4.1.2 Check the engine lubricating oil and coolant levels, top up as necessary. Do
not remove the coolant filler cap while the engine is hot.
3.4.1.3 Check the fuel level, fill/top up as necessary. Always wear protective clothes
and hand protection, do not smoke or have any source of ignition nearby
3.4.1.4 Check the tension and the condition of all drive belts. Re-tension or replace as
necessary.
3.4.1.5 Check all hoses for leaks, deterioration or loose connections. Replace or
tighten connections as necessary.
3.4.1.6 Check all battery terminals for corrosion and loose/bad connections, clean and
retighten as necessary. Do not smoke or have any source of ignition nearby.
3.4.1.7 Check the battery electrolyte level, and top up with de-ionized water as
necessary. Do not smoke or have any source of ignition nearby.
3.4.1.8 Check the air filter restriction indicator (if fitted) and replace the air filter if
necessary.
3.4.1.10 Remove any unnecessary unsecured items from the generator and its vicinity,
and clean up any dirt or dust that may have accumulated on any part of the generator.
3.4.1.11 Check for fuel, coolant and lubricating oil leaks. Repair as necessary and
clean up any spillage.
3.4.1.12 Make sure that the alternator output circuit breaker is in the off position.
start/stop mode of diesel generator shall be set at “auto” position, and control mode
switch of outlet switches on diesel generators shall be shifted to open position. Only
under in situ start/stop mode, start/stop mode of diesel generator can be set to
"Manual” position. When start/stop mode of diesel generator is set at "run” position,
start/stop tests may be carried out through "Simulated Voltage Loss” switch.
3.4.2.1.1 Check if start/stop mode of diesel generator has been set at "auto” position,
if water heater is operating, stops water heater.
3.4.2.1.2 Check if control power fuse has been installed inside diesel generator
control cabinet, if 24V battery voltage performs normally, and if indicator lamp shows
properly.
3.4.2.1.3 Starting instructions can be issued by DCS or press emergency start button
in control room. After control system received start signal, diesel generator can start
normally within 10 seconds. After voltage and frequency of diesel generator rise up to
rated values, it will automatically close outlet switches of diesel generators and send
operation signal to DCS. If unit fails to start three times, it will send failure start signal
to DCS.
3.4.2.1.4 Start-up time of diesel generator shall be within 10 seconds, the time from
starting to full loading shall be less than 30 seconds, if manual start-up failed, and the
next start-up shall be after an interval of 30 seconds or more.
3.4.2.1.5 Under normal circumstances, diesel generator must be stops only after
operating power of 480V PC bus has been restored. DCS shall send command to stop
the diesel generator, diesel generator then will shut down by sequence.
3.4.2.2.1 Set start/stop mode of diesel generator to "manual” position, check if outlet
switch of diesel generator has been set at open position. When water heater is
operating, stops water heater.
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 45 / 118
3.4.2.2.2 Start the engine. Turn the control switch to the “run” position. The engine will
automatically crank over until either the engine starts or if the engine has not started
after 3 attempts, in which case the control panel will indicate “Fail to Start” and lock
the control system. If this happens, do not proceed further, investigate and rectify the
cause of the failure to start. Check the control panel for signs of faulty operation. Oil
pressure should be normal within about 10 seconds, and coolant temperature should
be normal and stable after about 10-15 minutes.
3.4.2.2.3 Check if output voltage & frequency of diesel generator are normal.
3.4.2.2.4 Check if outlet switch of diesel generator can be closed automatically and
normally.
3.4.2.2.5 Press button "stop” on control panel of diesel generator and check if diesel
generator stops by sequence normally.
3.4.2.2.6 Set start/stop mode of diesel generator to “AUTO“ position and put water
heater into operation.
3.4.2.4.1 Set starting mode on control panel diesel generator to “AUTO” position.
3.4.2.4.2 When any of 480V PC loss power, 480V ATS will send diesel generators a
starting signal. After control system received the signal, diesel generator will start
normally within 10 seconds. After output voltage & frequency of diesel generator rise
up to rated values, shifted manual to security section, 480V PC will restore power
supply.
3.4.3.1 Check if start-up mode of diesel generator is set at “AUTO” position and stop
water heater running.
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 46 / 118
3.4.3.2 Press staring button in DCS to start diesel generator, check if diesel
generators operate normally, and if voltage and frequency rise up to rated values.
3.4.3.5 Half an hour later, press stop button in DCS to stop the diesel generator; check
if diesel generator stops by sequence normally.
3.5.1.1 Disconnect all load switches on bus and pull switch up to test position.
3.5.1.2 Disconnect inlet switch of standby power and pull switch up to test position.
3.5.1.3 Check if incoming breaker and generator breaker on 13.8kV busbar has been
pull up to test position.
3.5.2.1Running state
Trolley switch is located at the "close” position, switch is in closed state, the secondary
connection plug-in is at link position, DC power switch (for switch protection) is closed,
small switch of watt-hour meter, small power switch of transducer, and small power
switch for switch cabinet heating lighting are all closed.
Trolley switch is located at the "Test” position, the secondary connection plug-in is at
link position, DC power switch (for switch protection) is closed, and grounding
disconnecting link is disconnected.
Trolley switch is located at the "Test” position, the secondary connection plug-in is at
link position, DC power switch (for switch protection) is closed, small switch of
watt-hour meter, small power switch of transducer and small power switch for heating
lighting are all closed, and grounding disconnecting link is disconnected.
Switch is located at "close” position, small switch for control circuit is closed. Switch is
in “Closed” state.
Drawer switch is located at "Draw out” position, contactor is in "off” state, switch is in
the "off” state.
3.5.5.1 In main auxiliary, shift between working power supply and backup power for
480V bus after checking “Closed” state in the same period.
3.5.5.2 Bus power shifting between low-voltage auxiliary transformers which back up
each other shall be conducted bus short-time combined-ring mode.
3.5.5.3 Before closing disconnecting link, must ensure switch has been set at “Off”
position. After closing disconnecting link, check if disconnecting link is in proper
position.
3.5.5.4 During supplying power for auxiliary bus, all switches or disconnecting link of
outgoing line loop shall be disconnected. Fit with fuse of primary loop of voltage
transformer, push trolley of voltage transformer into operating position, close small
switch of secondary loop. After auxiliary bus has been supplied power, make sure
three-phase voltage is normal before supplying power to each of power supply circuit.
3.5.5.5 Before power cut of auxiliary bus, shall disconnect each of power supply circuit.
After disconnect incoming switch, check three-phase voltmeter without signal, open
DC/AC small switch of second loop, and then pull voltage transformer trolley to the
test position, remove fuse from primary loop.
3.5.5.8 During power cutting of auxiliary transformer, ATS device of 480V PC I II bus
shall operate and standby transformer shall supply power to PC section. After
auxiliary transformer has restored power supply, then manual operate ATS put the
auxiliary service.
3.6.1.1 Under normal circumstances, this system must operate according to standard
operating mode approved by DCS.
3.6.1.3 Any special operating mode must be made a draft measures, approved by the
Chief Engineer and reported to General Dispatch Officer. Maintenance can be carried
out only after getting instructions from General Dispatch Officer. After maintenance,
maintainer shall give a detailed explanation with a clear conclusion to operators.
Operators shall carry out necessary check and test before formal operation.
3.6.1.4 When need to change operation mode of system, it needs to fill in a switching
operation sheet as per provisions on switching operation.
3.6.1.6 All concerned operators must have a preconception of accident and there shall
be processing methods just in case of any stability damage.
3.6.1.7 Make sure that there is none of thunder, rain, fog or wind in the areas along
lines at that time, keep an eye on weather changes, contact with Dispatch Officer
timely and scheduling and strengthen inspection on factory equipments.
3.6.1.8 Dispatch Officer can decide to disable the circuit reclosing which exceed
transient stability operation limit to avoid as could as possible major operation.
