Australian Standard

Part 10: Approval documentation


Automatic fire sprinkler systems
AS 2118.10—1995
This Australian Standard was prepared by Committee FP/4, Automatic Sprinkler
Installations. It was approved on behalf of the Council of Standards Australia on
6 March 1995 and published on 5 June 1995.

The following interests are represented on Committee FP/4:


Asset Services—Department of Administrative Services
Australian Building Codes Board
Australian Chamber of Commerce and Industry
Australian Chamber of Manufactures
Australian Fire Authorities Council
Australian Water and Sewerage Authorities
Commonwealth Fire Board
CSIRO—Division of Building, Construction and Engineering
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

Department of Defence
Fire Protection Industry Association of Australia
Institution of Engineers, Australia
Insurance Council of Australia
Master Plumbers and Mechanical Services Association of Victoria
Melbourne Water
New Zealand Fire Equipment Association
Telecom Australia
Testing Interests
The Association of Consulting Engineers, Australia

Review of Australian Standards. To keep abreast of progress in industry, Australian Standards are subject
to periodic review and are kept up to date by the issue of amendments or new editi ons as necessary. It is
important therefore that Standards users ensure that they are in possession of the latest editi on, and any
amendments thereto.
Full detail s of all Australian Standards and related publi cati ons wil l be found in the Standards Australi a
Catalogue of Publications; this information is supplemented each month by the magazine ‘The Australi an
Standard’, which subscribing members receive, and which gives detail s of new publications, new edit ions
and amendments, and of withdrawn Standards.
Suggesti ons for improvements to Australian Standards, addressed to the head off ice of Standards Australi a,
are welcomed. Notif ication of any inaccuracy or ambiguit y found in an Australi an Standard should be made
without delay in order that the matter may be investigated and appropriate action taken.

This standard was issued in draft form for comment as DR 92189.


AS 2118.10—1995

Australian Standard

Automatic fire sprinkler systems


Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

Part 10: Approval documentation

PUBLISHED BY STANDARDS AUSTRALIA


(STANDARDS ASSOCIATION OF AUSTRALIA)
1 THE CRESCENT, HOMEBUSH, NSW 2140
ISBN 0 7262 9743 7
AS 2118.10— 1995 2

PREFACE

This Standard was prepared by the Joint Standards Australia/Standards New Zealand
Committee on Automatic Sprinkler Installations FP/4 to supersede in part
AS 2118 —1982, SAA Code for Automatic Fire Sprinkler Systems.
This Standard is the result of a consensus among representatives on the joint committee to
produce it as an Australian Standard.
The revisions to AS 2118 have included Standards Australia’s requirements to keep
product and installation Standards separate. When complete the series will comprise:
AS
2118 Automatic fire sprinkler systems
Part 1: Standard
Part 2: Wall wetting sprinklers (Drenchers)
Part 3: Deluge
Part 4: Residential
Part 5: Domestic
Part 6: Combined sprinkler and hydrant
Part 9: Piping support and installation
Part 10: Approval documentation
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

4118 Fire sprinkler systems


Part 1.1: Components—Sprinklers and sprayers
Part 1.2: Components—Alarm valves (wet)
Part 1.3: Components—Water motor alarms
Part 1.4: Components—Valve monitors
Part 1.5: Components—Deluge and pre-action valves
Part 1.6: Components—Stop valves and non-return valves
Part 1.7: Components—Alarm valves (dry)
Part 1.8: Components—Pressure reducing valves
Part 1.9: Components—Accelerators and exhausters
Part 2.1: Piping — General
The terms ‘normative’ and ‘informative’ have been used in this Standard to define the
application of the appendix to which they apply. A ‘normative’ appendix is an integral
part of a Standard, whereas an ‘informative’ appendix is only for information and
guidance.

