FROM TRANSAMADI

132KV INCOMING LINE A

FROM OMOKU
132KV INCOMING LINE

CVT-1
CVT-2 CVT-3 CVT-4 132KV OUTDOOR SWITCHYARD

LA-A1
LA-A4 LA-A5 LA-A8

IS + ES-A1 IS + ES-A2 IS + ES-A3 IS + ES-A4


CT-A1
CT-A3 CT-A5 CT-A7

CB-A1 M
CB-A3 M
CB-A5
M
CB-A7
M

SCHEDULE OF NEW EQUIPMENT FOR PROPOSED 132KV & 33KV EXTENSION


& REINFORCEMENT TO EXISTING 40MVA + 60MVA 132/33KV TRANSMISSION SUBSTATION
NOTE: 1 SET = 3PHASE, 1Nos = 1Phase 132KV MAIN BUS ACSR STRAINED BUSBAR
S/NOS DEVICE ID DEVICE DESCRIPTION SPECIFIC RATING QTY
1 IS-A19,A20 132KV DISCONNECT SWITCH Ur = 132KV; Um = 145KV; IS-A17
2Set IS-A12 IS-A15
Ir = 2000A; Isc = 31.5KA(1s) IS-A4 IS-A8 IS-A10 IS-A19
IS-A1 IS-A6
2 CVT-7 132KV CAPACITIVE VOLTAGE Ur = 132 0.11 0.11 KV Um = 145KV
TRANSFORMER 3 3 3 CVT-5
1Set
METERING CLASS: 20VA, CL 0.2
PROTECTION CLASS: 50VA, CL 3P
M
3 CB-A8 132KV CIRCUIT BREAKER Ur = 132KV; Um = 145KV; CB-A4
1Set
Ir = 2000A; Isc = 31.5KA(1s)
4 CT-A8 132KV CURRENT Ir = 800-300A/1A/1A/1A/1A/1A/1A CT-A4
TRANSFORMER CORE 1: CL 0.2 10VA
CORE 2: CL 0.2 10VA 1Set
CORE 3: CL 5P20 20VA IS-A9 IS-A11
CORE 4: CL 5P20 20VA IS-A2 IS-A7
CORE 5: CL X 20VA IS-A16
CORE 6: CL X 20VA IS-A5 IS-A13 IS-A20
IS-A18
5 LA-A9 120KV LIGHTNING ARRESTER Ur = 120KV; Um = 145KV; 1Set
Ipk = 10KA 132KV RESERVE BUS
6 NCT-A9 NEUTRAL CURRENT Ir = 400A/1A/1A
TRANSFORMER (TRAFO PRI CORE 1: 5P20 20VA 1Nos
NEUTRAL) CORE 2: 5P20 20VA
7 IS-B10, B11, 33KV DISCONNECT SWITCH Ur = 33KV; Um = 36KV; 4set CVT-6
B12, B13 Ir = 1250A; Isc = 25KA(1s)

8 IS+E-B7,B8, 33KV DISCONNECT SWITCH Ur = 33KV; Um = 36KV; 3set CVT-7


B9 WITH EARTH SWITCH Ir = 1250A; Isc = 25KA(1s) CB-A2 M
CB-A6 M CB-A8 M

9 LA-B4, B5, B6, 33KV LIGHTNING ARRESTER Ur = 33KV; Um = 36KV; 4set


B7 Ipk = 10KA
10 VT-B3, B4, B5, 33KV VOLTAGE Ur = 33 0.11 0.11KV Um = 36KV CT-A8
B6 TRANSFORMER 3 3 3 4Set
METERING CLASS: 20VA, CL 0.2 CT-A2 CT-A6
PROTECTION CLASS: 50VA, CL 3P
11 CT-B9 33KV CURRENT Ir = 1200/600A/1A/1A/1A/1A/1A LA-A2 LA-A6 LA-A9
TRANSFORMER CORE 1: CL 0.2 10VA
( TRAFO SECONDARY) CORE 2: CL 0.2 10VA LA-A3 LA-A7
CORE 3: CL 5P20 20VA 1Set
CORE 4: CL 5P20 20VA
CORE 5: CL 5P20 20VA
TX-1
40MVA
TX-1
60MVA
A' TX-3
60/66MVA
132/33KV 132/33KV 132/33KV
IS-A3
12 CB-B9, B10, 33KV CIRCUIT BREAKER Ur = 33KV; Um = 36KV; 4Set IS-A14
B11, B12 Ir = 1250A; Isc = 25KA(1s) CT-A9
13 CT-B10, B11, 33KV CURRENT Ir = 800-300A/1A/1A/1A/1A
B12 TRANSFORMER CORE 1: CL 0.2 10VA 4Set
(33KV FEEDER) CORE 2: CL 0.2 10VA
CORE 3: CL 5P20 20VA
CORE 4: CL 5P20 20VA
14 ETX 3 EARTHING TRAFO 6100/300KVA ETX-1 ETX-2 LA-B4
33/0.415KV 1Nos
ETX-3
15 TX-3 POWER TRAFO 60/66MVA, 132/33KV POWER
TRAFO 1Nos VT3