3.6.1.9.1 There shall be correct names of equipments on both front and rear of relay
protection screen. All of protective relay, press plates, test switches, fuses etc. on
screen shall be marked correctly. Any start/stop operation of equipments shall be
subject to approval of Chief Engineer and Dispatch Officer.
3.6.1.9.2 Before the protection of circuit plate, operator must check if signal indicates
properly, and shall adopt method using high-resistance millimeters to measure
terminal voltage with one end contacted with ground to verify that protection devices
tripping or reclosing pulse.
3.6.1.9.3 For operating and standby equipments, their protective and automatic
device shall be put into operation; any equipment without protection must not be put
into operation. Under emergency situations, some protection may be stop operation;
however, two main protections shall not be disabled at the same time.
3.6.1.9.4 When primary equipment powers off and protection device & secondary
circuit is not operating, protection device may not be disabled, but outlet press plate of
other operating switches shall be released.
3.6.1.9.5 Protection devices shall be put into operation by the following order: DC
power goes first, outlet press latter; Disabling protection shall be in the other way
round.
3.6.1.9.7 Under normal circumstances, relay protection and automatic device shall be
put into operation or disabled with specified press plate and switch, and shall not be
carried out by the method using disconnected secondary line joint plus temporary line.
3.6.1.9.8 After maintenance of relay protection and automatic device, there must be
clear written explanations and conclusions. If there is any change on setting value, the
operator shall explicitly clarify this to ensure that records are in line with actual setting
value of equipments. No equipment without conclusion can be allowed to put into
operation.
3.6.1.9.9 During power cutting for maintenance, the protective press plate which may
impact on the equipment shall be disconnected before hand. These press plates shall
be disable before equipment is put in to operation or standby,.
3.6.2.1 Check if all work orders have been completed, maintainer shall advise
required conditions for power supplying.
3.6.2.2 Make sure that there is no grounding, short-circuited line between gaps of
circuit being supplied power, make sure to remove all of security measures and meet
conditions of power supplying.
3.6.2.3 Make sure that all parts of switch and disconnecting link of circuit being
supplied power are in good conditions and meet conditions of power supplying.
3.6.2.4 According to Dispatch Officer’s instruction, put relay protection and automatic
devices of circuit being supplied power into operation.
3.6.2.5 Put control switch, signal fuse and circuit signal fuse of circuit being supplied
power into operation.
3.6.2.7 According to Dispatch Officer’s instruction, after regular check, connect circuit
bus side switch.
3.6.2.8 Inspect meters of circuit being supplied power, make sure all indications of
current, voltage, active/reactive power are normal.
3.6.2.9 Check if meter of switch on bus side of circuit being supplied power indicates
normally.
3.6.2.10 According to Dispatch Officer’s instruction, after the same period, makes sure
to connect intermediate contact switch.
3.6.2.11 Check if meter of intermediate contact switch of circuit being supplied power
indicates normally.
3.6.2.12 Check if the two switched of circuit being supplied power are well closed.
3.6.3.4 Check if all indications of current, voltage, active/reactive power return to zero.
3.6.3.5 According to operating principles of power cutting, open both isolator of circuit
breaker.
3.6.3.8 According to Dispatch Officer’s instruction and work order, detect electricity
and arrange safety measures.
4 Start/stop of Generator
4.1.2 Check if outlet PT primary fuse of generator is well pressed, push outlet PT
trolley of generator to operation position.
4.1.4 Close isolator of grounding transformer of generator neutral point and check if
tap is located correctly.
4.1.5 Check Voltage transformer to start excitation, air blower of AVR cabinet and
AC/DC control power supply of excitation cubicle.
4.1.7 Check state of excitation regulator on CCR screen is consistent with that on in
situ control panel.
4.1.9 Check if protection of generator has been put into correct operation.
4.2.1.1 Generator sounds normal with a vibration of not more than 0.025mm.
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 54 / 118
4.2.1.3 Confirm that operating mechanism power-storing and SF6 pressure of outlet
circuit breaker of generator exports shall be qualified.
4.2.1.4 All protection of generator has been put into proper operation.
4.2.1.5 Under normal conditions, switch fuse in each of cabinet of excitation system
need not to be put into operation.
4.2.2 Generator adopts automatic running excitation, automatic regulator step-up and
automatic semi-synchronization paralleling with system
4.2.2.2 Click icon of generator outlet switch in DCS, pop-up switch selecting operation
panel.
4.2.2.3 On switch selecting operation panel, click button "Startup & Synchronization",
pop-up operation panel of generator Synchronization.
4.2.2.9 Check if outlet switch of generator is well closed, carrying with 5% rated load,
click button "Power Input” on DCS device, and put power circuit into operation.
4.2.2.12 Put "Unit Trip Power” and "Power Trip Unit” protection into operations.
4.3.1 After diesel engine turning, observe whether there is unusual noise at generator
bearing.
4.3.2 When unit speed increasing, it needs to observe vibration of bearing and pay
attention to temperature of bearing, especially to vibration situation when generator
passing through critical speed and rotating speed rising up to rated speed.
4.3.4 Make sure that cooling system of generator is running properly before the
generator step-up. After generator step-up, shall check if no-load parameters of
generator show normally, stator current shall be close to zero value with three-phase
balanced.
4.3.5.1 During synchronization, shift foreman is in charge of monitoring and main shift
worker carry out operation;
4.3.6 If generator needs to add load, it needs to adjust reactive power of generator.
Pay attention to various operating parameters and temperature changes of various
parts of generator.
4.3.8 After generators with full load, it needs to carry out a detailed inspection on
primary and secondary system of generator.
4.4.1 Generator use automatic excitation methods to realize trip and outage from
system.
4.4.1.2 Click icon of generator outlet switch in DCS, pop-up switch selecting operation
panel.
4.4.1.3 On switch selecting operation panel, click button "Outage & Trip", pop-up
operation panel of generator trip.
4.4.1.4 Click buttons “Stop diesel later”, "AUTO” on operation panel of generator trip,
select trip method.
4.5.4 Disconnect AC/DC power control small switch of excitation regulator, fan power
switch of power cabinet and heating & lighting small switch.
During normal operation, operator shall inspect regularly main transformer, auxiliary
transformer, standby transformer, other dry-type transformer. In the event of overload,
defective equipment, after repairing or overhaul and in the severe weather, it is
necessary to increase inspection times.
a) Color of oil inside header tank and oil-filled bushing shall look transparent; oil level
shall be kept at a normal level;
g) Gas relay shall be full of oil, with no gas released, outgoing line intact, valve
unlocked;
j) There shall be no overheating on each of parts inside control box of cooling device
and all handles shall be so located as to meet operating requirements;
k) Oil pumps and fan shall run properly; oil flow display on main transformer cooler
shall indicate normal;
5.2.2 It is necessary to carry out special check of transformer under the following
circumstances:
b) Avoid lead from swing in windy weather and it is not allowed to hang something on
lead;
e) Oil level and oil temperature in transformer shall be normal at a sudden cold or
sudden heat condition and expansion joints shall not turn color overheat;
f) When transformer overloading, make sure that cooling system perform normally, put
standby cooler into operation;
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 59 / 118
g) Within 72h new equipment or repaired/rebuilt transformer being put into operation;
i) Booster station and switch field shall be carried out a light-out inspection weekly;
5.2.3 Heavy gas shall be replaced from "Tripping” to "Signal” position, when gas
protection of running transformer is carrying out the following work:
c) When open vent and outlet/inlet oil valves at any place, with the exception of
collecting oil sample and releasing gas via upper gas valve of gas relay;
f) When needs to open outlet gas/oil valve due to unusual increase of oil surface in oil
level indicator or respiratory system anomalies.
5.2.4 In the same ambient temperature and the same load conditions, there shall be
no significant difference between current oil temperature of transformer and previous
recorded values.