 Copyri ght STANDARDS AUSTRALIA


Users of Standards are reminded that copyright subsists in all Standards Austr alia publi cati ons and software. Except where the
Copyri ght Act all ows and except where provided for below no publications or soft ware produced by Standards Australi a may be
reproduced, stored in a retr ieval system in any form or transmitt ed by any means without prior permission in writ ing from
Standards Australi a. Permission may be condit ional on an appropri ate royalty payment. Requests for permission and information
on commercial software royalt ies should be directed to the head offi ce of Standards Austr alia.
Standards Austr alia wil l permit up to 10 percent of the technical content pages of a Standard to be copied for use
exclusively in-house by purchasers of the Standard without payment of a royalty or advice to Standards Austr alia.
Standards Austr alia wil l also permit the inclusion of its copyright materi al in computer software programs for no royalt y
payment provided such programs are used exclusively in-house by the creators of the programs.
Care should be taken to ensure that materi al used is from the current editi on of the Standard and that it is updated whenever the
Standard is amended or revised. The number and date of the Standard should therefore be clearly identif ied.
The use of materi al in print form or in computer software programs to be used commercially, with or without payment, or in
commercial contracts is subject to the payment of a royalty. This policy may be vari ed by Standards Austr alia at any ti me.
3 AS 2118.10— 1995

CONTENTS
Page

SECTION 1 SCOPE AND GENERAL


1.1 SCOPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. ... ......... 4
1.2 APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. ... ... .. ..... . 4
1.3 NEW DESIGNS AND INNOVATIONS . . . . . . . . . . .. .... ......... ... 4
1.4 REFERENCED AND RELATED DOCUMENTS . . . .. .. .. .. ... ....... 4
1.5 DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . .. .. .. .. ... .... 4

SECTION 2 REQUIREMENTS
2.1 STANDARD SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 WALL WETTING SPRINKLER (DRENCHER) SYSTEMS . . . . . . . . . . . . . 8

APPENDICES
A STANDARD SYSTEM COMPLETION CERTIFICATE . . . . . . . . . . . . . . . . 11
B WALL WETTING SPRINKLER (DRENCHER) SYSTEM
COMPLETION CERTIFICATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

Originated as part of AS CA16— 1939.


Previous editi on AS 2118— 1982.
Revised and redesignated in part as AS 2118.10— 1995.
AS 2118.10— 1995 4

STANDARDS AUSTRALIA

Australian Standard
Automatic fire sprinkler systems

Part 10: Approval documentation

S E C T I O N 1 S CO P E A N D G E NE R A L

1.1 SCOPE This Standard specifies requirements for the information to be provided
for the approval of standard fire sprinkler systems in accordance with AS 2118.1 and
automatic wall wetting sprinkler (Drencher) systems in accordance with AS 2118.2.

1.2 APPLICATION This Standard is intended for use by the specifiers, designers and
installers of fire sprinkler and wall wetting sprinkler (Drencher) systems.

1.3 NEW DESIGNS AND INNOVATIONS Any alternative materials, designs,


methods of assembly, and procedures, that do not comply with specific requirements of
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

this Standard, or are not mentioned in it, but that give equivalent results to those specified
are not necessarily prohibited. Advice on such matters can be sought from Standards
Australia, but the specified approval remains the prerogative of the regulatory authority.

1.4 REFERENCED AND RELATED DOCUMENTS The following documents are


referred to in this Standard:
AS
2118 Automatic fire sprinkler systems
2118.1 Part 1: Standard
2118.2 Part 2: Wall wetting sprinkler (Drencher)

2484 Fire—Glossary of Terms


2484.1 Part 1: Fire tests
2484.2 Part 2: Fire protection and firefighting equipment
3500 National Plumbing and Drainage Code
3500.0 Part 0: Glossary of Terms
2941 Fixed fire protection installations—Pumpset systems

1.5 DEFINITIONS For the purpose of this Standard, the definitions given in
AS 2484.1, AS 2484.2, AS 3500.0, AS 2118.1, AS 2118.2, and that below, apply.
1.5.1 Regulatory authority—a Minister of the Crown, a government department, or
other public authority having power to issue regulations, orders, or other instructions in
respect of any subject covered by this Standard.

COPYRIGHT
5 AS 2118.10— 1995

S E C T I O N 2 R E Q UI R E M E N T S

2.1 STANDARD SYSTEMS


2.1.1 At the preliminary stage A general specification of the proposed protection
including water supplies shall be provided to the regulatory authority. The specification
shall include a block plan of the premises showing—
(a) the class or classes of system to be installed according to the hazard class in the
various buildings or sections of the buildings;
(b) the extent of the sprinkler protection;
(c) the construction and occupancy of each building; and
(d) a cross-section of the full height of each building indicating the height of the
highest sprinkler with respect to a stated datum level.
2.1.2 Prior to commencing installation
2.1.2.1 General Prior to commencing installation, the necessary approvals shall be
obtained from the appropriate regulatory authority empowered to approve the installation
of the standard sprinkler system (the installation approving authority) and from the local
water supply authority.
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

