Professional Documents
Culture Documents
.VTRO N MANUFACTURING,INC,
1809001
QUALITY · RELIABILITY · SERVICE · VALUE QUAUTY SYSTEM CERTIRED
-- -
Neutral Grounding Resistors
Avtron Neutral Grounding Resistors are
designed to provide added safety to
industrial distribution systems by limiting
ground fault current to reasonable .--1. --- _ _ __ _
levels. In a typical solidly grounded four
wire system, the neutral is tied directly
to earth ground. This can cause high
ground fault current (typically 10,000 to
20,000 amps) and excessive damage to
transformers, generators, motors,
wiring, and associated equipment.
Inserting an Avtron Neutral Grounding
Resistor between neutral and ground
limits fault current to a safe level
(typically 25 to 400 amps) while still
allowing sufficient current flow to
operate fault clearing relays. Limiting
fault current also reduces the problem
of transient overvoltages (up to six
times normal voltage) which can occur
during arcing type ground faults.
Avtron Neutral Grounding Resistors are
engineered with reliability, safety, and
ease of installation as top priorities. .J
For total support in selecting the right neutral grounding resistor or industrial resistor product for your application, contact
your Avtron sales engineer at (216) 641-8310.
Neutral Grounding Transformers
Avtron Neutral Grounding Resistors can be supplied with open frame construction, for Avtron Neutral Grounding Transformers are
installation inside switchgear or similar enclosures, or fully assembled with indoor / similar in design to Avtron Neutral
outdoor safety enclosures. Options include: Grounding Resistors and provide high
Current Transformers resistance grounding for medium
voltage generators and transformers.
Potential Transformers
The standard package consists of a
Disconnect Switches (oil or air insulated) single-phase, dry-type, EpoxycasFM
· Overcurrent Relays transformer plus a secondary power
resistor, mounted in a common
· Aluminum or Stainless Steel Enclosures enclosure. The transformer is typically
Special Paint selected with a primary voltage equal to
or greater than the system voltage to
· Seismic Qualified Units
maintain a high insulation rating for
High Altitude Ratings (above 6000 feet) added safety. The transformer
· Hazardous Location Ratings (Class 1, Group D, Division II) secondary is rated at 240 volts and
factory wired to the resistor. The resistor
is sized so the fault current reflected
through the transformer produces the
desired fault current on the system
neutral (typically 2 to 12 amps for 60
seconds). A voltage relay connected to
the secondary resistor is used to detect
the presence of a ground fault. If the
fault persists beyond a certain time
period, the relay will send a signal to
open the main circuit breaker.
Grounding Transformer rated 2400 volts L-N, 10 amps, 60 seconds, with 15KVA 4160:240 p.T.
· KVA
Grounding Transformer
Rating (if applicable)
· Special Options
Neutral Grounding Resistors
10 Second Ratings (760'C Temperature Rise)
Avtron
Part
System Line-To- Initial Length Width Height Approx.
Voltage Neutral Current L W H Weight
Outline Drawings
Number Voltage (AMPS)
ANG14-1 2400 1390 100 42 42 42 250 ----- 1
ANG14-2 2400 1390 200 42 42 42 250 co '0) 2.62
ANG14-4 2400 1390 400 42 42 42 250 :
01
ANG14-6 2400 1390 600 42 42 42 300
ANG14-8 2400 1390 800 42 42 42 350
ANG14-10 2400 1390 1000 42 42 42 400
ANG14-12 2400 1390 1200 46 60 76 500
ANG24-1 4160 2400 100 42 42 42 300 01
NOTE: Other voltage, current, and time ratings available. Consult factory.
Specifications subject to change without notice. All
dimensions are in inches.
Printed in U.S.A. Bulletin 409
Rev. B
MANUFACTURING, INC.
10409 MEECH AVE., CLEVELAND, OH, U.S.A. 44105. (1) 216~41-8310. FAX: (1) 216-441-2459
E-MAIL: resistors@avtron.com. HOME PAGE: www.avtron.com
Avtron Wirewound Resistors
Avtron Wirewound Resistors are designed Avtron Resistance in
Continuous
Continuous
for low current industrial applications from Part AMP Capacity
1 amp to 32 amps continuous with Number OHMS @25°C* @375°C Rise WATTAGE
convection cooling. Heavy-duty AWR25 0.25 32.0 256
construction allows higher ratings for AWR30 0.30 31.0 288
intermittent duty applications. AWR35 0.35 .A$ 29.0_ ?Q<1
AWR50 0.50 27.0 365
Engineered for reliability, these resistors
AWR70 0.70 22.0 339
feature all stainless steel construction
AWR100 1.00 18.0 324
including the element, terminals and
AWR140 1.40 15.5 336
terminal hardware. Avtron Wirewound AWR150 1.50 15.0 338
Resistors can be supplied loose,
AWR190 1.90 13.3 336
preassembled with brackets, or fully
AWR200 2.00 13.0 338
assembled in indoor or outdoor enclo- AWR220 2.20 12.5 344
sures. This simplifies and speeds AWR250 2.50 12.0 360
installation to save time and money. AWR260 2.60 12.0 374
To further improve functionality, these AWR320 3.20 10.8 373
AWR350 3.50 10.5 386
resistors can be provided with optional
AWR390 3.90 10.0 390
wiring and control systems. Contact your
Avtron sales engineer for total support in AWR400 4.00 10.0 400
AWR450 4.50 9.2 381
selecting resistors, assemblies, and
AWR480 4.80 8.8 372
custom configurations for your application. AWR500 5.00 8.5 361
AWR550 5.50 8.0 352
AWR580 5.80 7.7 344
AWR600 6.00 7.6 347
Outline Drawings AWR650 6.50 7.4 356
AWR700 7.00 7.3 373
~
AWR800 8.00 7.1 403
2.50
APPROX. ITmill11IDfi AWR850
AWR860
8.50
8.60
7.0
6.8
417
398
0.38 -2.00
I 7.25 I AWR1000 10.00 6.2 384
DIA. APPROX. AWR1100 11.00 6.0 396
AWR1150 11.50 5.9 400
Loose resistor AWR1170 11.70 5.9 407
AWR1200 12.00 5.8 404
AWR1500 15.00 5.3 421
AWR2000 20.00 4.6 423
AWR2700 27.00 3.6 350
AWR3600 36.00 3.0 324
AWR4500 45.00 2.5 281
AWR6200 62.00 2.0 248
AWR8000 80.00 1.8 259
AWR8100 81.00 1.8 262
AWR10000 100.00 1.6 256
AWR12500 125.00 1.4 245
0.44 DIA. AWR15000 150.00 1.3 254
MTG
HOLES AWR17500 175.00 1.2 252
AWR20000 200.00 1.1 242
Resistors with panel mount brackets
AWR25000 250.00 1.0 250
10409 MEECH AVE., CLEVELAND, OH, U.S.A. 44105. (1) 216-641-8310. FAX: (1) 216-441-2459
E-MAIL: resistors@avtron.com. HOME PAGE: www.avtron.com
Avtron Wirewound Resistors
Type AWR
· Low temperature coefficient elements for
more stable resistance
- -- -