1C - 33KV XLPE CABLE 1C - 33KV XLPE CABLE


REVISIONS
LA-B1 LA-B2
CT-B9
33KV INDOOR SWITCHGEAR
VT1 VT2 CB-B9 M

CT-B1 CT-B5
00 24/07/2022 ISSUED FOR APPROVAL P. ERIC CHINEDUM
M M IS-B10
CB-B1 CB-B5
33KV OUTDOOR SWITCHYARD REV DATE DESCRIPTIONS DRAWN CHK'D APPROVAL
Al- TUBULAR BUS BAR - 33KV, 1250A
IS-B1 IS-B6

IS-B5 IS-B11 IS-B12 IS-B13

CB-B10 M CB-B11 M CB-B12 M

IS-B2 IS-B3 IS-B4 IS-B7 IS-B8 IS-B9 CT-B10 CT-B11 CT-B12

CB-B2 M CB-B3 M CB-B4 M CB-B6 M CB-B7 M CB-B8 M IS + E-B7 IS + E-B8 IS + E-B9

CT-B2 CT-B3 CT-B4 CT-B6 CT-B7 CT-B8


VT-B4 VT-B5 VT-B6
LA-B5 LA-B6 LA-B7
IS + E-B1 IS + E-B2 IS + E-B3 IS + E-B4 IS + E-B5 IS + E-B6
FROM TRANSAMADI
132KV INCOMING LINE A

