1
MC-HJ08/HJ09/3000F/4000F
Comprehensive technical indicators of special frequency converters
1. Input and output characteristics
Input voltage range: 220V±20%
Output voltage range: 0 ~ rated input voltage
Output frequency range: 0~100HZ
2. Peripheral interface characteristics
16 isolated external signal digital inputs: X0-X9. FWD, REV
Incremental encoder interface: input AB pulse frequency up to 100KHZ
Absolute encoder communication interface: 485 communication mode, baud rate 19200bps
Relay output: 2-way multi-function relay signal output
3. Technical performance characteristics
Control method: SVPWM
Overload capacity: 150% rated current 60s; 180% rated current 10s
Starting torque: 1.0Hz/150%
Carrier frequency: 1.0K-10.0 KHZ
V/F curve: V/F curve can be set arbitrarily
Acceleration and deceleration control: 16 segments of acceleration and deceleration time can be
selected arbitrarily
4. Protection features
Automatic shutdown when running overtime
The encoder is disconnected, and it will automatically stop if it is damaged.
Absolute encoder communication error, automatic protection over time
Overcurrent, overvoltage, undervoltage, overtemperature, phase loss, overload and other
protection functions
5. Support the automatic memory function of inverter usage time and door opening times
6. Support Chinese LCD panel
Real-time display of door status
Real-time display of current operating frequency
MC-HJ08-075-KSM
MC: Special for high-speed doors
HJ08: Power level
075: Hardware version HJ08 : 220V series; HJ09 : 380V series
KSM: Manufacturer code
1
1. 1.2 MC3000F-KSM plastic case (HJ08 bare metal) 220V selection standard specifications
220V Input series model specifications
MC3000F Plastic case model MC3000F-075KSM MC3000F-150KSM MC3000F-220KSM
MC-HJ08 Bare metal model MC-HJ08-075KSM MC-HJ08-150KSM MC-HJ08-220KSM
MC-HJ04 Bare metal model MC-HJ04-075KSM MC-HJ04-150KSM MC-HJ04-220KSM
Rated input voltage, frequency 1 Phase 220V(I60-260V), 50Hz/60Hz
Adapted motor power(kW) 0.75 1.5 2.2
Rated output current(A) 4.5 8.5 10.5
Maximum output frequency(Hz) 0. 0—80. 0
1. 1.3 MC4000F-KSM Plastic case (HJ09 bare metal) 380V type selection standard
specifications
380VInput series model specifications
2
1.2 Inverter installation size
120 mm ―
a、MC-3000F/4000FAppearance, Dimensions:
——130 mm ——
3
MC-HJ04Bare metal appearance,
dimension drawing:
Units: mm
d、Encoder appearance
Single-turn absolute value
magnetic encoder A - no battery
Communication Protocol
Mode: 02(or 03)
M02 series: M02-12A M02-05A
M03 series: M03-12A M03-05A
4
B. Wiring of frequency converter
2.1 Basic running wiring connection
MC3000F-HJ08 Basic configuration diagram of 220V special converter for fast door:
5
外接保护器 External protector
单相 220V 输入 Single phase 220V input
下超程/编码器清零 Lower overrange/encoder clearing
X1 下降行程开关 X1 drop stroke switch
X2 上升行程开关 X2 upstroke switch
X3 急停信号 X3 emergency stop signal
X4 手动/自动切换 X4 Manual/Automatic switchover
X5 雷达/地磁信号 X5 radar/geomagnetic signal
X6 光电/气囊信号 X6 photoelectric/airbag signal
X7 上超程 Super cheng x7
X8 互锁信号/第二雷达 X8 interlocking signal/second radar
X9 第二上行信号 X9 second uplink signal
REV/下行 REV/downward
FWD/上行 FWD/upward
外部输入公共端 External input common terminal
增量式编码器 Incremental type encoder
三相感应马达 Three-phase induction motor
机壳接地 Chassis ground
可编程继电器 1(联锁信号) Programmable relay 1 (interlocking signal)
可编程继电器 2(风联机信号) Programmable relay 2 (wind on-line signal)
MC 单圈绝对值磁编码器 MC single-turn absolute value magnetic encoder
MC 多圈绝对值磁编码器 MC multi-turn absolute value magnetic encoder
主电源 220V 输入端 Main power 220V input
三相马达连接端 Three-way motor connection
电机抱闸控制端子 Motor brake control terminal
多门互锁接线示意图 Wiring diagram of multi-door interlock
6
MC4000F/HJ09 Quick door 380V frequency converter is used to check this diagram:
7
Note: Input terminals X1, X2 and X3 are normally closed inputs by default, and others are
normally open inputs by default.
