Professional Documents
Culture Documents
Drainage Installation
Objective
Disclaimer
1.1 Scope
1.2 Design Responsibilities
Building Services Branch, ArchSD Page 3 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
1. Introduction
1.1 Scope
This design guide aims at providing general guidance on the design of drainage
installation. The design processes including coordination with Drainage Services
Department (DSD) at project inception stage, selection of systems and their
components, tank and pipe sizing, specifications and statutory submission are
introduced.
The scope of this design guide covers the general drainage installation except the
following:
The professional officer is responsible for the design and construction of the drainage
installation including establishment of client’s requirements, preparation of design and
contract document, supervision of construction and acceptance of the installation from
the contractors and handover to client and maintenance divisions. All the statutory
requirements and procedure of the departments, local and appropriate international
standards are to be observed.
Building Services Branch, ArchSD Page 4 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
2. Statutory Requirements, Standards and Guidelines
2.1.1 Drainage installation in buildings shall comply with the Buildings Ordinance
(Cap 123) and the following associated regulations:
(E) Building (Refuse Storage and Material Recovery Chambers and Refuse
Chutes) Regulations.
2.2.1 The following Practice Notes (PNAP) issued by Buildings Department are
relevant for the design of drainage installations.
(F) PNAP 218 - Facilities for External Inspection and Maintenance of Buildings
(K) PNAP 245 - Waste Minimization – Provision of Fitments and Fittings in New
Buildings
(O) PNAP 297 - Provision of Sanitary Fitments in Offices, Shopping Arcades and
Department Stores, Places of Public Entertainment and Cinemas
(C) EPD - Guidelines for the Design of Small Sewage Treatment Plants
2.3 Standards
The standard BS EN 752 : 2008, Drain and sewer systems outside buildings, specifies
the functional requirements for planning, design, installation, operation, maintenance
and rehabilitation, whilst the standard BS EN 12056-2 : 2000, Gravity Drainage
Systems Inside Buildings - Part 2: Sanitary Pipework, Layout and Calculation, covers
wastewater drainage systems which operate under gravity. It is applicable for drainage
systems inside dwellings, commercial, institutional and industrial buildings.
Building Services Branch, ArchSD Page 6 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
3. Drainage System and Design – Above Ground System
3.1.1 Introduction
A storm water drainage system should be designed to collect and convey the
run-off water from catchments during and after raining, and to discharge
safely into a receiving watercourse. The magnitude of peak flows that have
to be accommodated will depend primarily on the intensity of rainfall and the
size, topography, soil type, configuration and land use of the catchments.
General information on the planning and investigation required for storm
water drainage systems can be referred to BS EN 752 : 2008.
(A) Rainwater outlet or channels are the most common components for the
collection of rainwater on roof.
(B) The design of the rainwater drainage system for any roof structure will
depend upon the profile of the roof, i.e. pitched roof and flat roof.
(a) This type of roof is provided with gutters fixed at the eaves of the pitch,
but they may be external to the roof structure (Fig. a) or internal (Fig.
b). The down pipes may also be external or internal, when the design
requirements are of performance standards, which must comply with
the regulations for discharge pipes.
(b) Pitched roofs may be added together, this form of roof is often used as
a lightweight construction for large-plan factories. The junctions
between the pitches form valleys in which a valley gutter must be
provided. It is very important that this gutter is correctly sized and
installed, as failure will mean water overflowing into the building.
Figure (a)
Building Services Branch, ArchSD Page 7 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Figure (b)
(c) Provision must be made to allow the valley gutter to overflow external
to the building - usually by a weir overflow at the end (in case a
blockage of the down pipe or outlet occurs), and it is advisable to
provide slatted walk boards down the length of the gutter to prevent
both damage to the material of the gutter by maintenance operatives.