2.1.2.2 Detailed requirements Detailed working drawings and all relevant


documentation of the protection, giving the information listed below, shall be provided to
the installation approving authority.
The drawings shall be on an indicated scale not less than 1:100 (in exceptional cases a
scale of 1:200 may be accepted). They shall include the following information:
(a) Name of occupier and owner.
(b) Address and location of premises.
(c) Point of compass (north point).
(d) A key to all symbols used.
(e) The class or classes of system according to hazard class.
(f) Occupancy of each building.
(g) Constructional details of ceilings and roofs and exterior walls and walls separating
sprinklered and non-sprinklered areas.
(h) Sectional elevations of each floor of each building indicating the distance of
sprinklers from ceilings and structural features which affect the sprinkler layout or
distribution from the sprinklers.
(j) Location and size of concealed roof or ceiling spaces, offices and other enclosures
ceiled at a level lower than the roof or ceiling. All unprotected areas such as
stairways, voids (lower levels of lift shafts) and toilets shall be indicated on each
applicable drawing.
(k) Location of trunking, stagings, platforms and other equipment such as machinery,
fluorescent light fittings and heaters, which may adversely affect the sprinkler
distribution.
(l) Type and temperature rating of each sprinkler.
(m) Location and details of any water flow alarm switches or electric alarm pressure
switches.
(n) The type of system, location of each control assembly and water motor alarm.

COPYRIGHT
AS 2118.10— 1995 6

(o) Location and size of any tail-end air valves, subsidiary stop valves (where
permitted) and drain valves.
(p) For installations erected on the dry or alternate wet and dry systems, the direction of
the drainage slope of the piping.
(q) The details of the location and specification of any orifice plate.
(r) Information relative to the mode of calculation to be used as follows:
(i) Partially pre-calculated systems For partially pre-calculated systems the
following shall be provided:
(A) Identification reference letters for the design points of each array on
the floor concerned, from which the distribution piping back to the
control assemblies is to be calculated hydraulically.
(B) A summary of the pressure loss calculations for the distribution piping,
at the rate of flow for the respective hazard class, set out on a form
similar to Figure 2.1.
(C) For light and ordinary hazard systems, the total pressure loss from each
design point to the control assembly shall be related to the maximum
pressure loss allowed, ignoring static head loss. Any permitted increase
in these losses due to the difference in static pressure between the level
of the sprinkler in the top storey shall be shown as x in Column 7 of
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

Figure 2.1.
(D) For high hazard systems using the piping arrangements of
Tables 11.4.2.2(A) to 11.4.2.2(C) in AS 2118.1, the total pressure loss
in the various runs of distribution piping between each design point
and the control assembly shall be related to the residual pressure
available from the water supply when tested under the appropriate flow
rate. The pressure required at the design point and the static head loss
due to the height of the highest sprinkler, in the particular array, above
the control assembly shall be included in these calculations.
(ii) Fully hydraulically calculated systems Fully detailed and dimensioned
working drawings shall be provided. All drawings shall include the following
information:
(A) A node or pipe reference scheme which provides unique identification
of pipes, junctions, sprinkler heads and any pipe fittings which require
hydraulic consideration.
(B) The position of the hydraulically most unfavourable assumed area of
operation.
(C) The position of the hydraulically most favourable assumed area of
operation. Not required for unboosted town main water supply.
(D) Two or four sprinklers upon which the average density of discharge is
based.
(E) The height of each identified pressure value above datum.
Where required, a line diagram(s) shall be supplied and include the following
information:
(1) Node or pipe reference numbers.
(2) Distribution pipes under consideration.
(3) Range pipes under consideration.
(4) Sprinkler heads under consideration.

COPYRIGHT
7 AS 2118.10— 1995

(5) Identification of the four hydraulically most unfavourable sprinkler


heads.
(6) Flow through each pipe section and sprinkler head.
(7) Pressures at each end of each pipe section and at the entry to each
sprinkler assumed to be operating.
(s) A schedule listing the number of sprinklers, medium and high velocity sprayers and
the area of protection.
(t) A summary schedule which states—
(i) the total area served by each control assembly;
(ii) the height of the highest sprinkler served by each control assembly; and
(iii) the type of system, i.e. wet, dry or alternate wet and dry system, and the size
of main stop valves.
(u) Independent accredited certifier’s endorsement.
(v) An undertaking that the water supplies comply with, and that the system has been
designed and will be installed in accordance with, AS 2118.1.
(w) A detailed drawing of water supplies and piping from these to the control assembly,
indicating the position and type of stop and back-pressure valves and pressure-
reducing valves, water meters, water locks and orifice plates, and any connection
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

other than those for sprinklers.