8
MC-HJ04 Basic configuration diagram of 220V special converter for fast door:
9
外接保护器 External protector
单相 220V 输入 Single phase 220V input
X1 下降行程开关 X1 drop stroke switch
X2 上升行程开关 X2 upstroke switch
X3 急停信号 X3 emergency stop signal
X4 手动/自动切换 X4 Manual/Automatic switchover
X5 雷达/地磁信号 X5 radar/geomagnetic signal
X6 光电/气囊信号 X6 photoelectric/airbag signal
X7 上超程 Super cheng x7
X8 互锁信号/第二雷达 X8 interlocking signal/second radar
REV/下行 REV/downward
FWD/上行 FWD/upward
外部输入公共端 External input common terminal
增量式编码器 Incremental type encoder
三相感应马达 Three-phase induction motor
机壳接地 Chassis ground
可编程继电器 1(联锁信号) Programmable relay 1 (interlocking signal)
MC 单圈绝对值磁编码器 MC single-turn absolute value magnetic encoder
MC 多圈绝对值磁编码器 MC multi-turn absolute value magnetic encoder
主电源 220V 输入端 Main power 220V input
三相马达连接端 Three-way motor connection
电机抱闸控制端子 Motor brake control terminal
多门互锁接线示意图 Wiring diagram of multi-door interlock
10
2.2 Connection of main circuit terminals
Lower limit
upper limit
emergency stop
Automatic by hand
radar 1
photoelectric
signal
overtravel
Radar 2, interlock
down
up
MC multi-turn absolute
value magnetic encoder
Incremental encoder
MC single-turn absolute
magnetic encoder
11
Table 2-2 Input control terminal terminal function description
12
REV Down button
Power/Incre X24V
External power supply 24V or 12V
mental Maximum output current: 0.4A
Encoder (X12V) optional
13
Table 2-3 Function description of CN5 terminal
category Terminal number Terminal function Specification
description
Multi-function CM1、 N01、 NC1 Programmable relay 1, CM1/CM2-NC1/NC2:Normally closed
relay output which can be set as fault CM1/CM2-NO1/NO2:Normally open
terminal alarm, interlock signal, Contact rating:
air curtain machine
NO: 250VAC/5A
signal, etc.
NC: 250VAC/3A; 30VDC/3A
Programmable relay 2,
CM2、 M02、 NC2
which can be set to fault
alarm, interlock signal,
air curtain machine
signal, etc.
14
Please refer to Table 3-1 for the function description of each serial number of the operation panel
Table 3-1 Operation panel function description
15
When Cr029 is set to 1, the function of this button is
Manual/Auto
11 equivalent to the function of X4 manual automatic
Mode Switch
transfer switch
16
Rise acceleration Note: All the acceleration and 0.0-99. 99 S
Cr005 time deceleration time refers to the time from 0.5 秒
0 to the highest frequency (default
50Hz), and the actual acceleration and
Rise and
Cr006 deceleration time deceleration time should be converted 0.0-99. 99 S 0.3 秒
accordingly.
Fall acceleration
Cr007 time 0.0-99. 99 S 0.5 秒
Fall deceleration
Cr008 time 0.0-99. 99 S 0.3 秒
17
The total gate height corresponds to the number of encoder
pulses
Cr015 / 5000
From the lowest limit to the highest limit of the
corresponding encoder pulse value.
Cr017 0-100% 50
Note: When Cr019 is set to 1 and X4 is valid, the frequency
converter will slow down and stop when the number of
encoder pulses is greater than this value.
Cr018 0-100% 95
Description: When the encoder pulse number is greater than
this value, the frequency converter decelerates and stops
Cr020 spare
18
illustrate:
Cr021 Relay 1 function 0: Fault alarm output
definition
13: Pr040 output after reaching the lower
limit reward delay
14: Automatic state: Interlock valid
Manual state: Interlock invalid
15: Interlock signal output/to the lower
limit position
Interlock is valid in manual/automatic
state
16: Wind curtain machine signal / 15
output/leave the lower limit position
17: to the upper limit position
Relay 2 function
Cr022 18: Leave the upper limit position / 16
definition
19: During the ascent
20: During the descent
Cr024 How long is the delay to start the relay output (when Cr021 0-9999S 0
and Cr022 are set to 13)
19
Description: In encoder mode, if this parameter is set to 0, it
will detect whether the encoder has a signal during the
running process. If there is no signal after 3S, it will alarm
and display “Er 013”: when it is set to 1, there is no such
function.