(a) Flat roof usually refers to a roof whose outer surface is nearly
horizontal or inclined at an angle not exceeding 10 degrees. Eaves
gutters can be used to flat roofs and the design rules are then similar to
those for pitched roof systems of drainage, but often flat roofs are
finished with parapets or up stands of some form and the roof must be
drained by a system of outlets integrated with the pitch plan of the area.
(b) It is always advisable to position some of the outlets at the corners and
periphery of the building and inadvisable to rely on outlets positioned
only on pitch junctions down the centre line of a roof. It is
recommended that the provision of box gutters at parapets and
longitudinal box gutters across the roof will provide a good drainage
system.
(a) Runoff from a catchment depends upon many factors which include: -
(v) the condition of the surface and nature of the subsurface soils.
(a) Step 1: Determine the surface channel layout on open roof floor for
collection of rainwater. In general practice, at least 200mm wide of
each surface channel is considered sufficient for collection.
(b) Step 2: Design the direction and extent of fall of the channel(s) or
gutter(s) of gradient not less than 1:100 according to Cap.123I Reg. 61.
(Cap 123I Reg 61 is shown in Section 6.1)
(c) Step 3: Design and allocate the number of rainwater outlet(s) in the
channel(s) for collecting the rainwater downwards. According to
Building Regulations, Cap 123I Reg.32(2), projected horizontal roof
area of every 10m2 shall be served by a rainwater pipe of cross
sectional area of 700mm2. By using this formula, it is able to determine
the size and quantity of the rainwater down pipe(s).
(d) Step 4: Design the piping layout and rainwater down pipe(s), according
to Cap. 123I Reg. 31 to Reg. 35, Reg. 37, Reg. 38, Reg. 46, Reg. 52
and Reg. 61. The diameter of every rainwater pipe shall be not less than
65 mm, except for rainwater pipe connecting from the balcony or
varandah, the diameter shall be no more than 40mm. (Cap 123I Regs is
shown in Section 6.1)
(A) Step 1: Trace the rainwater down pipe(s) connecting to the above floor, e.g.
roof floor. If the rainwater pipe is concealed in a pipe duct, access panel shall
be provided for maintenance, according to Cap 123I Reg. 37 and PNAP 211.
(B) Step 2: Determine the surface channel layout on open air area of the floor(s),
such as verandas, balconies, etc. for collection of rainwater. Similar as the
design concept for open roof floor, at least 200mm wide of each surface
channel is considered sufficient for collection. Reference should be made on
Cap. 123I Reg.33 - Rainwater pipes for verandas or balconies. It requires that
the surface water collected from a veranda or balcony shall be connected to a
rainwater pipe for discharge by the rain water pipe of internal diameter not
more than 40 mm.
(C) Step 3: Design the direction and extent of fall of the surface channel of
gradient not less than 1:100 according to Cap.123I, Reg. 61.
(D) Step 4: Design and locate the rainwater outlets in the channels by using the
minimum gradient of the channels 1:100 and depending on the depth of the
Building Services Branch, ArchSD Page 9 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
channels, i.e. depending on the level of structural and finishing surfaces, for
example 150mm. Distance between outlets can be calculated by simple
geometry.
(E) Step 5: Design the piping layout and rainwater down pipe(s), according to
Cap. 123I Reg. 31 to Reg. 35, Reg. 37, Reg. 38, Reg. 46, Reg. 52 and Reg.
61. The diameter of every rain water pipe shall be not less than 65 mm.
(A) Step 1: Trace the rainwater down pipe(s) connecting to the above floor.
(B) Step 2: Determine the covered channel layout on G/F for collecting rainwater
at external ground area and the direction and extent of fall. The external
ground surface shall be laid to fall at a gradient of not less than 1 in 80 to a
gully trap or drainage channels connected to a surface water drain according
to Cap. 123B, Building Construction Regulations, Reg. 33.