Where the water supplies include a water main, the nominal diameter is to be given
and also the relevant pressure and flow characteristics and whether the main is
dead-end or circulating; if dead-end, details are required of the nearest circulating
main.
Where a compression-ignition engine drive pump is installed it shall be confirmed
that the engine is capable of operating continuously on full load at the site elevation
for a period of 6 h and that the conditions governing the heating and ventilation of
the engine room specified in AS 2118.1 are complied with.
Where automatic pumps form one or both of the supplies, pump characteristic
curves shall be provided showing the estimated performance of the pumps under
installed conditions.
2.1.2.3 To water supply authority Details of all water supplies upstream of the alarm
valve, including pumps and tanks, shall be submitted for approval to the water supply
authority.
2.1.3 On completion of installation When the installation has been completed and
final tests have been carried out, the installer shall provide the installation approving
authority with a certificate indicating that the work has been completed and the necessary
tests of the water supplies have been carried out in accordance with AS 2118.1.
NOTE: The form of completion certification to be used is shown in Appendix A.
2.1.4 Compliance requirements When the installation has been completed and
acceptance tests have been carried out in accordance with Clause 2.1.3, the installer shall
provide the building owner with a certificate from an independent authorized inspector
certifying that the work has been completed in accordance with this Standard and the
relevant regulatory authorities.

COPYRIGHT
AS 2118.10— 1995 8

2.2 WALL WETTING SPRINKLER (DRENCHER) SYSTEMS


2.2.1 At the preliminary stage A general specification of the proposed protection
including water supplies shall be provided to the regulatory authority. The specification
shall include a block plan of the premises showing—
(a) the extent of the protection;
(b) the elevation of all protected faces indicating the height of the highest wall wetting
sprinkler with respect to a stated datum level; and
(c) full details of exposure hazard required for calculation.
2.2.2 Prior to commencing erection
2.2.2.1 General Prior to commencing erection, the necessary approvals shall be
obtained from the regulatory authority empowered to approve the installation of a wall
wetting sprinkler system, and the water supply authority.
2.2.2.2 Detailed requirements Complete detailed working drawings and all other
relevant documentation for the protection, giving the data listed below and other
information set out in this Section, shall be provided to the installation approving
authority.
The drawings shall be on an indicated scale not less than 1:100 (in exceptional cases a
scale of 1:200 may be accepted). They shall include the following information:
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

(a) Name of occupier and owner.


(b) Address and location of premises.
(c) Point of compass (north point).
(d) A key to all symbols used.
(e) Construction details of all relevant portions of exterior walls of the faces to be
protected.
(f) Type and temperature rating of drenchers to be installed.
(g) Location and type of main control valves and position of alarm motor and gong.
(h) For installations erected on the dry or alternate wet and dry systems, the direction of
the drainage slope of the pipework.
(i) The details of the test facility.
(j) Identification reference letters for the design points at each array on the system,
from which the distribution piping back to the control valves is to be calculated
hydraulically.
(k) A summary of the pressure loss calculations for the piping.
(l) A schedule of the number and type of wall wetting sprinklers.
(m) A summary schedule which states—
(i) the total number of wall wetting sprinklers in each installation;
(ii) height of the highest wall wetting sprinklers in each installation; and
(iii) type of installation, i.e. wet, dry, or alternate wet and dry system, and size of
main stop valves.
(n) An undertaking that the water supplies comply with, and the system has been
designed and will be installed in accordance with, this Standard.
(o) A detailed drawing of the water supplies and piping from these up to the installation
control valves and indicating the position and type of stop and non-return valves.