Cr028 Description: 0: Up and down keys on the panel are invalid 0-1 0
1: The up and down buttons on the panel and the
external terminal can be activated
20
Parameter lock, 0: parameter can be modified;
Cr038 0-1 0
1: parameter cannot be modified
Cr039 0-1 0
X9 function selection: 0: the second door opening function
(the door cannot be opened during the descending process)
1: One-key door opening and closing function
Incremental encoder power-down configuration (cannot be
Cr040 **** ****
modified by the user)
Set the number of lower four digits for opening the door, the
Cr046 0 -9999 0
maximum number of times is 9999;
Set the high four digits of the opening times, ten thousand
Cr047 0—9999 0
times:
Cr048 X9 The options of the second uplink button are as follows : 0-1 0
0: The second uplink button is invalid during the bottom of
the door.
1: The second uplink button is valid during the bottom of
the door
Whether the photoelectric signal landing is valid; 0: landing
Cr049 0-1 0
is invalid, 1: landing is valid
21
X2 normally open and normally closed selection 0:
Cr052 0-1 1
normally open input; 1: normally closed input
The user sets the usage time method: enter the password (default password ****) and enter the
system parameter interface Pr*** state
Pr124 Inverter password setting 0 -9999 ****
Pr126 Inverter cumulative running time (hours) 0—9999 ****
22
3.3 Debugging Instructions
3. 3. 1 Travel switch mode (Note: After modifying the running mode, it will take effect after
power off)
Set the parameter Cr000 to 0 stroke switch mode (factory default), and install and connect
correctly as shown in Figure 2-1 before use. Optimize the opening and closing process by
adjusting parameters Cr001 to Cr012.
3.3.2 Encoder mode (including incremental encoder and absolute value encoder)
1. If the user uses an incremental encoder, please set the Cr000 to 1(incremental encoder
mode), and install and connect the cable according to Figure 2-1. In this case, terminals A
and B are connected to signal lines X12V/(X24V) of the encoder, and COM is connected
to the ground wire of the encoder 013 "). The X0 terminal is connected to the encoder
zeroclearing switch, which must be installed at the lowest floor of the door.
2. If the user uses the absolute value encoder, please set the Cr000 to 2(absolute value encoder
mode) to install and connect the cable according to Figure 2-1. In this case, terminals A+
and B are connected to signal lines A+ and B of the encoder, 12V is connected to the power
cable of the encoder, and DCM is connected to the ground cable of the encoder 010 ").
Note: Use the specified model when connecting with the absolute value encoder.
3. Encoder learning: in the state of frequency display interface, long press "Mode/learn key",
when the nixie tube blinks, it indicates that it has entered the learning door high mode.
Press DOWN OR UP KEY TO ADJUST THE door machine to the lowest point (zero),
long press the keyboard "reset" button, then the current display pulse number can be
cleared, that is, the current position is the zero point of the door. Press the up button (or
up button), the door should move upward, and the number of pulses displayed at this time
should increase in a positive direction (if the number of pulses displayed is negative,
please modify Cr014 to change the installation direction of the encoder, and power off
and restart the initialization. Press the up button (or up button) to make the door run to the
upper limit position. At this time, press the "confirm" button and the digital tube will stop
flashing. The current pulse number is the number of pulses corresponding to the total
door height and the corresponding parameter is Cr015;
(1) Encoder direction learning: when the up button is pressed, the value of door stroke pulse
displayed on the LED of the operation panel should be increased; Conversely, when the
down button is pressed, the value of the door travel pulse displayed on the operating
panel LED should decrease; If not, switch terminals A and B or set Cr014 to 1.