(C) Step 3: Design the direction and extent of fall of the flat channel, which
collects the ground surface water of gradient not less than 1:100 according to
Cap.123I, Reg. 61. Sizing of the drain pipe connecting to the gully trap
catering for the specific catchments area shall be determined by a hydraulic
calculation formula with the recommendation of the rainfall intensity being
258 mm/hr. The required flow (Q) in L/s is calculated by the following
Rational formula, which was developed in mid-nineteenth century.
i ΣσA
Q =
3600
Where σ is the Run-off Coefficient of the catchments area between 0 and 1
(for slope drainage, σ being 1 which includes the allowance of silting of
drains), i is the rainfall intensity in (mm/hr) and A is the catchments area(s)
in m2.
For the size of the pipe at 300mm diameter or below, the gradient of the pipe
is stated in the Table XII in Building Regulations, Cap. 123I Reg. 48, Fall of
drains as follow: -
Every drain or private sewer shall be laid with a minimum fall from its
highest inlet to its connection with a public sewer or other outlet in
accordance with the table below.
Building Services Branch, ArchSD Page 10 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
If the size of pipe is over 300mm diameter, the gradient should be
determined such that the flow velocity will be maintained at 1m/s, full bore
flow condition which provides the self-cleansing effect on the rainwater pipe.
The following table provides the hydraulic data of the pipe:
(D) Step 4: Design and locate the gully traps in the surface channels on G/F by
using the minimum gradient of the channels 1:100 and depending on the
designed depth of the channels, i.e. depending on the level of structural and
finishing surfaces, for example 150mm. Distance between traps can be
calculated by simple geometry.
(E) Step 5: Design and locate the pipe(s) from high floors. Rainwater pipes shall
not be connected with any soil pipe, waste pipe or ventilating pipe.
(F) Step 6: Design the drain for connecting the down rainwater pipe according to
Cap 123I, Reg. 32 on Rain water pipes: -
(a) If a rainwater pipe installed outside a building, the discharge point shall
be located either 150mm higher than ground level over a trapped gully
or connected into a trapped gully below the level of grating but above
the level of the water in the trap.
(d) A cast iron conductor with a shoe at the foot shall be provided for any
surface water discharge by the rainwater pipe to the side channel in a
street. Similarly, cast iron conductor shall be provided for rainwater
pipe discharges across footpath to the side channel of a street.
(A) Unplasticized PVC (UPVC) to ISO 4435 (replacing BS 4660) for pipework
size not exceeding 80 mm diameter, and to ISO 3633 for pipework size
exceeding 80 mm diameter is widely used for storm water drainage due to its
low cost, light weight and ease of installation. Expansion joints must be
provided to the pipework for external installation. Interchangeability shall
not be allowed between different plastic pipe manufacturer’s products.
Plastic pipes should be protected from the sun when stacked and during
laying. The strength of the UPVC pipe is relatively low at 70ºC when
compared with metal pipe.
(B) Cast iron pipes and fittings shall be to BS 437, with flexible joints to BS EN
877 could be used for storm water drainage. Coupling jointed cast iron pipes
(Hubless Cast Iron Pipe System) shall be to ISO 6594 standard (BS EN 877).
(C) Hubless epoxy coated cast iron pipe to ASTM 888 could be used. This kind
of cast iron pipe is watertight and resistance to corrosion. The major problem
of this pipework is the equal-potential bonding since epoxy is an insulted
material. Since this kind of pipe does not in line with Cap. 123I,
modification should be obtained from Buildings Authority.
There are different types of floor drains in the market, but not limited to
followings:
Building Services Branch, ArchSD Page 12 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(C) Gully outlet
Considering design for storm drainage system for the roof of 84m2, in
connection with down storm water pipes to the ground floor. Rainwater
intensity is designed at 250mm/ hr.
For roof:
Storm water is collected by flat channel(s) with not less than 1:100 gradient
fall on the roof. Rainwater outlet(s) are required to be located at the lowest
level of each channel.
