The 530IOD01 is a module of the RTU530 product line
and provides:
Binary input unit
• up to 8 galvanic isolated binary process inputs with
a common return I01
I1
• up to 4 binary process outputs using relay contacts
I02
without a common return. I2
Micro- I03
The module allows: controller I3
I04
I4
Input register
RTU530 I/O bus
continious current. I6
I06
• 530IOD01 R0001
I08
I8
• 530IOD01 R1001 conformal coated IC
5 V DC R02
C02 Command monitoring functions:
CPU
Voltage monitoring CMD
R03
O03 • monitoring of the output bit patterns by reading
C03
UART V2
O04
back the output state
Output relay control
R04
C04 • switching voltage monitoring (24 V DC coil voltage)
before and during output
24VDC
• command output duration monitoring
Figure 2: Block diagram binary output unit The module provides a data buffer for temporally
The module 530IOD01 of the RTU530 product line can storing of up to 50 event messages including time
be used for the control of 4 binary process signals stamps. The events are stored in chronological order
using relay contacts. The allocation of an output signal designated for transmission to the communication
to the processing functions can be done according to unit (CMU).
the rules of configuration.
During initialization and operation the module carries
The module 530IOD01 is able to process the following out a number of tests. If a fault occurs it is reported
types of signals: to the communication unit. A failure of the module is
• Single or double commands (SCO or DCO) with 1 or detected and signalized by the communication unit.
2 pole output
• Regulation step command (RCO), 1 or 2 pole
• Bitstring output, 1 or 2 Bit (BSO1 or BSO2) Power supply input
The module allows switching voltages up to 72 V DC or The required power for the module is supplied via the
max. 5 A continious current. RTU530 I/O bus connector.
150 m/s², 11 ms
3 shocks per direction
IEC 60255-21-2 class 1
IEC 60870-2-2 class Bm
100 m/s², 16 ms
1000 shocks per direction
IEC 60255-21-2 class 1
Connection type Binary inputs - immunity and insulation tests
Process connector (X4) 1 x 17 pole 5.08 mm Insulation resistance, IEC > 50 MΩ @ 500 V DC
pluggable screw terminals 60255-27
(included in delivery), 0.2...
2.5 mm²/ AWG 24 - AWG 12
Connector from CMU/ADD 2 x 6 pin, male Binary output channels 530IOD01
or other I/O module (X2) Outputs 4 Relay contacts,
Connector to next I/O 2 x 6 pin, female single pole, normal open
module (X3) Coil voltage 24 V DC @ 10 mA
Max. switching voltage 72 V DC
Current consumption for power supplied via RTU530 Continuous current 5A
I/O bus Max breaking current 5 A ≤ 30 V DC
5 V DC max. 96 mA, typ. 72 mA (resistive load) 1 A @ 60 V DC
24 V DC max. 50 mA Max. breaking capacity 50 VA (L/R= 40 ms)
(inductive load)
AC dielectric voltage 2.5 kV, 50 Hz, 1 min
Binary input channels 530IOD01 R0001 test, IEC 60255-27, IEC
61000-4-16, IEC 60870-2-1
Inputs 8 channels, (class VW3)
1 common return for all Impulse voltage withstand 5 kV (1.2 / 50 µs)
channels, test of insulation, IEC
60255-27, IEC 60870-2-1
isolated by opto-couplers (class VW3)
Nominal input voltage 24... 60 V DC (+/- 20%) Insulation resistance, IEC > 50 MΩ @ 500 V DC
60255-27
Max. input voltage 72 V DC
Electrical fast transient / 4 kV (level 4), criterion A
Input current 1.2... 5 mA
Burst, IEC 61000-4-4
Logical ‘1’ definitely ≥ 18 V DC
Surge 1.2/50 µs, 4 kV (level 4)
detected
IEC 61000-4-5
Logical ‘0’ definitely ≤ 9 V DC
Conducted distur- 10 V (level 3), criterion A
detected
bances, induced by
Reverse voltage yes radio-frequency fields,
protection IEC 61000-4-6
Max. input frequency for 120 Hz Ring wave, IEC 61000-4-12 2.5 kV line to earth, 1
integrated totals kV line to line (level 3),
criterion A
Binary inputs - immunity and insulation tests Conducted, common 30 V continuous distur-
mode disturbances in the bance/ 300 V short
Electrical fast transient / 4 kV (level 4), criterion A
frequency range 0 Hz to duration disturbance
Burst, IEC 61000-4-4
150 kHz, IEC 61000-4-16 (level 4), criterion A
Surge 1.2/50 µs, 4 kV (level 4)
Damped oscillatory wave, 2.5 kV line to earth, 1
IEC 61000-4-5
IEC 61000-4-18 kV line to line (level 3),
Conducted distur- 10 V (level 3), criterion A criterion A
bances, induced by
radio-frequency fields,
IEC 61000-4-6
Ring wave, IEC 61000-4-12 2.5 kV line to earth, 1
kV line to line (level 3),
criterion A
Conducted, common 30 V continuous distur-
mode disturbances in the bance/ 300 V short
frequency range 0 Hz to duration disturbance
150 kHz, IEC 61000-4-16 (level 4), criterion A
Damped oscillatory wave, 2.5 line to earth, 1 kV line
IEC 61000-4-18 to line (level 3), criterion A
AC dielectric voltage 2.5 kV, 50 Hz, 1 min
test, IEC 60255-27, IEC
61000-4-16, IEC 60870-2-1
(class VW3)
Impulse voltage withstand 5 kV (1.2 / 50 µs)
test of insulation, IEC
60255-27, IEC 60870-2-1
(class VW3)
Signaling by LEDs
I1… I8 LED displays the active
inputs
O1… O4 LED displays the active
output relays
Ordering information
530IOD01 R0001 1KGT049600R0001
conformal coated
ABB Power Grids Germany AG We reserve the right to make technical We reserve all rights in this document and in ABB is a registered trademark of ABB
changes or modify the contents of the subject matter and illustrations contained Asea Brown Boveri Ltd. Manufactured
P.O. Box 10 01 64 this document without prior notice. therein. Any reproduction, disclosure to third by/for a Hitachi Power Grids company.
1KGT151127 V001 1
68128 Mannheim, Germany With regard to purchase orders, the parties or utilization of its contents – in whole
agreed particulars shall prevail. Hitachi or in parts – is forbidden without prior written
ABB Power Grids does not accept any consent of Hitachi ABB Power Grids.
responsibility whatsoever for potential © 2020 Hitachi Power Grids
errors or possible lack of information in All rights reserved
hitachiabb-powergrids.com/rtu this document.