COPYRIGHT
9 AS 2118.10— 1995

Where the water supplies include a town main, the nominal diameter shall be given
and also the relevant pressure/flow characteristics and whether the main is dead-end
or circulating; if dead-end, details shall be given of the nearest circulating main.
Where a compression-ignition engine driven pump is installed, it shall be confirmed
that the engine is capable of operating continuously on full load at the site elevation
for a period of 6 h and that the conditions governing the heating and ventilation of
the engine room laid down in AS 2941 are complied with.
Where automatic pumps form one or both of the supplies, a pump characteristic
curve(s) shall be provided showing the estimated performance of each pump under
installed conditions.
2.2.2.3 To water supply authority Details of all water supplies up to the alarm valve,
including pumps and tanks, shall be submitted for approval to the water supply authority.
2.2.3 On completion of installation When the installation has been completed and
final tests have been carried out, the installer shall provide the installation approving
authority with a certificate indicating that the work has been completed and the necessary
tests of the water supplies have been carried out in accordance with AS 2118.1.
NOTE: The form of completion certificate to be used is shown in Appendix B.
2.2.4 Compliance requirements When the installation has been completed and
acceptance tests have been carried out in accordance with Clause 2.2.3, the installer shall
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

provide the building owner with a certificate from an independent authorized inspector
certifying that the work has been completed in accordance with this Standard and the
relevant regulatory authorities.

COPYRIGHT
AS 2118.10— 1995 10

HA ZAR D GROU P: Ordinary Hazard—Design Flow Rate: 1800 L/min


NA ME AND ADDR ES S: A.B. Company, See Lane, Ending

1 2 3 4 5 6 7 8
Total
Distribution pipe from Equiv. pipe Total equiv. Pressure loss
Pipe Pipe Number pressure loss
valves to design point length of length of per metre of
size length of turns at design flow
(letter) turns pipe pipe
rate*
mm m m m kPa/m kPa
A—Floor 3 65 3.5 — — 3.5 10.3 36.05
80 7 — — 7 4.7 32.9
100 49 2 6 55 1.3 71.5
Total 140.45
× = 0
Diff= 140.45
B—Floor 3 65 7 — — 7 10.3 72.1
80 1.9 — — 1.9 4.7 8.93
100 20 1 3 23 1.3 29.90
Total 110.93
× = 0
Diff= 110.93
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

C—Floor 2 65 4.1 — — 4.1 10.3 42.23


80 16.9 — — 16.9 4.7 79.43
100 28.3 2 6 34.3 1.3 44.59
Total 166.25
× = 38
Diff= 128.73
D—Floor 2 65 8.8 — — 8.8 10.3 90.64
80 10 — — 10 4.7 47
100 16.3 1 3 19.3 1.3 25.09
Total 162.73
× = 38
Diff= 124.73
E—Floor 1 65 10.5 — — 10.5 10.3 108.15
80 12.8 2 6 12.8 4.7 60.16
100 2.5 — — 2.5 1.3 3.25
Total 171.56
× = 76
Diff= 95.56
F—Floor 1 65 8.9 — — 8.9 10.3 91.67
80 9.9 1 3 12.9 4.7 60.63
100 2.5 — — 2.5 1.3 3.25
Total 155.55
× = 76
Diff= 79.55

* Including pressure losses across any orifice plates (high hazard systems only).

NO TE: In all sections the pressure loss in the distribution pipe is less than 150 kPa.

FIGURE 2.1 TYPICAL STATEMENT OF DISTRIBUTION PIPE LOSSES


BETWEEN THE VARIOUS DESIGN POINTS AND THE CONTROL ASSEMBLY
(FOR PARTLY PRE-CALCULATED SYSTEMS ONLY)

COPYRIGHT
11 AS 2118.10— 1995

APPENDIX A
STANDARD SYSTEM COMPLETION CERTIFICATE
(Informative)

We (name of installer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
of . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
hereby certify that we have completed on (date) . . . . . . . . . . . . . . . . . . . . . . . . . .
a (name of system) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
automatic sprinkler installation/s extension/s designed and erected in accordance
with AS 2118, Automatic fire sprinkler systems, Part 1: Standard
Name of client . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Address of protected premises . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Premises known as, or occupied by . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type of system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

Buildings Number of Total† Highest


Hazard Installation
or areas heads heads on head
class* No.
protected installed installation m

* The hazard class will normally have been determined by the owner in consultation with
the authority having jurisdiction before the installation is designed.
† Excluding those in concealed spaces.

The maximum number of sprinklers in any one separate risk is . . . . . . . . . . . . . . .

