Professional Documents
Culture Documents
PS of H Pressure Vessels
PS of H Pressure Vessels
PERFORMANCE STANDARD
ICE Tag: Z060-V-220 ICE Description: Wet Train - 3rd Stage Separator
GOAL
The liquid phase coming from the 1st Stage is routed to 2nd stage separator in order to realize the water-oil separation. After water and oil have been separated in the
2nd stage separator , the oil is sent to dehydrator Z060-V-280, while the water is sent to drainage vessel after that the oil come from dehydrator to 3rd stage separator in
order to realize the water-oil separation where the oil is sent to desalter Z060-V-290 for salt remove while the water is sent to drainage vessel.
SCOPE
The following Performance Standard applies to the Zubair Field and more specifically to the Hammar DGS
FUNCTIONALITY
The inspection of the corrosion inhibitor system is Perform inspections of the corrosion inhibitor injection
mandatory to ensure high valus of the corrosion system to ensure appropriate working conditions and Corrosion inhibitor skid is properly working.
treatment availability. injection dosages.
Adequate corrosion inhibitor availability shall be Ensure the fluid is properly treated with corrosion
guaranteed for the whole operating life. inhibitors for CO2 corrosion control. Corrosion inhibitor skid is properly working.
Internal visual inspection of vessels is to be carried out Vessel internal shall not present any signs of rust, corrosion,
during periodical plant shut-in. Perform visual inspection of tanks and vessels internals oxidation and damages
and deadlegs to check evidences of corrosion, the
status of internal coating/lining and the anodes of the
CP System.
Batch treatments shall be performed on a periodical Ensure the fluid is properly treated with biocide for MIC
No assurance value is currently available for this parameter
basis. and biofouling avoidance.
External visual inspection of the vessel in accordance to
API 510 Check vessel status for signs of rust, corrosion, Vessel surface shall not present any signs of rust, corrosion,
oxidation and any external damage oxidation and external damages
Frequency: Every five years
An earth ground connection of the exposed conductive parts of electrical equipment helps protect Check earthing connection status
from electric shock by keeping the exposed conductive surface of connected devices close to earth Frequency: Every one year Check the voltage between neutral and earth Voltage: 0 V
potential, when a failure of electrical insulation occurs
General maintenance of the vessel has to be performed to keep overall performance of the equipment within Clean of the internals
the design parameters Frequency: Every 10 years or during Plant shutdown
Remove and clean the internals for further inspections should be internally inspected at 2023
AVAILABILITY/RELIABILITY
Target Value
Availability 0.0022
Reliability 0.0022
SURVIVABILITY
N/A
System and/or equipment interacting with this ICE Reason for the dependency/interaction
The Dehydrator receives oil from the 2nd stage separtor Z060-V-210 through 10" pipe to improve the sepration between oil and water. The water is sent to Produced Water
Dehydrator Z060-V-280 Treatment CPI , while the oil is sent to 3rd stage separtor Z060-V-220. In case of failure of the Dehydrator, the vessel can be bypassed and send to 3rd stage separtor Z060-V-220. The
system will continue to work, however the oil quality will degrade.
The 3rd Stage Separator - Wet Train Z060-V-220 send oil/water mixture to the Desalter for water and salt removal , salt water is sent to drain header and recycle water pump, while
Desalter Z060-V-290 oil is sent to 4th stage separator to improve the oil-water separation, the vessel can be bypassed and send to 4th stage separtor Z060-V-230. The system will continue to work,
however the oil quality will degrade.