(2), the total height of the door: under the pulse mode, long press "model/learning key, digital
tube at the same time scintillation, says it has entered into a state of total height of the
door to learn, and hold down the button, the door began to fall, when the door is touching
the reset switch X0 (or long press" reset "button), the encoder pulse number, frequency
converter to stop; At this point the gate nadir learning is complete. Keep pressing the up
button and the door will start to rise. When it reaches the upper limit, release the up
button and the frequency converter will stop. At this time, press the confirm button (or
press the emergency stop button first, and then press the up or down button), the digital
tube will stop flashing, and the frequency converter will automatically record the total
23
stroke pulse number of the current door height into the parameter Cr015. Alternatively,
the parameter Cr015 can be set manually to the current number of gate travel pulses.
After the setting of the total gate height, the frequency converter will automatically
calculate the lower limit, middle limit and upper limit according to the setting of
parameters Cr016, Cr017 and Cr018. If the positions of the lower limit, middle limit and
upper limit are found to be inappropriate during the operation, the setting values of
parameters Cr016, Cr017 and Cr018 can be adjusted manually. If the half-open/full-open
state function is required, set the parameter Cr019 to 1. At the same time, when the X4
terminal is effective, the frequency converter will stop when it rises to the mid-limit
position.
24
Er. 12 Express gate one-way timeout
25
Appendix I
Multi-door interlock wiring diagram 1
A door control box X8 B door control box X8 C door control box X8
interlock enable interlock enable interlock enable
26
Note: Pr068 can be set to d0012 to restore the double-door automatic door opening function
parameters
Cr037—>0001 Automatic door opening function in interlock state
Cr022—>013 Delay output from relay 2 to lower limit position
Cr048—>001:X9 The second door opening function is enabled
Appendix II
How to debug and learn door height in inverter mode:
Fast door converter debugging method: inverter factory may be mechanical limit mode, may also
be a single turn absolute value encoder mode. The method of debugging encoder mode or
mechanical limit mode is as follows:
Power on → display F000.5(or F000.8)→ Press the programming key once → Display Cr000→
Press the OK key once → display D0000 or D0002 → Press the up or down key to adjust the
corresponding mode (adjust it to D0000 by mechanical limit, D0001 by incremental encoder,
D0002 by M02 encoder) Then press the OK button once → power off (power on after the display
screen is completely off)
How to learn door height after adjusting mode (adjust upper and lower limits)
Electricity to display F0005 or F0008, push the study long - when the screen flash open - learn to
lower limit, under the direction key key to the low of the door (closed) - long press reset button to
reset the (when see digital display to let go after five zero) - according to the direction key key he
transferred to the highest point (the door) - according to determine the key after transferred to the
highest point at a time → Completion of learning
For example, when the encoder is learning, when the pulse from bottom to top is negative (there is
a minus sign in front of the number), please adjust it according to the following method (the
incremental encoder directly swaps the AB line):
Power on → display F0005 or F0008→ Press the programming button once → Display CrXXX
→ Press the direction key to adjust Cr014→ Press OK once → Display D0000 → press the up key
to adjust D0001 → press OK once → Power off (power on after the display screen is completely
off)
27
Appendix III
Common fault solutions:
28
① When using an incremental encoder, check whether the encoder
mode is adjusted (Cr000 is set to d0001, and there is no power off
after adjustment).
② If the inverter displays Er. 13. The power to decelerate may be too
small when ascending and decelerating, you can adjust Cr002 to
Er. 13
18Hz or 20Hz.
③ Check whether the incremental encoder is installed and connected
well, and whether there is any problem with the encoder.
④ If Er. 13 is reported during learning, check whether the motor
holding brake is released and whether the encoder pulse changes.
② The motor is abnormal and the brake fuse of the inverter is burned
Er. 14
out
③ Whether the input L and N of the 380V inverter are wired (220V)
In the encoder mode, if 00000 is displayed when learning the height of the door, press up
or down, the pulse is unchanged, the door can only move up or down a little, is not
adjusted to the corresponding encoder mode or no power off after adjusting the mode
After successful learning, the door will not come down at the highest point:
① Check whether the stop indicator on the panel of the inverter is always on or flashing
once and for all. If it is on, it means it is normal, and if it flashes once, it means it is in
emergency stop. It is enough to cancel the emergency stop.
② Unplug all the green terminals connected to the photoelectric, radar and door opening
and closing of the inverter, and press the door close key on the inverter panel, the door
should be able to close. Then check the photoelectric, radar and other external equipment,
whether the wires are connected properly, wrongly connected, and whether there is a short
circuit.
29