= 84 m2 / 10 m2 x 700mm2
= 5880mm2
= Ø87mm (one step commercial size, i.e. Ø100mm can be used, according to
Reg.32(b)(3), min. size of rainwater down pipe being Ø65mm)
For intermediate floors storm water design, the calculation principle is based
on the ‘Collection Surface Area’ of storm water for the location(s) with storm
water outlet(s), such as balcony of each flat/ unit, open roof garden at
intermediate floor(s), etc. Depending on the schematic diagram on the storm
water design, the storm water down pipe sizing will depend on the
summation of all Collection Surface Area at the collection locations of each
floor.
For Ground floor, the total catchment area equals to total collection surface
Building Services Branch, ArchSD Page 13 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
area collecting the storm water from floor above to the central storm drain,
including the roof surface area. If the storm water system contains only the
roof and the open area on ground floor, i.e. no storm water outlets on
intermediate floors, catchment area of the open space on G/F is 116 m2. Thus,
the total catchment areas become 84 m2 + 116 m2 = 200 m2.
By Rational formula,
From Step 3, Table XII in Building Regulations, Cap. 123I Reg. 48,
Ø150mm pipe with fall of 1:70 should be used.
3.2.1 Introduction
(b) The major advantage of this system is low cost, easy to install and easy
to maintain. However, the trap seal is recommended to be at least
75mm to prevent the loss of water seal. The stack extends to the roof
level with open end and a wire balloon for venting. The downstream of
Building Services Branch, ArchSD Page 14 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
the stack is usually embedded in the underground for connection to the
manholes and underground sewers.
(a) The fitments can be categorized into soil fitment and waste fitment.
Soil fitment (e.g. urinal, water closet, bidet, etc.) is defined as the
fitment, which will receive the human excrement whereas waste
fitment (e.g. hand basin, bathtub, sink, etc.) is defined as the fitment,
which will receive wastewater except human excrement.
(b) The drain pipes connected to the soil and waste fitment are respectively
denoted as soil pipe and waste pipe.
(a) Bitumen coated cast iron pipe to BSEN877 by spun casting or sand
moulding, which is most traditional drain pipe being used for many
decades until 90's.
(b) Hubless epoxy coated cast iron pipe to ASTM 888 becomes more
popular since 90's. This kind of cast iron pipe is watertight and
resistance to corrosion. The major problem of this pipework is the
equal-potential bonding since epoxy is an insulted material. Since
this kind of pipe does not in line with Cap. 123I, modification should
be obtained from Buildings Authority.
Building Services Branch, ArchSD Page 16 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
3.2.5 Traps and Floor Drains
(A) Trap is a very important component in soil and waste system. A water seal
should be provided between the upstream and the downstream of the trap.
The trap has the following major functions:
(a) To prevent the ingress of foul air from the soil and waste system.
(b) To prevent the noise transmission from the foul system to the interior
of the bathroom; and
(a) Leakage will allow water in the trap to empty on to the floor and is
consequently soon noticed and repaired.
Self siphonage
Induced siphonage
(c) Compression occurs when the water is discharge from the higher
fitting the air in the vertical pipe may become compressed sufficiently
to ‘blow’ out the seal in the lower fitting.
(e) Wavering out is caused by gusts of wind passing over the top of the
vent pipe and is often noticed in a W.C. trap on a windy day.
(f) Evaporation occurs if the trap is not in use, the rate of evaporation of
the water will depend upon the humidity of the air in the room.
(g) Momentum is caused by the sudden discharge of water into the trap.
This type of trap has a division between the inlet and outlet legs formed
by a dip tube or vane within the body of the trap, with the lower part of
the trap being removable for access. Bottle traps should only be used
with wash basins.
Building Services Branch, ArchSD Page 19 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(D) Trap seal
Flow of water induces movement of air in the direction of flow. Full bore
flow can occur in pipe of small diameter, but is not likely in discharge pipe
(100 mm diameter) from W.C.
At foot of stack, flow leaves walls and runs in bottom of pipe, thus
reduced velocity result in greater cross sectional area of pipe being
Building Services Branch, ArchSD Page 20 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
occupied and reduced the air space. Positive pressure develops at foot
of stack and may blow traps (sharp bend at foot makes problem worse).