5.2.5 Under normal circumstances, oil level of transformer varies with temperature
change. There shall be no significant difference of transformer oil level, So long as oil
temperature remains the same.
a) Make sure coil temperature is normal and temperature control device has its
surface clean and indicates correctly;
d) Transformer body shall be clean and free from fouling, without dew and other
endangering miscellaneous items around.
5.2.8 After overhaul and during operation, transformer must be conducted oil
chromatographic analysis.
a) In the case of strong winds, make sure that upper lead on transformer shall not
swing violently and get loose and there are no sundries on cover and surrounding;
d) When weather become cold or hot dramatically, inspect changes on oil temperature
and oil level and operation of cooling device, check if there freezing or overheating.
5.3.1 During normal operation, make sure that voltage of 125V DC bus shall be within
115~135V.
5.3.2 When signal "DC bus insulation is too low” appears due to insulation reduction, it
is required to find out the related reasons.
5.3.3 When voltage of DC bus appears too high or too low, it needs to find out the
reasons and inform maintainer to address. If necessary, switch the load from failed
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 61 / 118
5.3.4 Operator on duty shall carry out a complete check on DC system per shift.
1) Check if voltage DC bus is within the normal range, accumulator jar is intact,
voltage of battery cell is normal, press line remains in order, and room temperature
meets the requirements (15℃ ~ 25℃);
2) Check if wiring of charger and bus has a good contact, without loosening or
overheating. Make sure that fuse is intact, setting values meets requirements, and
charger output current normally;
3) The actual location of each of switch on DC panel shall be in line with the operating
mode;
5.4.1 After electric motor has been repaired, maintainer shall clear procedures of work
order and advise status and insulation resistance value of equipment to operators.
a) Make sure that work orders have been closed and in situ workers have been
evacuated, clean up around motor and there is no sundries interfering operation;
b) Check if power cutting protection and interlocking apparatus have been put
correctly into operation;
c) Check if devices provided with electric motor meet startup requirements and
without any inversion;
d) Bearing has a normal oil level, oil looks transparent without impurities, no oil
leakage, and no defect on oil cap. If needs to take compulsive recycling oil lubrication,
oil system shall be put into operation first;
e) Check if commutator brush on DC motor has a good contact, smooth surface and
proper spring pressure;
f) Foot-screws, grounding wire and coupling, protective cover and junction box on
electric motor shall be fixed firmly;
g) Manual jigger shall be free from sticking, and stator/rotor shall be without friction
noise;
h) Make sure that electrical equipments and thermal instruments built in electric motor
shall be kept in a good condition and have been put into proper operation.
a) Allowed startup times of squirrel-cage motor in the cold and hot state shall be
provided by manufacturer. If no such as provisions by manufacturer, it may depend on
mechanical properties being driven and start-up conditions. Under normal
circumstances, electric motor can be allowed to started up twice in the cold state with
a interval of not less than five minutes, once in the hot state, and can be activated
once more only if when dealing with accident and start-up time shall be no more than
2~3 seconds. Electric motor provide by Shanghai Electric Motor Factory can be
restarted 4 hours after two consecutive starts in the cold state, and can be restarted 4
hours after one consecutive starts in the hot state.
- For motor < 200 KW, it shall not be less than 0.5 hours;
- For motor = 200 ~ 500 KW, it shall not be less than 1 hour;
b) When starting motor, shall motoring closely change of starting current, if current
does not return startup, or ammeter does not move after closing switch, and motor
fails to run, shall exit startup immediately and restart only after identifying reasons.
a) Check if ammeter indicates stably and not more than rating, otherwise any
increased value shall be reported to Chief Foreman and take measures as per Chief
Foreman’s instructions; once current reaches full rating suddenly, shall stop
equipment immediately;
b) Motor sounds normal, without vibration and displacement not exceed the specified
value, indicator lamp looks normal;
c) Temperature of each part of motor does not exceed the specified value, and there is
no smoke, burning smell, overheating and so on;
d) Motor shell and grounding wire of starter shell are in good conditions, foot-screws
do not get loose. Oil level of bearing is normal without oil spout or oil spill. Oil looks
transparent and without impurity, oil ring rotates smoothly, end/top covers seal well;
e) Motor is well ventilated without any blocking, valves of cooling water and air chutes
are located in place, it’s clean and without sundries around motor.
a) During running, electric motor, whose bearing is lubricated with oil ring, shall be
applied oil according to oil level readings, rolling bearings shall also be refilled with oil
in general, when necessary, some lubricants with the same oil quality shall be applied
with oil ejector (oil gun).
5.5.1 Operators shall check UPS device per shift to make sure that there is no
unexpected noise, foreign odor and overheating on each of parts in cabinet. All of
indicator lamps and measuring meters shall indicates correctly, all of cooling fan shall
run normally, and room temperature shall remain within the allowable range.
5.5.2 Check if bypass output voltage, inverter output voltage, and voltage/ current/
frequency of load appear normal.
5.5.3 Make sure that each of switch inside UPS cabinet is located in place.
5.5.4 No abnormal alarm signal is shown on device, indictor lamps on panel shall
indicate corresponding to actual operating mode.
5.6.1 Check if indicator lamp and start/stop mode on control cabinet of diesel engine
operate properly.
5.6.2 Check if oil levels of lubricating oil of diesel, fuel and coolant read correct.
5.6.3 Check if auxiliary AC power to supply power normally, storage battery can be
automatically charged properly.
5.6.4 Make sure that unit body shall be clean, oil/water heater automatic start/stop
normally, and control mode of power switch of security segment and each of security
MCC segment shall be correct.
5.6.5 During diesel engine running, make sure that there is no leakage and leather
belt of charger shall be without any damage or abnormal smell.
5.6.6 All meters shall indicates correctly, pressure and temperature of lubricating oil
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 65 / 118
5.6.7 During running, check if frequency and voltage of unit read proper, three-phase
current is balanced and storage battery can be well charged automatically.
5.7.1 During transformer operating, so long as the voltage ranges within rating value
of ±5%, its rated capacity shall remain unchanged. The maximum operating voltage
shall not exceed 105% of rating of each of tap.
5.7.4 Temperature rise of and main transformer winding shall not exceed 65K,
temperature rise of the upper oil shall be not more than 55K, temperature rise of oil
tank, iron core and metal component shall not exceed 75K. Maximum designed
ambient temperature shall be 40℃. High-voltage auxiliary transformer, standby
transformer winding shall not exceed 85K.
5.7.5 Maximum temperature of main transformer shall not exceed 85℃; the maximum
temperature of winding shall not exceed 95℃. It will give an alarm when temperature
of main transformer winding exceeds 95℃ or temperature of upper oil exceeds 85℃,
and it will give an “ultra-high” alarm when temperature of winding exceeds 110℃ or
temperature of upper oil exceeds 100℃.
5.7.7 When all coolers stop operation, transformer is allowed to operate successively
with rated load for 20 minutes. When temperature of oil surface does not exceed 75℃,
transformer is allowed to operate successively for 1 hour.
5.7.8.1 For newly-installed, repaired and long-time disabled (more than one day)
transformer, before operation, shall measure insulation resistance and the measured
date shall be recorded.
5.7.8.3 Transformer shall be measured along with cables and enclosed bus by a
2500V megohm meter, insulation resistance shall be ≥1MΩ/kV. Transformer with a
voltage rating of below 0.48kV shall be measured with a 500V megohm meter,
insulation resistance shall be not less than 0.5MΩ.
5.7.8.4 Insulation resistance of main transformer coil shall be measured with a 2500V
megohm meter, for each of coil and grounding, it shall meet the following
requirements:
a) Insulation resistance R60 shall be not less than 85% of ex-factory value or R60>
2500MΩ.
b) Absorption ratio R60/R15 shall be not less than 85% of ex-factory value or
R60/15≥1.3.
c) Dielectric loss angle tgδ shall be not more than 120% of ex-factory value (same
as temperature). At 20℃, when the value is less than 0.5%, it needs not to be
compared with the ex-factory value.