FROM OMOKU
132KV INCOMING LINE

CVT-1
CVT-2 CVT-3 CVT-4

LA-A1
LA-A4 LA-A5 LA-A8

IS + ES-A1 IS + ES-A2 IS + ES-A3 IS + ES-A4


CT-A1
CT-A3 CT-A5 CT-A7

CB-A1 M
CB-A3 M
CB-A5
M
CB-A7
M

132KV MAIN BUS ACSR STRAINED BUSBAR

IS-A17
IS-A12 IS-A15
IS-A1 IS-A4 IS-A6 IS-A8 IS-A10
CVT-5

M
CB-A4

CT-A4

IS-A9 IS-A11
IS-A2 IS-A7
IS-A16
IS-A5 IS-A13
IS-A18
132KV RESERVE BUS

CVT-6

CB-A2 M
CB-A6 M

CT-A2 CT-A6

LA-A2 LA-A6

LA-A3 LA-A7
TX-1
40MVA
TX-1
60MVA
A'
132/33KV 132/33KV
IS-A3
IS-A14

REVISIONS

ETX-1 ETX-2
00 24/07/2022 ISSUED FOR APPROVAL P. ERIC CHINEDUM

REV DATE DESCRIPTIONS DRAWN CHK'D APPROVAL

1C - 33KV XLPE CABLE 1C - 33KV XLPE CABLE

LA-B1 LA-B2
33KV INDOOR SWITCHGEAR
VT1 VT2
CT-B1 CT-B5

M M
CB-B1 CB-B5

IS-B1 IS-B6

IS-B5

IS-B2 IS-B3 IS-B4 IS-B7 IS-B8 IS-B9

CB-B2 M CB-B3 M CB-B4 M CB-B6 M CB-B7 M CB-B8 M

CT-B2 CT-B3 CT-B4 CT-B6 CT-B7 CT-B8

IS + E-B1 IS + E-B2 IS + E-B3 IS + E-B4 IS + E-B5 IS + E-B6


A

SCHEDULE OF NEW EQUIPMENT FOR PROPOSED 132KV & 33KV EXTENSION


& REINFORCEMENT TO EXISTING 40MVA + 60MVA 132/33KV TRANSMISSION SUBSTATION
NOTE: 1 SET = 3PHASE, 1Nos = 1Phase
S/NOS DEVICE ID DEVICE DESCRIPTION SPECIFIC RATING QTY
1 IS-A19,A20 132KV DISCONNECT SWITCH Ur = 132KV; Um = 145KV; 2Set
132KV OUTDOOR SWITCHYARD Ir = 2000A; Isc = 31.5KA(1s)
2 CVT-7 132KV CAPACITIVE VOLTAGE Ur = 132 0.11 0.11 KV Um = 145KV
TRANSFORMER 3 3 3 1Set
METERING CLASS: 20VA, CL 0.2
PROTECTION CLASS: 50VA, CL 3P
3 CB-A8 132KV CIRCUIT BREAKER Ur = 132KV; Um = 145KV; 1Set
Ir = 2000A; Isc = 31.5KA(1s)
4 CT-A8 132KV CURRENT Ir = 800-300A/1A/1A/1A/1A/1A/1A
TRANSFORMER CORE 1: CL 0.2 10VA
CORE 2: CL 0.2 10VA 1Set
CORE 3: CL 5P20 20VA
CORE 4: CL 5P20 20VA
CORE 5: CL X 20VA
CORE 6: CL X 20VA
5 LA-A9 120KV LIGHTNING ARRESTER Ur = 120KV; Um = 145KV; 1Set
Ipk = 10KA
6 NCT-A9 NEUTRAL CURRENT Ir = 400A/1A/1A
TRANSFORMER (TRAFO PRI CORE 1: 5P20 20VA 1Nos
NEUTRAL) CORE 2: 5P20 20VA
7 IS-B10, B11, 33KV DISCONNECT SWITCH Ur = 33KV; Um = 36KV; 4set
B12, B13 Ir = 1250A; Isc = 25KA(1s)

8 IS+E-B7,B8, 33KV DISCONNECT SWITCH Ur = 33KV; Um = 36KV; 3set


IS-A19 B9 Ir = 1250A; Isc = 25KA(1s)
WITH EARTH SWITCH
9 LA-B4, B5, B6, 33KV LIGHTNING ARRESTER Ur = 33KV; Um = 36KV; 4set
B7 Ipk = 10KA
10 VT-B3, B4, B5, 33KV VOLTAGE Ur = 33 0.11 0.11KV Um = 36KV
B6 TRANSFORMER 3 3 3 4Set
METERING CLASS: 20VA, CL 0.2
PROTECTION CLASS: 50VA, CL 3P
11 CT-B9 33KV CURRENT Ir = 1200/600A/1A/1A/1A/1A/1A
TRANSFORMER CORE 1: CL 0.2 10VA
( TRAFO SECONDARY) CORE 2: CL 0.2 10VA
CORE 3: CL 5P20 20VA 1Set
CORE 4: CL 5P20 20VA
IS-A20 CORE 5: CL 5P20 20VA

12 CB-B9, B10, 33KV CIRCUIT BREAKER Ur = 33KV; Um = 36KV; 4Set


B11, B12 Ir = 1250A; Isc = 25KA(1s)
13 CT-B10, B11, 33KV CURRENT Ir = 800-300A/1A/1A/1A/1A
B12 TRANSFORMER CORE 1: CL 0.2 10VA 4Set
(33KV FEEDER) CORE 2: CL 0.2 10VA
CORE 3: CL 5P20 20VA
CORE 4: CL 5P20 20VA
14 ETX 3 EARTHING TRAFO 6100/300KVA
CVT-7 33/0.415KV 1Nos
CB-A8 M
15 TX-3 POWER TRAFO 60/66MVA, 132/33KV POWER
TRAFO 1Nos

CT-A8

LA-A9

A' TX-3
60/66MVA
132/33KV
REVISIONS
CT-A9

00 24/07/2022 ISSUED FOR APPROVAL P. ERIC CHINEDUM

REV DATE DESCRIPTIONS DRAWN CHK'D APPROVAL


LA-B4
ETX-3

VT3

CT-B9

CB-B9 M

IS-B10
33KV OUTDOOR SWITCHYARD

Al- TUBULAR BUS BAR - 33KV, 1250A

IS-B11 IS-B12 IS-B13

CB-B10 M CB-B11 M CB-B12 M

CT-B10 CT-B11 CT-B12

IS + E-B7 IS + E-B8 IS + E-B9

VT-B4 VT-B5 VT-B6


LA-B5 LA-B6 LA-B7