Professional Documents
Culture Documents
Automation Solution
Programmable Logic Controller
All-In-One PLC
With Next Generation Technology
XGB is the micro PLC that offers maximum automation at minimum cost.
With its high performance and functionality, it can support from simple control to complex task.
Strengthening its communication functions, XGB offers user-oriented integrated control.
Based on its strengths, it can be used in many fields of applications.
2
Contents
▶
Feature 4
▶
Main Unit 7
▶
Built-in functions 14
▶
Expansion 19
▶
DC Input 19
▶
Transistor Output 21
▶
Relay Output 23
▶
DC Input / Relay Output 24
▶
Analog Input 25
▶
Analog Output 26
▶
RTD 27
▶
Thermocouple 28
▶
Communication 29
▶
Software 30
▶
Product list 31
▶
Dimension 32
3
Feature
(Unit: mm)
Item W H D
DR/DN16S (16pt)
XBC / XEC
DN32S (32pt)
DR/DN32H (32pt)
DR/DN64H (64pt)
30
114
180
90
90
90
60
64
64
Relay output / Ethernet 27 90 60
Expansion
Others 20 90 60
Compactness
XGB is even more compact but provides powerful functions and performance.
Compact & Powerful solutions & XGB’s steadfast competitiveness.
4㎜
11
90
㎜
64㎜
㎜
30
60㎜
90
㎜
4
High Performance
With its high-speed processing and system capability,
XGB offers utmost efficiency for your applications.
Max. 10stages
XBM (S-Type)
•160ns/Step processing speed and floating-point arithmetic with on-board CPU
•Max 7 expansion modules, Max. 256 I/O point control: PLC systems for Small- and medium-scale applications
•Max. 5-Ch Communication with built-in functions and expansion modules
Max. 7stages
5
Feature
Easiness &
Convenience
XGB offers convenient user interface with various network
diagnosis & monitoring functions and back-up function
Frame monitoring
6
Main Unit | DC power Programmable Logic Controller
*1) Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used.
Pollution level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to
condensing.
7
Main Unit | DC power
8
Programmable Logic Controller
Connection cable
Terminal board
XBM-DN16S
Terminal board Connection cable Remark
XBM-DN32S
1. Cable length
SLT-CT051-XBM ● CT051: 0.5m
CT101: 1.0m
SLP-T40P
2. Board type
SLT-CT101-XBM ● T40P: Terminal board
RY4A: Relay board
9
Main Unit | AC or DC power
*1) Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used. Pollution
level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to condensing.
10
Programmable Logic Controller
11
Main Unit | AC power
Input wiring
(XBC-DR32H / XBC-DN32H
XEC-DR32H / XEC-DN32H)
485+ 485- P00 P02 P04 P06 P08 P0A POC POE COM 24V
Input wiring
(XBC-DR64H / XBC-DN64H
XEC-DR64H / XEC-DN64H)
RX TX SG P01 P03 P05 P07 P09 P0B P0D POF NC P11 P13 P15 P17 P19 P1B P1D P1F 24G
485+ 485- P00 P02 P04 P06 P08 P0A P0C P0E COM0 P10 P12 P14 P16 P18 P1A P1C P1E COM1 24V
AC100 ~
P20 P22 COMO P25 P27 P28 P2A COM2 P2D P2F
240V
FG NC P21 P23 P24 P26 COM1 P29 P2B P2C P2E COM3
12
Programmable Logic Controller
AC100 ~
P20 P22 COMO P25 P27 P28 P2A COM2 P2D P2F
240V
FG P P21 P23 P24 P26 COM1 P29 P2B P2C P2E COM3
AC100
P20 P22 COM0 P25 P27 P28 P2A COM2 P2D P2F P30 P32 P34 P36 COM4 P39 P3B P3D P3F
240V
FG NC P21 P23 P24 P26 COM1 P29 P2B P2C P2E COM3 P31 P33 P35 P37 P38 P3A P3C P3E COM5