5.7.9.1 Heavy gas protection device shall trip normally. When operating on circuit of
heavy gas protection device, it needs to change heavy gas protection to signal, check
if protection device can trip after non-operation.
5.7.9.3 When charging transformer which is put into operation newly or after repairing,
it needs to put heavy gas protection into tripping. After normal charging, change it to
signal, and then put it into tripping after 48-hour releasing gas by operating gas relay.
5.7.9.4 During heavy gas protection stopping operation, it is prohibited to stop any
other main protection of transformer.
5.8.1 Voltage of high-voltage auxiliary power system shall be 13.8kV and 4.16kV.
transformer with a capacity of the 2000VA per unit, high-voltage working transformer
shall be equipped with two sections of 13.8kV bus.
5.8.3 Set up a standby transformer with a capacity of the 2000VA as a standby power
for the unit, standby transformer shall be a kind of on-load voltage regulation
transformer. Low voltage side neutral point standby transformer shall be directly
grounded.
5.9.2 Set up a 480V power distribution center for low-voltage load of 480V auxiliary
unit of this unit sets.
5.9.3 Each segment of 480V power distribution center in auxiliary is supplied power by
a low-voltage auxiliary transformer. Set up contact switch link between the centers of
two segment 480V power distribution centers (except for electric dust removing
segment). Low-voltage auxiliary transformer adopts back-up for each other;
transformer capacity can be selected according to the load capacity of two segment
power distribution center. Under normal operation, contact switch of two power
distribution center shall be disconnected. If either of two transformers needs to be
repaired, contact switch shall be put into operation manually.
5.9.4 Power distribution center for electric dust removing shall be equipped with a
special low-voltage transformer as a backup. Electric dust removing segment of each
of unit shall be equipped with backup power auto-input device, In the case of failure of
work transformer, Power distribution center for electric dust removing can be put into
operation automatically. When work transformer needs to be repaired, power
distribution center for electric dust removing can be switched by closing back-up
branch switch manually.
5.9.5 Low-voltage auxiliary power system in main auxiliary adopts direct neutral point
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 69 / 118
grounding.
5.10.1 Set up a segment security 480V MCC on 13.8kV I busbar room. Units set up a
diesel generator unit as power for security 480V MCC busbar. Under normal operation,
security 480V MCC is no power. Diesel generator shall be in a good standby status,
outlet switch of diesel generator shall be set at “OFF” position. Start/stop mode of
diesel generator shall be set at "AUTO” position.
5.10.2 Operators shall check thoroughly security power system per shift to ensure that
security system shall be in a good standby status.
5.11.1 Enclosure of each of motor shall carry with nameplate of manufacturer. Once
nameplate is missing, it needs to make up a new nameplate based on the original
data or test results of manufacturer.
5.11.2 Motor and its carrying-on equipment shall be marked with clear arrow to
indicate the direction of rotation, there shall be clear code/name to show its affiliation
shipment. Startup device shall be marked with "Start", "Run” and "Stop” signs.
5.11.3 All of switches, contactors, operating handle and the accident button on motor
shall be clearly marked to indicate them belongs to which one motor. Accident button
shall be equipped with a shield.
5.11.4 Coupling of electric motor and mechanical connection shall be equipped with a
solid shield, motor shell and enclosure of startup device shall be supplied with a good
grounding device.
5.11.5 Standby motor shall be regularly inspected and tested to ensure that at any
5.11.6 Fuse-link of all types of fuses used for protection of electric motor shall be
checked. Each of fuse holders shall be marked with rated current of fuse-link. Model
and capacity of the fuse shall be marked on motor in situ.
a) In general, motors can operate at a range of 95~110% of rating value, with its rated
output unchanged.
b) When the voltage is lower than its rating, current can be increased accordingly, but
shall not exceed its rated current value by 10%, and make sure that winding, shell and
outlet temperature shall not exceed the specified values.
c) When motor is running at rated output, phase voltage imbalance must not exceed 5%
of rating, current difference between three phases must not exceed 10%, and in
addition, current of any phase shall not exceed the rated current.
b) For motor disabled more than 24 hours, it needs to measure insulation resistance
before startup. For motor disabled more than 8 hours at bad environment, it needs to
measure insulation resistance before startup.
- Insulation resistance value of 480V (or below) stator winding of motor not less than
0.5MΩ.
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 71 / 118
Under normal circumstances, the temperature for long-time operation of the motor
shall be provided by factories. If there is no factory’s specification, the temperature for
each of parts shall be referred to following table (the allowed temperature rises listed
below is calculated based on an ambient temperature of 40℃):
Parts Allowed maximum temperature (℃) Allow maximum temperature rise (℃)
Level A 105 60
Level E 120 75
The surface of iron core and structural parts shall not exceed the allowed temperature
rise of contact insulating material (Thermometer Method).
a) Vibration of motor shall not exceed the values listed as following table:
b) Axis-direction moving value of motor shall not exceed the following values:
a) Normal operation mode of 125V DC system shall be: after parallel operation,
charger and battery supply power to segment DC bus via segment bus-coupling
switch.
b) On 125V DC system, chargers generally carry with the load on segment and carry
out floating charge on accumulator battery.
a) Under normal circumstances, charger shall not to supply power to DC load alone.
b) When unit is running normally, DC system shall not take any action to cause any
instantaneous power cutting on DC bus.
d) Any floating charge batteries, if for some reason, have been discharged or disabled
for long time, shall be carried out a balanced charging.
a) Voltage of each of DC bus and floating charge current of each of charger shall be
normal (0.01C, C means battery capacity).
c) Check if monitoring module shows the parameters and status indicators are normal,
and if there is any alarm signal.
d) Check if charging module of charger cabinet operate normally, voltage and current
shown on LCD are normal.
a) Battery shall be clean and dry, without cracking or leakage; during the service life of
battery, do not open its valve.
b) Make sure that floating charge voltage of battery shall be within the normal range.
c) When battery is carried out balanced charging, voltage and current of balanced
charging shall be normal (0.08C, C means battery capacity).
e) Inspection regularly data logger of battery to see if the measured value is consistent
with the actual value.
b) Do not wear watches, rings and other metal objects during working around the
battery.
c) Do not use organic solvents but soap lye or clear water to clean up external
appearance.
d) In the case of battery on fire, do not use carbon dioxide fire extinguishing agent and
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 75 / 118
--- After completion of discharge and before being put into use.
--- If AC power failure lasting more than 10 minutes or after 60 days of continuous
floating charging, the system will automatically start the balanced charging.
5.14.1 Each of unit shall be equipped with UPS, AC bus adopts single-bus
configuration. In order to provide double power supply to unit control system, each of
unit shall be equipped with not only a UPS power distribution cabinet but also a
security power distribution cabinet. Security power distribution cabinet AC bus power
shall be supplied by isolation transformer and automatic coupling voltage regulator of
unit security via UPS bypass.
5.14.2 UPS system of units consists of a UPS basic cabinet, a bypass cabinet and a
security cabinet. UPS AC input power has two ways, of which one way is for working,
and the other is for backup, both of two way connected to electric power plant auxiliary
power system. Bypass AC power has one way.
5.14.3 UPS disabling operation shall be conducted only after thermal control switching
of concerned power.
5.14.4 In the case of inverter fault or too much load impact, or UPS load short-circuit
beyond of capacity of inverter; static switch will switch automatically to bypass power.
After fault removed, static switch will return to automatically to power supply by
inverter. When power meets switching conditions, manual switching time for static
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 76 / 118
switch shall be 0ms, when load is switched from inverter to bypass, there will no
phase hits; when switching from bypass back to inverter, this switch is undisturbed
switching.