With total bridging of pipe, hydraulic pump may occur. Under this
condition, gross pressure fluctuations will occur. Therefore, venting
should be provided.
Flow from branch entering stack gravitates downwards and assumes a form
of sheet on wall of stack. Air flow is induced down the stack and pressure
fluctuations will develop throughout the entire stack. When 1/4 to 1/3 full
flow capacity is reached, the whole section of the pipe is bridged at intervals
by ‘plugs’ of water. Severe pressure fluctuation will occur. Complete trap
venting would be required.
Q =AV
Building Services Branch, ArchSD Page 21 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Where A and V are the pipe cross-sectional area and flow velocity
respectively
Pipe flowing
1/3 bore 1/2 bore 2/3 bore Full bore
HMD CSArea HMD CSArea HMD CSArea HMD CSArea
0.186D 0.299D2 0.25D 0.39D2 0.291D 0.556D2 0.25D 0.785D2
Note: D = Pipe diameter in m
HMD = Hydraulic mean depth in m
CSArea = Cross sectional area in m2
Building Services Branch, ArchSD Page 22 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(F) Colebrook-White Equation
ks 2.51v
V = √ (8g D s) log ( + )
3.7D D√(2g D s)
(b) For open channel flows
ks 1.255v
V = √ (32g R s) log ( + )
14.8R R√(32g R s)
where V = mean velocity (m/s)
g = gravitational acceleration (m/s2)
R = hydraulic radius (m)
D = pipe diameter
ks = equivalent sand roughness (m)
v = kinematic viscosity of fluid (m2/s)
s = frictional slope (energy gradient due to frictional loss)
Building Services Branch, ArchSD Page 23 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Table B.1 - Capacity of drains, filling degree 50%, (h/d = 0.5)
Slope DN DN DN DN DN DN DN
100 125 150 200 225 250 300
i Qmax v Qmax v Qmax v Qmax v Qmax v Qmax v Qmax v
cm/m L/s m/s L/s m/s L/s m/s L/s m/s L/s m/s L/s m/s L/s m/s
0.50 1.8 0.5 2.8 0.5 5.4 0.6 10.0 0.8 15.9 0.8 18.9 0.9 34.1 1.0
1.00 2.5 0.7 4.1 0.8 7.7 0.9 14.2 1.1 22.5 1.2 26.9 1.2 48.3 1.4
1.50 3.1 0.8 5.0 1.0 9.4 1.1 17.4 1.3 27.6 1.5 32.9 1.5 59.2 1.8
2.00 3.5 1.0 5.7 1.1 10.9 1.3 20.1 1.5 31.9 1.7 38.1 1.8 68.4 2.0
2.50 4.0 1.1 6.4 1.2 12.2 1.5 22.5 1.7 35.7 1.9 42.6 2.0 76.6 2.3
3.00 4.4 1.2 7.1 1.4 13.3 1.6 24.7 1.9 389.2 2.1 46.7 2.2 83.9 2.5
3.50 4.7 1.3 7.6 1.5 14.4 1.7 26.6 2.0 42.3 2.2 50.4 2.3 90.7 2.7
4.00 5.0 1.4 8.2 1.6 15.4 1.8 28.5 2.1 45.2 2.4 53.9 2.5 96.9 2.9
4.50 5.3 1.5 8.7 1.7 16.3 2.0 30.2 2.3 48.0 2.5 57.2 2.7 102.8 3.1
5.00 5.6 1.6 9.1 1.8 17.2 2.1 31.9 2.4 50.6 2.7 60.3 2.8 108.4 3.2
Slope DN DN DN DN DN DN DN
100 125 150 200 225 250 300
i Qmax v Qmax v Qmax v Qmax v Qmax v Qmax v Qmax v
cm/m L/s m/s L/s m/s L/s m/s L/s m/s L/s m/s L/s m/s L/s m/s
0.50 2.9 0.5 4.8 0.6 9.0 0.7 16.7 0.8 26.5 0.9 31.6 1.0 56.8 1.1
1.00 4.2 0.8 6.8 0.9 12.8 1.0 23.7 1.2 37.6 1.3 44.9 1.4 80.6 1.6
1.50 5.1 1.0 8.3 1.1 15.7 1.3 29.1 1.5 46.2 1.6 55.0 1.7 98.8 2.0