AC100 ~
P20 P22 COM0 P25 P27 P28 P2A COM2 P2D P2F P30 P32 P34 P36 COM4 P39 P3B P3D P3F
240V
FG P P21 P23 P24 P26 COM1 P29 P2B P2C P2E COM3 P31 P33 P35 P37 P38 P3A P3C P3E COM5
13
Built-in functions | High-speed counter
Wiring
14
Programmable Logic Controller
15
Built-in functions | Positioning
16
Programmable Logic Controller
Electrical specification Rated input Load voltage Max. load Max. voltage Leakage Response
Signal
voltage range current/inrush current drop (On) current (Off) time
Output
DC 100mA(1 point) DC 0.3V or 0.1mA or
Output pulse DC 5~24V 100㎲ or less
4.75~26.4V 1A/10ms or less less less
Rated input Load voltage On Off Input Response
Signal
voltage/current range voltage/current voltage/current resistance time
External high limit DC 19V/5.7mA DC 6V/1.8mA
Input DC 24V/7mA 3.3Ω
External low limit DC 20.4 ~ or more or less
0.5ms or less
Approximate zero 28.8V DC 19V/3.4mA DC 6V/1.1mA
DC 24V/4mA 5.6Ω
zero or more or less
Wiring
Wiring with DC 5V
17
Built-in functions | PID/Pulse catch/Input filter/Task
Cascade Improved control precision by serial connection between Master loop and Slave loop
Function SV Ramp Preventing overload caused by excessive SV change by setting variation slope
Improved control stability with various alarm function such as MV high limit/low limit,
Alarm
PV high limit/low limit, PV variation width
Auto tuning Auto tuning with improved auto-tuning algorithm
Additional function PWM output, PV Tracking, ▵MV, ▵PV, etc
Pulse catch When the On-condition time of input signal (P0000~P0007) is shorter than 1 scan time (Min. 50㎲), Pulse catch
processes the input signal as normal input.
Input filter Input filter prevents processing of the input signal that is shorter than the filtering time. (Filtering time is set by
parameter) In the application site where noise is frequently generated, input filter prevents wrong input caused by noise.
Item Description
No. of setting points Every input contact
Input filtering time setting Assigning for each module
Setting range 1 ~ 100㎳ (1,3,5,10,20,70,100)
Task Task function is the processing method of internal/external signal generated preriodically or aperiodically.
(Total 24 task can be assigned.) It stops operation of scan program for the moment and then execute the
assigned task.
Types of Task 2. Fixed-cycle task setting
1. Initialization task setting Description
Item
Running a task one time before INIT_DONE No. of setting points 8 points
at initial execution Setting range 1~42,94,967,295ms
18
Expansion | DC Input Programmable Logic Controller
XBE-DC08A
XBE-DC16A
XBE-DC32A
19
Expansion | DC Input
20
Expansion | Transistor Output Programmable Logic Controller
Specification Model
Specification XBE-TN08A XBE-TP08A XBE-TN16A XBE-TP16A XBE-TN32A XBE-TP32A
21
Expansion | Transistor Output
22
Expansion | Relay Output Programmable Logic Controller
23
Expansion | DC Input / Relay output
XBE-DR16A
Wiring (XBE-DR16A)
8-point DC input 8-point Relay Output
24
Expansion | Analog Input Programmable Logic Controller
※Use 22AWG, 2 conductor, twist shielded cable when wiring between analog module and
external device.