5.15.1 Under normal circumstances, the rated power for long-time continuous
operation of generator shall be 8350kW.
a) When the voltage of generator stator varying within rating of ±5% and power factor
is the rated value, its rated capacity shall keep unchanged. That is, when the voltage
of generator stator is higher or lower than 5% of rated value, the allowed current value
of stator can be allowed to be lower or higher than 5% of rated value.
b) Generator can operate with variable power factors, when power factor is reducing,
the current of rotor shall not be greater than the rated current, and the apparent output
shall be reduced. When the power factor is increasing, the apparent power of
generator cannot be greater than its rating.
In the state of system failure, it is allowed for generator to operate with overload.
However, at this time, hydrogen parameters, cold water parameters within the stator
winding and stator voltage of generator shall be same as their ratings.
5.15.3 Under the accident conditions, it is allowed for generator to fulfill short-time
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 77 / 118
asynchronous operation. During excitation system failure and power grid conditions
permitted, at a stator current of 1.0~1.1 times IN, the allowed running time shall be
15min, at this time the allowed load shall be within 40% of rating, in addition, when
occurs loss of excitation, load shall be reduced to 60% of rating within initial 60s, and
then down to 40% of rating within subsequent 90s.
5.15.4 When the generator is ongoing load unbalance operation, the negative
sequence current cannot exceed 8% of rated current, and the current of each phase
must not exceed rated current, otherwise the generator output shall be reduced to the
allowed range.
5.15.5 In a very short time, generator can withstand unbalanced load of accident
conditions, (I2/IN)2*t≤10S. The allowed value of accidental negative sequence current
time and the related time shall be in accordance with the following table.
5.15.8 Generator can structurally operate stably under the condition of leading power
factor being 0.85 and at the rated power.
5.15.9 Generator can output rated power continuously at rated power factor, rated
voltage deviation of ±5%, and rated frequency deviation of +2% to -3%. The allowed
operation time for generator to output the rated power at rated power factor, rated
voltage deviation of ±5%, and rated frequency deviation of +3% to -6%.
5.16.1.1 Allowed temperature limit of bus, disconnecting link and joints of all parts is
70℃.
5.16.1.2 Maximum temperature rise of conductor of closed bus is 50℃ (at ambient
temperature of 40℃), the maximum allowed temperature is 90℃. Maximum
temperature rise of enclosure is 30℃, the maximum allowed temperature is 70℃.
Maximum allowed temperature of silver plated area is 105℃.
a) Check if work orders have been taken back, and remove temporary security
measures.
b) Measure bus insulation. 480V bus shall be measured with 500V megohm meter,
and its value shall not be less than 100MΩ. 13.8kV bus shall be measured with 2500V
megohm meter, and its value shall be not less than 200MΩ.
c) Support porcelain insulator, wall bushing shall be clean, in good condition, and free
of crack nor spark tracking.
a) Support porcelain insulator and rod porcelain insulator, keep insulator clean and
intact.
b) During trail pulling disconnecting link, make sure three phases act in a unified way
and contacts shall have good contact.
c) Grounding disconnecting link have a good mechanical interlocking with the main
disconnecting link.
f) Fixed and moving contacts shall have good contact, and the contact depth shall be
appropriate.
c) There shall not be overheating, flushing burning out on all of joints and contacts.
e) Make sure that equalizer ring shall be solid, reliable and smooth.
f) Operating mechanism boxes shall be properly closed and free from water leakage.
a) Close pull-in voltage transformer when there is no grounding fault in the system.
e) When switch is closed, the bypass disconnecting link parallel connected with switch
can close the bypass current.
f) Close no-load transformer with excitation current of 2A and no-load circuit with
capacitive current of less than 5A.
5.16.1.7 Before disconnecting link operating, ensure related switch has been set at
“OFF” position first, and then conduct the operation. During supplying power, close
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 80 / 118
disconnecting link on power side, and then close disconnecting link on load side. The
sequence of power cutting is the other way round. During operation, if there is any
damage, fracture, or discharging, contact, overheating, flushing or burning-out, shall
report immediately to Dispatch Officer and ask to switch operation mode or reduce
load.
5.16.1.8 In the case of electrical operation malfunction, check the following items:
b) If 110V DC control power supply is normal, and if DC control power switch QF1 has
been put into operation.
c) Check if remote/in situ small switch of control box is in line with operating mode.
e) If auxiliary switch, limit contact and closed-loop contact has been well closed.
5.16.1.9 After closing disconnecting link, check contact situation immediately. After
completion of electric operation, shall open small switches of operational power
supply and motor power supply.
allowed operating voltage of voltage transformer, current on primary side shall not
exceed the rated current of current transformer.
5.16.2.3 138kV voltage transformer shall directly access to the 138kV system, voltage
transformer shall be put into operation together with themselves own equipments.
5.16.2.4 Secondary voltage of 138kV voltage transformer shall pass through a small
switch to protection device and measuring circuit, synchronous voltage shall be output
by small switch. During normal power failure, secondary small switches shall be
disconnected, when power supplying, they shall be closed.
a) Porcelain insulator shall be clean and intact, free of cracks, breakage and
discharging and spark tracking;
e) There shall be not overheating, flushing, red, strands breakage or wire fracture on
joints and lead;
f) Part of the secondary connection shall be clean, without sparking tracking, and well
fused.
5.16.2.6 After thunder, strong winds and rainstorm, it’s necessary to carry out special
inspections on the transformer.
5.17.1 After repairing, arrester shall be carried out power frequency discharge test
and measured insulation resistance by high-voltage testing stuff. Whether it can be
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 82 / 118
put into operation shall be clarified by the responsible person in written. Except for the
duration of check and test, the arrester shall be put into operation all the year around.
5.17.2 After each of lightning strike or system failure, the arrester shall be thoroughly
checked, the detailed date shown on discharge recorder shall be recorded into
arrester’s operation log.
a) Porcelain insulator shall be clean and free of cracks, breakage and discharging;
5.18.1 Operating voltage of power cables shall not be higher than 115% of rated
voltage.
5.18.2 Before being put into operation, it needs to measure insulation resistance of
power cable. Insulation test on cable provides as follows: 480V (or below) cables shall
be measured with 500V megohm meter, its value shall not be less than 3MΩ and
value ratio shall not be more than 2.5 times. 1000V below cables shall be measured
with 1000V megohm meter, and its value shall not be less than 10MΩ. 1000V above
cables shall be measured with 2500V megohm meter , the insulation resistance of
value 6~10kV cables shall not be less than 400MΩ, and unbalance factor of insulation
resistance of each of phase shall be not more than 2 times. Measured insulation
resistance value shall be subject to the reading data of 1 minute later. After
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 83 / 118
5.18.3 Allow the maximum operating temperature for long-time running cable (℃)
refers to the following table:
PVC insulation 65 65 —
Polyethylene insulation — 70 70
XLPE 90 90 90
5.18.4 Cable in general may not be overloaded. In the case of accident, it is allowed
for cable to overload for short time, but shall be subject to the following provisions:
a) Low-voltage cables can bear a 10% of overload, 6~10kV can bear a 15% of
overload, but both of two are not allowed to overload for more than two hours;
b) For intermittent overload, re-overloading shall be conducted only after 10-12 hours
later than previous overload.
c) When cable overloading, its temperature shall not exceed the allowed values,
otherwise, it needs to reduce load immediately.
Inspection on cable:
a) Asphalt on steel armored cable shall not be detached, and scarfskin of unarmored
cable shall not be damaged;
b) Bracket shall be kept in good condition; cable shall be placed in order, no extrusion
nor bump;
6.1.2 There must be correct name of equipment in front of and behind protection
screen of relay, and all of relay protections, press plates, test switches, fuses, etc. on
the screen shall be marked correctly, and shall be checked before the operation.
6.1.4 Test for relay protections, automatic device and there secondary circuit shall be
carried out in line with main at power outage, the following conditions by the
dispatcher or the value of long (according to jurisdiction). Under the following
conditions, after get approval of Dispatch Officer or Chief Foreman (depends on
responsibility), inspection and may not power on the relay protection equipment and
automatic device of live equipments.
