2 Field examples
of combined VLF Withstand Testing,
Tan Delta (TD) and Partial Discharge (PD) Diagnostics
Paper # A 209
1950 2012
Difficulties:
• Water Tree Prone XLPE cable from early 1980’s
• Newer XLPE (1990-2012)
• Mixture of PILC with XLPE (e.g. after fault repair)
• Transition joints XLPE/PILC – 3phased cables
• Restrictions in cable section replacement (max. 100m)
Helping Details :
• Detailed cable records
• Understanding of characteristic of certain elements
• Understanding typical behavior pattern of elements
CMD 2012, 23.-27.09.2012 Bali 4 Neier – Gerstner – Jenny A209
2 Applied Diagnostic Technique TD and PD, VLF testing
Diagnostic approach:
1. Tan Delta measurement
• 0.5 Uo , 1.0 Uo, 1.5 Uo
• Information of water tree ageing condition, general cable condition
2. PD measurement
• Up to max. 1.7 Uo (phase to phase voltage)
Portable Systems
Viola TD PD
…42.5kVrms
Frida TD PD
… 24kVrms
CMD 2012, 23.-27.09.2012 Bali 11 Neier – Gerstner – Jenny A209
4 Case Study # 1 …1
Cable details:
11kV, 3core XLPE cable
9 heat shrink joints,
cable length 806m
TD Result 26.10.2011
TD
STD
TD Trend
TD analysis of L2
▼ 10.22
▼ 1.74
Δ 1.45
Clear indication of
Water Ingress in at
least one of the joints
PD will be affected in
the suspect joint(s)
Indication of
- Cable length 806m
- Impedance Changes at
Joints
Jt. #4 at 150m
Jt. #5 at 260m
(neg. imp. change
pattern)
=> Indication of
Joint with Water
Ingress
TD results improved
slightly
TD Result 17.10.2011
TD analysis of L2
Two stages:
1. Ramp-up
2. MWT (or hold)
Understand the
cable condition
during the VLF test.
PD portable
viola TD frida TD
VLF generator
Integrated tan delta TD measuring function
MWT – Monitored Withstand Test
CMD 2012, 23.-27.09.2012 Bali 27 Neier – Gerstner – Jenny A209
Networks are sensitive.
We help you to protect them.