Building . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation No. . . . . . . . . . . . . . . . . High piled storage (type, height, location and

design density of discharge) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Direct brigade alarm is/is not connected to . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fire brigade station. Date of connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Portions of building(s) not protected and not requiring protection under the Code . .

Variations of the Code previously agreed to . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Date of placing sprinklers in full commission . . . . . . . . . . . . . . . . . . . . . . . . . . . .

COPYRIGHT
AS 2118.10— 1995 12

WATER SUPPLIES

The following water supplies have been provided:

Town main (1)*: Diameter . . . . . . . mm Supply pipe diameter . . . . . mm


Town main (2)*: Diameter . . . . . . . mm Supply pipe diameter . . . . . mm
Elevated private
reservoir*: Construction . . . . . . . . . . Capacity . . . . . . . . . . . . . . litres
Gravity tank*: Construction . . . . . . . . . . Capacity . . . . . . . . . . . . . . litres
Suction tank*: Construction . . . . . . . . . . Capacity . . . . . . . . . . . . . . litres

* These supplies have been tested in accordance with the procedures laid down in Clause 4.14 of
AS 2118.1 Standard, and at the date of test met/did not meet the minimum requirements for
particular hazard classes. Particulars are set out in the attached Data Sheet.

Rate of replenishment by town main . . . . . . . . L/min

Pumps † 1 2 3
Motive power ............. .............. ..............
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

Nominal rating
litres/min ............. .............. ..............
kPa ............. .............. ..............
Drawing water
from
Pressure tanks†
Total capacity . . . . . . . . . . . . . litres Ratio: Air-to-water . . . . . . . . . . . . . .
Required air pressure . . . . . (taking into account any losses referred to below):

† The pressure loss under the flow conditions for the respective hazard class in the pipework and
fittings, back pressure valves and alarm valves, between the pump or pressure tank and the
various installation pressure gauges, are calculated to be as follows:

Pressure loss Flow rate


Installation No.
kPa L/min

Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .. . .. . .. . .. .. . .. . .. .. . .. . .. .. . .. . .. .. .. ... .. .. .. . .. . .. .. . .. ..
. .. . .. . .. . .. .. . .. . .. .. . .. . .. .. . .. . .. .. .. ... .. .. .. . .. . .. .. . .. ..

(Signature): . . . . . . . . . . . . . . . . . . . . . . . .

(Date): . . . . . . . . . . . . . . . . . . . . . . . . . . . .

COPYRIGHT
13 AS 2118.10— 1995

WATER SUPPLIES TEST DATA SHEET


Accompanying CO MP LETION CER TIFICA TE in respect of sprinkler systems completed on:

Name of Client: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Address of protected premises: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Test apparatus (type, size): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Test Pump Highest Static


Test Requirements
results Cut-in head Loss*
Inst Water at .................
(kPa) (kPa) (m) (kPa)
No. Supply
Hazard Flow Pressure
A B C D E
Class (L/m) (kPa)
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

Alarm times — Diesel Alarm times— Electric Alarm times (if required)

Inst 15 mm Test Remote Test 15 mm Test Remove Test 15 mm Test Remote Test
No. Valve (sec) Valve (sec) Valve (sec) Valve (sec) Valve (sec) Valve (sec)
Gong DB A Gong DB A Gong DB A Gong DB A Gong DB A Gong DB A

Remarks:
........... ... .. .... ........ .... .. ... ............ .. .. .. ............. ... ... ..
........... ... .. .... ........ .... .. ... ............ .. .. .. ............. ... ... ..
........... ... .. .... ........ .... .. ... ............ .. .. .. ............. ... ... ..
A is measured at the installation gauge; D diesel pump;
B is measured at the pump discharge gauge; E electric pump.
C is measured at the pump suction gauge;
* Where an installation comprises more than one hazard class, the loss to be stated shall be that
between the installation gauge and the highest sprinkler in the particular hazard class or, where
advantage is taken of the static pressure gain, it shall be the height of the sprinkler used for the
purpose of sizing the distribution pipework for the particular installation.

Completed by: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Date: ........... ... .. .... ........ .... .. ..