Close and check if the Permit to Work has been correctly signed
Wet Train - 3rd Stage Separator - Z060-V-220 - Every five years or during Plant shutdown/turnaround for Internal Inspection
Action Remarks Results
Inform the Control Room of beginning of the works and open the Permit
to Work
Check vessel status for signs of rust, corrosion, oxidation and any
external damage
Open the manhole and ventilate the vessel and make sure is gas free
Enter into the vessel (external support to people entering the vessel is
mandatory)
Close manholes
Close and check if the Permit to Work has been correctly signed
Make sure the connection lines are not blocked and flush if required
Close and check if the Permit to Work has been correctly signed
Inform the Control Room of beginning of the works and open the Permit
to Work
Make sure the connection lines are not blocked and flush if required
Close and check if the Permit to Work has been correctly signed
Close and check if the Permit to Work has been correctly signed
Attachment G - Performance Standard Template
PERFORMANCE STANDARD
ICE Tag: Z060-V-230 ICE Description: Wet Train - 4th Stage Separator
GOAL
The liquid phase coming from the 1st Stage is routed to 2nd stage separator in order to realize the water-oil separation. After water and oil have been separated in the 2nd
stage separator , the oil is sent to dehydrator Z060-V-280, while the water is sent to drainage vessel after that the oil come from dehydrator to 3rd stage separator in order
to realize the water-oil separation where the oil is sent to desalter Z060-V-290 for salt remove while the water is sent to drainage vessel. after the oil is sent to 4th stage for
final water- oil separation where the oil is sent to flow tank and water is sent to drainage header.
SCOPE
The following Performance Standard applies to the Zubair Field and more specifically to the Hammar DGS
FUNCTIONALITY
Ensure corrosion rate is within predicted values. Monitor corrosion rate from fast-response ER/LPR
Consider intervention in case corrosion rates higher than
expected are detected. Use results of corrosion probes and long-term response CC installed at CMPs.
Consider also the possibility to measure Corrosion rate expected: HOLD
monitoring to check corrosion inhibitor effectiveness by
corrosion/erosion rates by means of advanced
comparing data upstream and downstream the chemical
injection point. corrosion monitoring systems.
Corrosion of vessel shell can bring to leakages or ruptures. Corrosion can be internal or external. External corrosion
can be easy and immediate to detect.
The inspection of the corrosion inhibitor system is Perform inspections of the corrosion inhibitor injection
mandatory to ensure high valus of the corrosion system to ensure appropriate working conditions and Corrosion inhibitor skid is properly working.
treatment availability. injection dosages.
Test of vessel integrity to avoid any leakage and
Z060-V-230 structure collapse
Adequate corrosion inhibitor availability shall be Ensure the fluid is properly treated with corrosion
guaranteed for the whole operating life. inhibitors for CO2 corrosion control. Corrosion inhibitor skid is properly working.
An earth ground connection of the exposed conductive parts of electrical equipment helps protect from
electric shock by keeping the exposed conductive surface of connected devices close to earth potential, Check earthing connection status Check the voltage between neutral and earth Voltage: 0 V
when a failure of electrical insulation occurs Frequency: Every one year
General maintenance of the vessel has to be performed to keep overall performance of the equipment within the Clean of the internals
Remove and clean the internals for further inspections
No assurance value is currently available for this
design parameters Frequency: Every 10 years or during Plant shutdown parameter
Check level alarms value on the instrument is at design Check level alarms values on the instrument to ensure
value Design value for LSLL-6224: Hold
Frequency: Every three months that design data is observed
Z060-V-230 Test of level switch integrity to avoid spurious signals To avoid oil flowing out in the water line, a level instrument is installed in order to trigger LSD action in case of low
Z060-LSLL-6224 triggering LSD action low level inside the Vessel. Clean the instrument externally Perform external cleaning of the instrument
No assurance value is currently available for this
Frequency: Every three months parameter
Visual inspection of level instrument Perform a visual inspection of the instrument and check
No leakages shall be detected
Frequency: Every three months for leakages
AVAILABILITY/RELIABILITY
Target Value
Availability 0.0022
Reliability 0.0022
SURVIVABILITY
N/A
The Preventive Maintenance procedure for the Z060-V-230 and its sub-equipment is available in the following Preventive Maintenance Task Lists (PMR):
• VX01M - Pressure Vessels;
• XT01I - Electric and Pneumatic Transmitters
• LS01I - Level Switch
System and/or equipment interacting with this ICE Reason for the dependency/interaction
The 3rd Stage Separator - Wet Train Z060-V-220 send oil/water mixture to the Desalter - Wet Train Z060-V-290 for water and salt removal , salt water is sent to drain header and
Desalter Z060-V-290 recycle water pump, while oil is sent to 4th stage separator to improve the oil-water separation, the vessel can be bypassed and send to 4th stage separtor Z060-V-230. The system will
continue to work, however the oil quality will degrade.