3) Relay protection equipments and automatic devices which can stop operation as
agreed by Dispatch Officer or Chief Foreman;
6.2.2 After maintenance of relay protection and automatic device, there must clear
explanations and conclusions in written. If need to change the setting value, modifying
person shall advise details to ensure that record shall be in line with of actual setting
value of equipment. Any equipment in question shall not be allowed to put into
operation.
6.2.3 Measurement and test on operating secondary current circuit shall be carried
out with specified current terminal, and make sure that CT secondary open circuit
measures in place, after the end of the work, restore original state.
6.2.4 During outage and maintenance of equipment, the impact on the operation of
equipment should be pre-outage protection, equipment operation and the protection
of the reserve should be put into operation before. During power cutting for
maintenance, the protection which may impact on the equipment shall be
disconnected beforehand. These protections shall be disabled before equipment is
put in to operation or standby
6.2.5 Start/stop of normal operation of relay protection and automatic devices shall be
conducted by operators. When start/stop of protection needs to change secondary
circuit or the setting of microprocessor-based protection, it shall be conducted by
protection persons.
6.2.6 It is prohibited to do any vibration work on the operating protection panel and
automatic device panel. Under special circumstances, it must make proper safety
measures or disable related protection. Do not use any telecommunications
equipments in electronic equipment room.
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 86 / 118
6.2.7 Relay protection and automatic devices shall be check once per shift according
to the following items:
1) After shift changeover, operators shall make sure that there is unpleasant smell,
overheating, unexpected noise, no vibration, no abnormal signal on relay protection
and automatic device.
2) Make sure that enclosure of relay and door of microprocessor-based protection etc.
are intact and without crack.
3) Check if all outdoor terminal boxes are well sealed, if PT secondary switch has
been set at “Putting into operation” position, and if CT has not open circuit.
4) All of switches, disconnecting links, fuse, plugs and press plates of test components
etc. on device shall be in proper place.
6) Indicator lamp status and the start/stop of protection device shall be in line with the
current actual operation mode.
7) Relay shall be free of any action signal, missing nameplate or other anomalies.
9) Exception handling
10) In the case of system or equipment failure, workers on duty shall find out
immediately protections, switches, signals and light-word plates of action, and report
to Chief Foreman, after recording, restore the signal, and then fill the situation of
action into "Relay Protection Action Log".
11) During operation, if electrical equipment failure occurs, workers on duty shall find
out action status of protection and automatic device, and report timely to Chief
Forman and Dispatch Stuff. At the same time details shall be recorded and reviewed
by another person, then restore the signal.
12) If tripping of protection action and switch occurs, it is necessary to instruct the
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 87 / 118
work team holding the work orders to stop working and find out reasons for timely
solving. If found any wrong protection or abnormal signal, shall inform maintenance
team to inspect, after find out the reasons and resolutions, then can conduct the
operation.
13) If found any emergency such as fire, smoking or huge noise etc on device,
workers on duty shall do necessary emergency processing first, and then report to
Chief Foreman and Dispatch Stuff.
Protection shall be configured as 1 main plus 1 backup, the specific configuration shall
be as follows:
Full cut-off: disconnect outlet circuit breaker tripping coil I, disconnect de-excitation
switch, stop diesel engine, start outlet circuit breaker failure protection.
- Overload Protection
- Cooling Initiation
Full cut-off: disconnect 138kV circuit breaker tripping coil, start 138kV circuit breaker
failure protection, disconnect 13.8kV circuit breaker, disconnect generator outlet
circuit breaker, disconnect 13.8kV auxiliary power supply etc..
Trip circuit breakers on all side: trip 138kV circuit breaker tripping coil, trip main
transformer low side circuit breaker.
Trip off circuit breakers on all side: trip off 13.8kV middle circuit breaker tripping coil,
block 480V ATS.
Trip off circuit breakers on all side: trip off 4.16kV middle circuit breaker tripping coil
7.1.1.1 Unit tripping, machine tripping, generators step-out; alarm ring, all related
light-word-plate on.
7.1.1.2 All segment auxiliary bus voltage drops to zero, with green lamp of power
switch on.
7.1.1.3 All running AC auxiliary units stops, backup AC auxiliary unit not linked.
7.1.2 Reasons
Transformer trips off, 13.8kV each segment working power lost, backup power
quick-switching is not successful, or standby transformer fault trip, security power
supply fail to put into operation automatically.
7.1.3 Actions
7.1.3.1 Notify external operators the corresponding resolution against lose of auxiliary
power. Restore each of tripping devices, release linkage of backup equipments.
7.1.3.2 Come to diesel engine room immediately carry out the following inspection on
security power:
7.1.3.3 Check if diesel generator start automatically, otherwise, put security power into
operation and restore security power.
7.1.3.4 After security bus restore the power, and resume gradually all segments
security MCC power and AC emergency lighting.
7.1.3.6 Start lubricating oil pump the host exchange oil pump.
7.1.3.7 Put lubricating oil system of the auxiliary unit into operation.
7.1.3.8 Check if UPS power can be switched normally. Open trip floating machine of
125V DC system.
7.1.3.9 Open all of 13.8kV closed switches. Find out the reason why 480kV backup
power failed to start automatically, after trouble shooting; restore the operation of each
segment of 480V power and low-voltage auxiliary transformer.
7.1.4 During motor startup, if occurs the following abnormal situations, must stop any
operation immediately:
7.1.4.2 After closing switch, motor does not turn but keep buzzing.
7.2.1 If one of the following situations occurs, shall stop immediately the operation of
motor:
7.2.1.2 Motor and its subsidiary electrical equipments is smoking and on fire;
7.2.1.6 Temperature of motor bearing is increasing sharply till exceed allowed values;
7.2.1.7 Flooding or fire disaster etc. endangering the safe operation of motor, fire.
7.2.2 During the following circumstances, for important auxiliary motor, you can start
backup equipments first, and then stop operation of auxiliary motor:
7.2.2.1 There are some abnormal noises on motor burning smells on insulation;
7.2.2.3 Current of stator exceeds value required for normal operation (with same
load);
7.2.3 If the motor tripped off affects the output or safe operation of unit and there is no
backup or cannot enable the backup motor rapidly, then it is allowed to reclose the
motor tripped off, except for the following situations:
7.2.3.5 When voltage of important motor lost or decreased, do not cut out auxiliary
motor within 1 minute.
7.2.4.1 Reasons
d) Lower voltage.
7.2.4.2 Actions
a) Start backup.
c) If trip off when starting, it shall not be activated again until identify the reasons.
f) If there is any short circuit, grounding, wire broken on motor coil and cable;
g) If the driven mechanism is stuck, or if fuse is blew out, interlock circuit is in good
condition;
7.2.5.1Reasons
a) Due to askew bearing center or bushing friction which makes rotor collides with
each other.
c) Stator coil insulation damp, filthy, aging, the occurrence of inter-phase short-circuit
or earth fault.
7.2.5.2 Actions
b) Adopts dry powder fire extinguishers, 1211 fire extinguishers, carbon dioxide fire
extinguisher or mist water spraying. It is strictly prohibited to use huge stream of water
flowing, sand or foam for fire-fighting.
7.2.6.1 Reasons
a) Center of motor is not aligned with that of and its attendant equipments, main shaft
is bending and there is mechanical damage.
7.2.6.2 Action
b) If there is no backup motor, it needs to reduce load of motor to see whether or not
this can ease or eliminate vibration, if not, it is necessary to advise maintenance
department to deal with.