2.00 5.9 1.1 9.6 1.2 18.2 1.5 33.6 1.7 53.3 1.9 63.6 2.0 114.2 2.3
2.50 6.7 1.2 10.8 1.4 20.3 1.6 37.6 1.9 59.7 2.1 71.1 2.2 127.7 2.6
3.00 7.3 1.3 11.8 1.5 22.3 1.8 41.2 2.1 65.4 2.3 77.9 2.4 140.0 2.8
3.50 7.9 1.5 12.8 1.6 24.1 1.9 44.5 2.2 70.6 2.5 84.2 2.6 151.2 3.0
4.00 8.4 1.6 13.7 1.8 25.8 2.1 47.6 2.4 75.5 2.7 90.0 2.8 161.7 3.2
4.50 8.9 1.7 14.5 1.9 27.3 2.2 50.5 2.5 80.1 2.8 95.5 3.0 171.5 3.4
5.00 9.4 1.7 15.3 2.0 28.8 2.3 53.3 2.7 84.5 3.0 100.7 3.1 180.8 3.6
Building Services Branch, ArchSD Page 24 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(G) Manning Formula
1
V = R⅔ S½
n
where R= hydraulic radius (m)
S= inclination, gradient or slope = fall or head / length
n = Manning’s coefficient of roughness (Manning’s n)
A French engineer, Antoine Chezy, assumed that the resisting force per unit
area of the channel bed is proportional to the square of the mean velocity,
KV2. The expression derived by Chezy is simplified to Chezy’s formula for
open channel flow:
V = C (m · s)1/2
where C = Chezy’s resistance factor (for most practical purpose, C may be
taken as 55 – a constant)
m = Hydraulic mean depth (m)
s = Inclination, gradient or slope = fall or head / length
The followed table gives the discharge unit values (DU), in L/s, for common
appliances. The values for WC’s are dependent on the design of the
appliance, and the relevant manufacturer should be consulted. Where the
type of WC is unknown at the design stage, or likely to change, the
maximum rating should be assumed. The first task is to add up all the
discharge units applicable to a discharge stack.
Building Services Branch, ArchSD Page 25 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Appliance DU (L/s)
Wash basin 0.3
Shower without plug 0.4
Shower with plug 1.3
Single urinal with cistern 0.4
Slab urinal (per person) 0.2
Bath 1.3
Kitchen sink 1.3
Dishwasher (household) 0.2
Washing machine (6 kg) 0.6
Washing machine (12 kg) 1.2
WC with 6 L cistern 1.2 – 1.7
WC with 7.5 L cistern 1.4 – 1.8
WC with 9 L cistern 1.6 – 2.0
Not all sanitary appliances will be in simultaneous use. The peak design
flow can be assessed by applying a frequency of use K factor to the total
sum of the discharge units, and by using the following equation:
Qww = K √∑DU
Usage of appliances K
Intermittent use, e.g. indwelling, guesthouse, office 0.5
Frequent use, e.g. in hospital, school, restaurant, hotel 0.7
Congested use, e.g. in toilets and/or showers open to public 1.0
Special use, e.g. laboratory 1.2
Building Services Branch, ArchSD Page 26 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Sum of
discharge K = 0.5 K = 0.7 K = 1.0 K = 1.2
units
∑DU Qww (L/s) Qww (L/s) Qww (L/s) Qww (L/s)
10 1.6 2.2 3.2 3.8
12 1.7 2.4 3.5 4.2
14 1.9 2.6 3.7 4.5
16 2.0 2.8 4.0 4.8
18 2.1 3.0 4.2 5.1
20 2.2 3.1 4.5 5.4
25 2.5 3.5 5.0 6.0
30 2.7 3.8 5.5 6.6
35 3.0 4.1 5.9 7.1
40 3.2 4.4 6.3 7.6
45 3.4 4.7 6.7 8.0