COPYRIGHT
AS 2118.10— 1995 14

APPENDIX B
WALL WETTING SPRINKLER (DRENCHER) SYSTEM
COMPLETION CERTIFICATE
(Informative)

We (Name of installer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
of . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
hereby certify that we have completed on (date) . . . . . . . . . . . . . . . . . . . . . . . . . .
a (name of system) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
wall wetting sprinkler installation/s extension/s designed and erected in accordance
with AS 2118.2 wall wetting sprinkler (Drencher).
Name of client . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Address of protected premises . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Premises known as, or occupied by . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type of system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

Number of Highest
Buildings Installation
sprinklers sprinklers
protected No.
installed m

The maximum number of wall wetting sprinklers assumed to be operating


simultaneously . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Direct brigade alarm is/is not connected to . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fire Brigade Station. Date of connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Variations of the Code previously agreed to . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Date of placing sprinklers in full commission . . . . . . . . . . . . . . . . . . . . . . . . . . . .

COPYRIGHT
15 AS 2118.10— 1995

WATER SUPPLIES

The following water supplies have been provided:

Town main (1)*: Diameter . . . . . . . mm Supply pipe diameter . . . . . mm


Town main (2)*: Diameter . . . . . . . mm Supply pipe diameter . . . . . mm
Elevated private
reservoir*: Construction . . . . . . . . . . Capacity . . . . . . . . . . . . . . litres

Gravity tank*: Construction . . . . . . . . . . Capacity . . . . . . . . . . . . . . litres


Suction tank*: Construction . . . . . . . . . . Capacity . . . . . . . . . . . . . . litres

Rate of replenishment by town main . . . . . . . . L/min

* These supplies have been tested to verify the flow and pressure requirements in AS 2118.2, Wall
wetting sprinklers (Drenchers), and at the date of test met/did not meet the minimum requirements
for particular hazard classes. Particulars are set out in the attached Data Sheet.

Pumps † 1 2 3
Motive power .............. .............. ..............
Nominal rating
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

litres/min .............. .............. ..............


kPa .............. .............. ..............
Drawing water
from .............. .............. ..............
† The pressure loss at the design system flow in the piping and fittings, non-return valves and
control valves, between the pump(s) and the installation pressure gauge, are calculated to be as
follows:

Pressure loss Flow rate


Installation No.
kPa L/min

Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .. . .. . .. . .. .. . .. . .. .. . .. . .. .. . .. . .. .. .. ... .. .. .. . .. . .. .. . .. ..
. .. . .. . .. . .. .. . .. . .. .. . .. . .. .. . .. . .. .. .. ... .. .. .. . .. . .. .. . .. ..

(Signature): . . . . . . . . . . . . . . . . . . . . . . . .

(Date): . . . . . . . . . . . . . . . . . . . . . . . . . . . .

COPYRIGHT
AS 2118.10— 1995 16

WATER SUPPLIES TEST DATA SHEET


Accompanying CO MP LETION CER TIFICA TE in respect of sprinkler systems completed on:

Name of Client: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Address of protected premises: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Test apparatus (type, size): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Test Pump Highest Static


Test Requirements
results Cut-in head Loss*
Inst Water at .................
(kPa) (kPa) (m) (kPa)
No. Supply
Hazard Flow Pressure
A B C D E
Class (L/m) (kPa)
Licensed to LUU MINH LUAN on 25 Feb 2002. Single user licence only. Storage, distribution or use on network prohibited.

Alarm times — Diesel Alarm times— Electric Alarm times (if required)

Inst 15 mm Test Remote Test 15 mm Test Remove Test 15 mm Test Remote Test
No. Valve (sec) Valve (sec) Valve (sec) Valve (sec) Valve (sec) Valve (sec)
Gong DB A Gong DB A Gong DB A Gong DB A Gong DB A Gong DB A

Remarks:
........... ... .. .... ........ .... .. ... ............ .. .. .. ............. ... ... ..
........... ... .. .... ........ .... .. ... ............ .. .. .. ............. ... ... ..
........... ... .. .... ........ .... .. ... ............ .. .. .. ............. ... ... ..
A is measured at the installation gauge; D diesel pump;
B is measured at the pump discharge gauge; E electric pump.
C is measured at the pump suction gauge;
* Where an installation comprises more than one hazard class the loss to be stated shall be that
between the installation gauge and the highest sprinkler in the particular hazard class or, where
advantage is taken of the static pressure gain, it shall be the height of the sprinkler used for the
purpose of sizing the distribution pipework for the particular installation.

Completed by: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Date: ........... ... .. .... ........ .... .. ..