7.2.7 For unusual temperature rise on motor, the following examination shall be
conducted:
7.2.7.1 Check if voltage is below the specified value and if current exceeds the
specified value;
7.2.7.2 Check if cooling air exceeds 35℃, if cooling system is blocked, and if fan is
operating normally;
7.2.7.4 Whether or not the driven mechanism is stuck hence causing overload.
7.3.1 Evidence
7.3.1.3 Switch on high/low-voltage side of auxiliary transformer trips off, green lamp
on;
7.3.2 Action
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 96 / 118
7.3.2.5 Take security measures onto auxiliary transformer and submit to maintenance
for further treatment.
7.4.1 Evidence
a) Alarm rings, control room send 13.8kV "Voltage Circuit Disconnected” signal, "PT
Fault” lamp on 13.8kV PT cabinet on, bus voltage indicates normally.
7.4.2 Actions
7.5.1 Evidence
7.5.1.3 Switch on high/low-voltage side of standby transformer trips off, green lamp
on;
7.5.2 Action
7.5.2.3 Push backup power switch of 4.16kV bus to the test position;
7.5.2.5 Take security measures onto standby transformer and submit to maintenance
for further treatment.
7.6.1 In the case of 480V auxiliary power failure due to the malfunction of low-voltage
auxiliary transformer outside the main plant, check and confirm if working switch has
been disconnected. If there is no signal of over-current on working branch, close bus
contact switch manually and restore 400V power running. Isolate failed low-voltage
auxiliary transformer, take necessary safety measures and contact maintenance
department to deal with.
7.6.3.2 When switch is tripping off on 480V PC and, shall check if security MCC
working power trips off, and if diesel generator is running for power supply of security
MCC.
7.6.3.3 Measure insulation of 480V PC bus, disable the bus, and inform maintenance
staff to deal with.
7.6.4 There is evidence showing that fuse of bus PT on 480V PC segment has been
blew out.
Centralized control room sends out the signal of “Voltage circuit of bus PT on 480V
PC segment A is broken". Voltmeter of bus indicates voltage is decreased.
7.6.5 Action
automatically.
7.6.6.2 Reduce load of transformer or switch its 480V bus to another transformer for
further power supply.
7.7.1 DC system fault and trouble shooting for abnormal voltage of accumulator
battery:
7.7.1.2 After received fault information, on-duty workers shall come to scene and
measure the actual terminal voltage of single battery cell immediately, and notify
maintainer to deal with.
7.7.2.1 When a single charger module fails, withdraw the single module from the
operation, and maintenance deal with contact.
7.7.2.2 When entire group of charger fails, withdraw the whole modules from the
operation, if cannot be repaired temporarily, the batteries carried by the failed charger
shall be switched onto another normal charger for further charging. In the process of
7.7.3.1 Alarm rings, "Unusual Voltage DC Bus” is shown on light words plate.
7.7.3.2 Voltage of bus shown on charger display and feeder display is too low.
7.7.4.1 Restore alarm ring, confirm if voltage of DC bus is dropping and check
whether or not charger is working normally.
7.7.4.2 Failed bus, if necessary, shall be switched onto the power supply of another
bus, and inform maintainer to deal with.
7.7.5.1 Alarm rings, "Unusual Voltage DC Bus” is shown on light words plate.
7.7.5.2 Voltage of bus shown on charger display and feeder display is too high.
Restore alarm ring, if charger trips off, the power of DC system may be supplied
accumulator batteries separately until voltage of DC bus drops down to the specified
value, and then put charger into operation to ensure the voltage of bus to fall into the
allowed range.
7.7.7.1 Check ground electrode and ground resistance on the on-line monitoring
device of insulation, fault alarming point is the earth point.
7.7.7.2 Trial running shall be conducted according to the nature of load, by the order
of “load first, power later” and “backup first, working later”. Before trial running, shall
notify concerned operators, power for heat engineering shall be conducted by thermal
workers, power of electrical protection shall be conducted by protection workers.
7.7.7.3 Trial running of main protection shall be get approval of dispatch stuff, any
protection apt to faulty operation shall be removed.
7.7. 7.4 After trial running, whether or not the equipment is grounded, power shall be
supplied immediately.
7.7.7.5 After found out the grounding equipment, notify the maintainer to deal with.
Find out the reason of AC losing electricity and restore power supply as soon as
possible. If fails to restore temporarily, shall switch its DC bus to the power supply of
another DC bus, and stop the charger for further treatment.
Centralized Control Room issued the signal of "Fuse Failure on 125V DC System
Accumulator Battery ".
7.7.10 Measures for blown out fuse of 125V DC system accumulator battery
7.7.10.2 Switch the related load onto the power supply of another bus and stop the
charger of the faulty bus;
7.7.10.4 After eliminating the fault, replace the fuse of the accumulator battery and
restore the original operation mode.
7.7.11.4 Voltage shown on feed cabinet of voltage-lost bus is close to zero; load
indicator lamp is out.
7.7.12.2 Open all disconnecting links of voltage-lost bus and check the bus;
7.7.12.3 Measure the insulation of DC bus, if there is obvious fault on bus, stop the
use of faulty charger and accumulator battery of bus; advise maintainer to deal with as
soon as possible;
7.7.12.4 Ask maintainer to check power failure protection and monitor closely the
normal operation of another bus.
7.7.13.2 Switch the bus load electrified by the faulty battery to the by the power supply
of another normal bus.
7.7.13.4 Put out fire with carbon dioxide or carbon tetrachloride fire extinguishers.
During the normal operation, it is not allowable for to operate under overloaded. In the
case of accident, generator can operate under overloaded for a short time but not
more than 2 times per year, with a time interval of not less than 30min. Generator
adopts inverse-time-lag overload protection, when generator is overloaded 1.2 times,
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 103 / 118
the maximum running time shall be 60s and generator shall be separated and
stopped.
7.8.5.1 If protection operation generator trips off, this can be treated the same as main
switch tripping.
7.8.5.2 If generator fails to trip, check if there is any water leakage, and if any
generator PT fault, check thoroughly against meter, if confirm this is due to grounding
of generator stator, generator shall be stopped urgently for further treatment.
Signal "One Point Grounding Fault of Generator Rotor “is issued. Fault recorder is
activated.
7.8.7.1 If generator trips out, this can be treated the same as protection operation
outage.
7.8.7.2 Check thoroughly the excitation system to see if any clear grounding. If there
is loss of excitation or step-out occurring on generator while grounding, the generator
shall be separated and stopped immediately.
7.8.7.5 If grounding point is inside rotor, it shall be reported to Chief Forman, and the
generator shall be stopped for repairing promptly.
7.8.8.5 Signal “Generator Reverse Power Trip” is issued. Fault recorder is activated.
7.8.9.1 If generator protection operation trips out, this can be treated the same as
protection operation outage.
7.8.10.3 Active load waves and reduce and reactive load is shown below zero.
7.8.13.1 Ammeter of stator swings back and forth, current is usually more than rated
value.
7.8.13.2 Voltmeter of stator swings dramatically; voltage is usually more than rated
value.
7.8.13.5 Generator emits rhythmic noise, which beats together with the swing of
meter.
7.8.14.4 If the oscillation occurs on generator and system and step-out protection
does not work, generator shall be separated immediately.
7.8.14.5 If the oscillation caused by the system, it need to increase the excitation
current of generator, maintain the system voltage, and deal with it in accordance with
instructions by Dispatch Stuff and Chief Foreman.
7.8.15.1 Check what this is kind of protection operation, determine the nature of
failure and notify maintainer.
7.8.15.2 If this is a faulty operation by workers, it needs not to check generator, and
generator shall be boosted and synchronized according to the instruction by Chief
Foreman.
7.8.15.3 After eliminating failure and there is not any more problems on all aspects,
then generator can be re-incorporated into electric network.
7.8.15.4 If there is fault on only one circuit breaker, after confirming no further problem,
generator can conduct parallel operation.
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 107 / 118
7.8.16.2 During step-out and outage, If open phase is caused by switch fault of
generator, the main throttle valve of steam turbine shall be not closed and maintain a
rotating rate of 3,000rpm.