Performance Standard Checklist
Wet Train - 4th Stage Separator - Z060-V-230 - Every one year for External Inspection
Action Remarks Results
Inform the Control Room of beginning of the works and open the Permit
to Work
Close and check if the Permit to Work has been correctly signed
Wet Train - 4th Stage Separator - Z060-V-230 - Every five years or during Plant shutdown/turnaround for Internal Inspection
Action Remarks Results
Inform the Control Room of beginning of the works and open the Permit
to Work
Check vessel status for signs of rust, corrosion, oxidation and any
external damage
Open the manhole and ventilate the vessel and make sure is gas free
Open the manhole and ventilate the vessel and make sure is gas free
Enter into the vessel (external support to people entering the vessel is
mandatory)
Close manholes
Close and check if the Permit to Work has been correctly signed
Inform the Control Room of beginning of the works and open the Permit
to Work
Make sure the connection lines are not blocked and flush if required
Close and check if the Permit to Work has been correctly signed
Inform the Control Room of beginning of the works and open the Permit
to Work
Make sure the connection lines are not blocked and flush if required
Close and check if the Permit to Work has been correctly signed
Inform the Control Room of beginning of the works and open the Permit
to Work
Close and check if the Permit to Work has been correctly signed
Z060-V-600
GOAL
The air coming from the instrument air compressor & dryer unit(60-U-600 C/D) and (60-VH-600E/F) after that to instrument air receiver Z060-V-600 for hold-up before
distributing it to instrument air network , plant air network and pilot ignition burner panel
SCOPE
The following Performance Standard applies to the Zubair Field and more specifically to the Hammar DGS
FUNCTIONALITY
NDT inspection Perform NDT inspection to determine vessel thickness No mechanical design drawing is currently available
Corrosion of vessel shell can bring to leakages or ruptures. Corrosion can be internal or external. External corrosion Next Inspection: 2019 (shell & head) and determine corrosion level in the RBI
can be easy and immediate to detect. study
RBI Study in accordance to API 580 Perform RBI study, based on previous NDT inspections Expected design life of equipment: 20 years
Next Assessment: 2019 to determine corrosion rate and residual life of the
equipment
Test of vessel integrity to avoid any leakage and
Z060-V-600
structure collapse Check earthing connection status Check the voltage between neutral and earth Voltage: 0 V
An earth ground connection of the exposed conductive parts of electrical equipment helps protect from electric
shock by keeping the exposed conductive surface of connected devices close to earth potential, when a failure of Frequency: Every one year
electrical insulation occurs
Clean of the internals Remove and clean the internals for further inspections No assurance value is currently available for this parameter
Frequency: Every 5 years or during Plant shutdown
General maintenance of the vessel has to be performed to keep overall performance of the equipment within the
design parameters
AVAILABILITY/RELIABILITY
Target Value
Availability NA
Reliability NA
SURVIVABILITY
N/A
The Preventive Maintenance procedure for the Z060-V-600 and its sub-equipment is available in the following Preventive Maintenance Task Lists (PMR):
• VX01M - Pressure Vessels;
System and/or equipment interacting with this ICE Reason for the dependency/interaction
The vessel is the hold-up for the air network
Air Network
Z060-V-600
Inform the Control Room of beginning of the works and open the Permit
to Work
Close and check if the Permit to Work has been correctly signed
INSTRUMENT AIR RECEIVER - Z060-V-600 - Every five years or during Plant shutdown/turnaround for Internal Inspection
Inform the Control Room of beginning of the works and open the Permit
to Work
Check vessel status for signs of rust, corrosion, oxidation and any
external damage
Open the manhole and ventilate the vessel and make sure is gas free
Enter into the vessel (external support to people entering the vessel is
mandatory)
Close manholes
Close and check if the Permit to Work has been correctly signed