25
Expansion | Analog Output
Wiring
2kΩ or more 510Ω or less
XBF- XBF-
2kΩ or more 510Ω or less
DV04A DC04A
26
Expansion | Analog Input/Analog Output Programmable Logic Controller
Specification XBF-AH04A
Item
Input Output
❶ Analog channel 2 channels 2 channels
❷ DC 1 ~ 5V, DC 0 ~ 5V, DC 0 ~ 10V DC 1 ~ 5V, DC 0 ~ 5V, DC 0 ~ 10V
(Input resistance: 1 MΩmin.) (Load resistance ≥ 2kΩ)
❽ Analog range
DC 4 ~ 20mA, DC 0 ~ 20mA DC 4 ~ 20mA, DC 0 ~ 20mA
(Input resistance 250Ω) (Load resistance ≤510Ω)
❸ Analog range Selection XG 5000 I/O parameter and External switch
Unsigned value 0 ~ 4000
❹
Signed value -2000 ~ 2000
Digital data 100 ~ 500 (DC 1 ~ 5V), 0 ~ 500 (DC 0 ~ 5V), 0 ~ 1000 (DC 0 ~ 10V)
Precise value
400 ~ 2000 (DC 4 ~ 20mA), 0 ~ 2000 (DC 0 ~ 20mA)
❺
Percentile value 0 ~ 1000
1.25mV (DC 1~5V, 0~5V), 2.5mV (DC 0~10V)
Resolution(1/4000)
5 (DC4~20mA, 0~20mA)
❻ Max. conversion speed ±15V, 25mA
Max. absolute output 1ms / channel
Accuracy ±0.5% or less
Insulation method Photocoupler insulation between I/O terminal and power supply
❼
Connection terminal 11-point terminal block
Occupied I/O points Fixed type: 64 points
XBF-AH04A Current DC 5V 120mA
consumption DC 24V 130mA
Wiring Wiring with 2-wire sensor (for analog input) Wiring with 4-wire sensor (for analog input)
※Use 22AWG, 2 conductor, twist shielded cable when wiring between analog module and
external device.
27
Expansion | RTD
XBF-RD04A
Wiring
28
Expansion | Thermocouple Programmable Logic Controller
Wiring
Compensation Shield
Module
cable Terminals cable Sensor
29
Expansion | Communication
XBL-EMTA
RS-232C, RS-422 / 485 Item Built-in RS-232C XBL-C21A Built-in RS-485 XBL-C41A
Interface RS-232C 1Ch RS-232C 1Ch RS-485 1Ch RS-422 / 485 1Ch
MODEM Function Remote communication via the external MODEM (XBL-C21A Only)
Dedicate 1:1 or 1:N via the dedicated protocol
Mode XG5000 mode Program download, upload and control via the remote control
P2P Communication defined by the protocol using XG-PD XGT / Modbus master
Operation Server (slave) XGT / Modbus Server, User-defined communication
Mode Client (master) XGT / Modbus P2P Master, User-defined communication
Start Bit 1
Data Bit 7 or 8
Data format Stop Bit 1 or 2
Parity Even / Odd / None
Setting Setting by XG-PD parameter
Synchronous Asynchronous
XBL-C21A Speed (bps) 1,200 / 2,400 / 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps
XBL-C41A Station number Setting by XG-PD, Max. 32 stations
Distance RS-232C: Max.15m (Expansion by MODEM), RS-422/485: Max 500m
MODEM communication - Support - -
Network 1: 1 1: N
Diagnostic Via LED and XG-PD
Max. expansion Built-in 2 stages Built-in 2 stages
30
Software Programmable Logic Controller
Variable Monitor
Ladder Monitor
Forced I/O
Fast Ethernet
XGT Panel
Cnet
Other PLC
31
Product list
32
Dimension Programmable Logic Controller
Dimension
60
90
64
30
100
90
W 64
(Unit: mm)
Item Model W H D
XBM Main unit 30 90 60
DR/DN32H (32pt) 114 90 64
XBC/XEC
DR/DN64H (64pt) 180 90 64
RY output / EMTA 27 90 60
DC input
Common
TR output 20 90 60
Analog
33
MEMO
34
MEMO Programmable Logic Controller
35
� For your safety, please read user's manual thoroughly before operating.
� Contact the nearest authorized service facility for examination, repair, or adjustment.
� Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned.
www.lsis.biz
2009. 05 LS XGB (E) 2006. 06/ (07) 2009. MAY Printed in Korea HumanPower