7.8.16.3 Re-synchronize the generator-transformer unit with the system and notify
maintainer to resolve it.
7.8.16.4 If main throttle valve has been closed or generator-transformer unit cannot be
synchronized with system, it is required to open all switches adjacent to the failed
switch immediately.
7.8.16.5 If single-phase fault of circuit makes main switch single-phase trip, at this
time, the operator shall not disturb reclosing action.
7.8.17.2 Check if de-excitation switch of generator is well closed, if generator can start
excitation, and if startup excitation power is normal.
7.8.20 During the following conditions, transformer can be disabled after getting
instruction:
5) Insulating oil looks deep dark, feculent, and its viscosity, acidity, ash content is
increasing.
7) When load, ambient temperature and cooling conditions remains unchanged, while
the temperature of oil and winding of transformer rise up abnormally.
7.8.21 When temperature of transformer rises up and exceeds the allowable value,
the following examination shall be conducted:
3) If there is cooling device failure, the load of transformer shall reduced so that to
allow the oil temperature of transformer to increase up to the allowable value.
4) If confirm that oil temperature increase abnormally, the transformer shall stop
running immediately.
7.8.22 Although oil temperature of transformer falls within the maximum allowed value,
the maximum is higher 10℃ above that under the same load and cooling conditions, it
shall be regarded as an abnormal temperature rise. Abnormal temperature rise may
be caused by the following reasons:
4) There are anomalies such as short circuit or eddy between iron core and silicon
sheets.
7.8.23 When oil level of transformer is significantly lower than that shall be required at
the time, it is necessary to find out the reasons and notify the maintainer to refuel.
During re-filling, heavy gas protection shall be switched from tripping to signal.
7.8.24 If one of the following circumstances occurs on transformer and the protection
fails to trip, the transformer shall be stop from running immediately:
3) Transformer is smoking and on fire, and pressure relief valve pressure release
valve is activated.
6) Under the normal load and cooling conditions, top oil temperature or coil
temperature exceeds the limit value and is increasing dramatically.
7) Over-excitation of transformer reaches limit value, and the protection fails to trip.
8) Person electric shock occurs and cannot be separated from the power supply.
1) Check if there is any short circuit, flashover and damage trace on all electrical
equipments within the scope of protection.
2) Check if transformer has been painted, and if temperature and color of oil is normal.
1) In the process of oil filtering and refueling process, air enters inside transformer.
3) Check if there is gas inside gas relay, if yes, it is required to sample gas and
analyze and observe the color of gas. In addition, gas release test shall be conducted
and gas shall be sampled according to "Safety Code".
4) If the failure reason is that there is air in oil, it is required to release air and record
exactly signal failure time, if interval between successive failures is shortened, shall
report to Chief Engineer, and change the heavy gas protection signal to signal or
switch it to operation under backup transformer.
When gas protection has been put into signal position and hence signal “Heavy Gas
Failure” is issued, it shall be switched to operation under backup transformer, If while
signal “Heavy Gas Failure” is appearing, the current of transformer is getting normal,
then the transformer shall stop running immediately.
1) Check if the upper oil temperature / level is normal, and if explosion-proof tubes
and other parts have been oil painted.
2) When heavy gas traps and light gas issues signal, shall check the failure situation
of gas relay and need to analyze gas oiliness, the transformer cannot be put into
operation unless passed through a test inspection.
1) If it is colorless, tasteless and nonflammable gas, this means there is air inside
transformer.
2) If it is gray or steel grey gas with odor, this means paper insulation fault on
transformer.
4) If it is black flammable gas, this shall be carbide decomposition due to insulating oil
internal fault.
1) Cut off the power immediately, put out the fire with dry powder or CO2 fire
extinguisher and notify the fire brigade. It is strictly prohibited to fight fire with any
liquid before cutting off the power supply.
3) If the transformer cap is on fire, open the emergency oil release throttle to make oil
level below the fire, and it is shall not be allowed to bring out the flame.
2) Identify the reasons promptly and restore the running of cooling device as soon as
possible.
3) Reduce the load of transformer to the specified value and make sure that oil
temperature of transformer shall not exceed the specified value.
4) If power fails to be restored, and the upper oil temperature of transformer has
reached the specified value or the duration of full stop of cooler has reached up to
specified value, the transformer shall stop running.
7.8.34 Abnormal operation and the corresponding measures for SF6 switch, vacuum
switch and air switch:
1) Close the control circuit to see if circuit power is normal, if small switch of control
power is proper closed, if there is broken wire on circuit, and if control power switch is
breaking.
10) If any failure on auxiliary power switch caused by thermal or electrical latch-up
closed contacts.
Serial No.:HTP-ER-OM-A-3 R e v. 0 Issued Date:01/01/2014
Dept. Operation Regulation for Page:
O&M Electric System 114 / 118
1) Check if trip circuit has been electrified, if there is broken wire on circuit, and if
control power switch is tripping.
7) If tripping relay and tripping coil is broken, burning, jammed or poorly contacted.
7.8.34.3 Measures for circuit breaker refusing to trip and not being eliminated:
1) For 138kV system, shall contact with Dispatch Stuff to call for leapfrog power
cutting or other alternatives.
2) For 13.8kV, 4.16kV or 480V switch, shall adopt manual tripping immediately. If still
fails to trip, shall report to Chief Foreman and open the higher-level.
3) Before trouble shooting completed, do not put any circuit breaker refusing to trip
into operation again.
7.8.34.4 During operation, if the following situation takes place, circuit breaker shall
call for an immediate outage.
2) SF6 gas leaks and cannot supplement gas on power when being electrified.
6) When fire or personal electric shock happens on circuit breaker, the circuit breaker
shall stop running immediately.
2) If there is no backup equipment available, the load shall be so adjusted that the
temperature drops to below 70℃.
3) Take temporary cooling measures, after the load satisfying the requirement, ask for
outage for further treatment.
2) The corresponding voltmeter indicates to zero, watt-hour meter will not turn.
1) Identify failed voltage transformer and monitor the operation with ammeter.
3) As for secondary switch tripping or fuse melting down, can be given one more trial,
if still fails, shall notify maintainer to deal with.
If high-voltage fuse melts down, shall cut off the power supply and measure the
insulation and ask maintainer to deal with.
1) Report immediately to Chief Foreman and ask for outage for further treatment.
2) Disable failed voltage transformer, can only be fulfilled by switch, and shall ask for
switching operation.
3) If voltage transformer is on fire, shall disconnect immediately the power and put out
fire with dry-type fire extinguisher or sand.
2) According to the evidence, check current transformer secondary circuit to find out
open circuit. During checking, necessary measures shall be taken against electric
shock.
3) If open circuit is obvious, wear insulated boots and gloves immediately and connect
the open circuit or connect at terminal before open circuit.
If the main body is still buzzing after short-circuit, this means internal open-circuit,
shall ask for should apply for outage for further treatment.
6) If the second open-circuit caused a fire, it must cut off the power supply first, then
put out fire with fire extinguisher to prevent fire spreading.
1) Try to cut off the power with switch and put out fire quickly with dry powder or
carbon tetrachloride fire extinguishers.
2) Put out fire with carbon tetrachloride, carbon dioxide or sand, it is prohibited to put
out fire with foam extinguisher or water.
3) When cable pit is on fire, shall close all of doors, windows and ventilation
equipments, after putting out fire, and re-open them to ventilated bad gases.
4) Any person entering to cable pit for fire-fighting, shall wear gas masks, insulated
gloves and insulated boots etc.
5) Do not touch any earth-free metals, steel armored cables and removal cables
during fire-fighting.
7.8.38 If cable encounters the following circumstances, it is required to cut off the
power supply immediately
7.8.39 When electrical equipment is on fire, it is necessary to cut off the power supply
first, then put out fire with fire extinguishers. If fire happens nearby which may cause
danger risk against electrical equipments, shall stop the operation of electrical
equipments and cut off the power supply.