Professional Documents
Culture Documents
Aim
LEARNING OUTCOMES
Overview
This lesson provides students with an understanding of the working principle of the
Air Circuit Breaker and the protection incorporated in it for safe operation of
generators.
Air Circuit Breaker
151X
440 / 110 V RP
Under-
voltage coil
Trip
Contacts
N.O Latch
.
Push-
Button
Closing
Coil
Main
Contacts
Auxiliary
Contacts
Closing Push-
Button
440 / 110 V
Generator
Figure 1
Figure 1 shows an Air Circuit Breaker of the draw-out type found in main
switchboard of an a.c. system. It is used to connect the alternator safely onto the
bus bars as well as to disconnect it safely should a serious malfunction occur. It can
break a circuit in abnormal conditions - under-voltage, over-current, short-circuit,
reverse power- in an installation. It thus disconnect automatically a faulty circuit.
Principle of Operation
1. The main contacts are kept closed and latched against high spring force.
2. Quick acting tripping action is provided by release spring.
3. Cooling and splitting of arc is done by arc chutes. Arcing contacts close earlier
and open later than main contacts.
4. Closing coil is provided to close the circuit breaker. This coil operates on d.c.
power from rectifier and is energised by a closing relay operated by a push-
button.
5. The no-volt coil trips the circuit breaker when severe voltage drop (setting could
be 50% - 70% of rated voltage) occurs. It also prevents circuit breaker from
being closed when generator voltage is very low or absent.
6. This coil operates on d.c. power. A push-button switch for opening the circuit
breaker by de-energising the no-volt coil is used. Normally-open contacts are
used for de-energising the coil and trip the circuit breaker by electronic over-
current and reverse power relays.
The following switchboard protections are incorporated in the Air Circuit Breaker
shown in Figure 1:
a. Over-current
b. Reverse-power
c. Under-voltage release
In the event of low voltage (50 % to 70% of rated voltage), ACB trips because the
no-volt coil is de-energised to release the mechanical latch. See simplified diagram
of ACB in Figure 2.
Air Circuit
Breaker
Under-voltage
relay coil
Generator
Circuit
Breaker
Latch
Figure 2
Under-voltage trip also gives protection against loss of voltage while the machine is
connected to the switchboard.
In the event of reverse power, the fault is sensed by the reverse-power relay which
then closes the contact RP which is connected into the ACB circuit as shown in
Figure 1. This de-energised the no-volt coil to release the latch and trips the ACB.
Reverse power occurs when two (or more) generators are running in parallel. When
there is a loss of prime-mover power, the driven generator acts as a motor and
impose a heavy load on the remaining sets in parallel. To obviate overload trip in the
other generators, its ACB must be released.
To ACB Circuit
Laminated Iron Core
Contact
RP
connected to ACB
Voltage Coil
Spindle
Current Coil
Aluminium Disc
End View
Figure 3
The reverse power relay is similar in construction to the electricity supply meter.
The lightweight non-magnetic aluminum disc, mounted on a spindle which has low-
friction bearings is positioned in a gap between 2 electromagnets. The upper
electro-magnet has a voltage coil connected through a transformer between one
phase and an artificial neutral of the alternator output. The lower electromagnet has
a current coil also supplied from the same phase through a transformer.
Magnetic fields are produced by the voltage and current coils. Both fields pass
through the aluminum disc and cause eddy currents.
The effect of the eddy currents is that a torque is produced in the disc. With normal
power flow, trip contacts on the disc spindle are open and the disc bears against a
stop. When power reverses, the disc rotates in the other direction, away from the
stop and the contacts are closed so that the breaker trip circuit is energised.
Over-current Protection
The electronic over-current trip device operates on the current of the current
transformer mounted on the generator output conductors as shown in Figure 4.
In the event of over-current drawn from the generator, the fault is sensed by the
over-current relay which causes its contact 1TX to close and energise relay 151X.
When contact 151X , which is connected into the ACB circuit closes, the no-volt coil
is de-energised to release the latch and trips the ACB. See Figure 5.
Current Transformer
21 22
1TX
P1 P2
Over-Current
Device
Generator
Figure 4
24 V dc
21
1 TX
22
151 151X
PX
Figure 5
Inverse Definite Minimum Time (IDMT) Relay
To Trip Circuit
Aluminium Disc
Closed Winding
Figure 6
Accurate inverse time delay characteristics are provided by an induction type relay
with construction similar to that of a domestic wattmeter or reverse power relay.
Current in the main winding (see fig.) is obtained through a CT from the alternator
input to the switchboard. (The main winding is tapped and the taps brought out to a
plug bridge for selection of different settings.)
Alternating current in the main winding on the centre leg of the upper laminated iron
core produces a magnetic field that in turns induces current in the closed winding.
The magnetic field associated with the closed winding is displaced from the
magnetic field of the main winding and the effect on the aluminium disc is to produce
changing eddy currents in it. A tendency for the disc to rotate is prevented by a
helical restraining spring when normal current is flowing. Excessive current causes
rotation against the spring and a moving contact on the spindle comes in to bridge
after half a turn the two fixed contacts so that the tripping circuit is closed.
Speed of rotation of the disc through the half turn depends on the degree of over-
current. Resulting inverse time of characteristics are such as shown. In many
instances of over-current, the IDMT will not reach the tripping position as the excess
current will be cleared by other means,. The characteristic obtained by the relay is
one with a definite minimum time and this will not decrease regardless of the
amount of over-current. Minimum time, however can be adjusted by changing the
starting position of the disc.
Time in Seconds
Figure 7
Preferential
Definite Trip
Minimum
Time Overload of
an alternator
Over-current may be due
to increased
Relay Inverse Time Characteristics switchboard
load or to a
serious fault causing high current flow. Straight overload (apart from the brief
overload due to starting of motors) is reduced by the preferential trips which are
designed to shed non-essential switchboard load. Preferential trips are operated by
relays set at about 110% of normal full load. They open the breakers feeding
ventilation fans, air conditioning equipment, etc. The non-essential items are
disconnected at timed intervals, so reducing alternator load.
e.g.
This order of tripping varies from ship to ship. when sufficient non-essential load
has been disconnected, then the preference overload trip resets and no further load
is disconnected.
Main Switchboard
X
X X
15
10
5 Seconds
Essential
Services
G1 G2
1st Trip
Timing Relay 2nd Trip 3 rd Trip
Circuit Breaker
Trip Coil
Figure 8