50 3.5 4.9 7.1 8.5
60 3.9 5.4 7.7 9.3
70 4.2 5.9 8.4 10.0
80 4.5 6.3 8.9 10.7
90 4.7 6.6 9.5 11.4
100 5.0 7.0 10.0 12.0
110 5.2 7.3 10.5 12.6
120 5.5 7.7 11.0 13.1
130 5.7 8.0 11.4 13.7
140 5.9 8.3 11.8 14.2
150 6.1 8.6 12.2 14.7
160 6.3 8.9 12.6 15.2
170 6.5 9.1 13.0 15.6
180 6.7 9.4 13.4 16.1
190 6.9 9.6 13.8 16.5
200 7.2 9.9 14.1 17.0
220 7.4 10.4 14.8 17.8
240 7.7 10.8 15.5 18.6
260 8.1 11.3 16.1 19.3
280 8.4 11.7 16.7 20.1
300 8.7 12.1 17.3 20.8
320 8.9 12.5 17.9 21.5
340 9.2 12.9 18.4 22.1
360 9.5 13.3 19.0 22.8
380 9.7 13.6 19.5 23.4
400 10.0 14.0 20.0 24.0
Building Services Branch, ArchSD Page 27 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(J) Total flowrate (Qtot)
Qtot is the design flowrate in a part or in the whole drainage system where
sanitary appliances, appliances with continuous flow and/or wastewater
pumps are connected to the system.
Continuous flows and pump discharge rates shall be added to the wastewater
flowrate without any reduction.
Qtot = Qww + Qc + Qp
Where 1 bath, 2 wash basin, 3 WC, 4 floor gully, 5 air admittance valve,
6 stack, 7 branch discharge pipe, 8 drain, 9 stack vent
Building Services Branch, ArchSD Page 28 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Stack and stack vent Qmax (L/s)
(DN) Square entries Swept entries
60 0.5 0.7
70 1.5 2.0
80 2 2.6
90 2.7 3.5
100 4.0 5.2
125 5.8 7.6
150 9.5 1.4
200 16 21
Where square entry equals branch junction that is more than 45°, or
has a centre line radius less than the internal pipe diameter;
swept entry equals branch junction that is at 45° or less, or
has a centre line radius not less than the internal pipe diameter
Where 1 bath, 2 wash basin, 3 WC, 4 floor gully, 5 air admittance valve,
6 stack, 7 branch discharge pipe, 8 drain, 9 stack vent, 10 ventilating
stack, 11 branch ventilation pipe, 12 urinal
Building Services Branch, ArchSD Page 29 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Sizes and limitations of the secondary ventilated discharge stacks are
given in the following table.
Building Services Branch, ArchSD Page 30 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Unventilated discharge branch configuration
Sizes and limitations upon the use of Unventilated and Ventilated Branch
Discharge Pipes are given in Table 6 and Table 9. For the detail
configurations, Section 2.2.6 Part K can be referred.
Building Services Branch, ArchSD Page 31 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Table 6 - Limitations for unventilated branch-discharge-pipes, system III
Appliance Diameter Min. trap Max. length (L) Pipe Max. Max.
seal depth of pipe from gradient number of drop
trap outlet to bends (H)
stack
DN mm m % No. m
Washbasin, bidet 30 75 1.7 2.21) 0 0
(30 mm diameter trap)
Washbasin, bidet 30 75 1.1 4.41) 0 0
(30 mm diameter trap)
Washbasin, bidet 30 75 0.7 8.71) 0 0
(30 mm diameter trap)
Washbasin, bidet 40 75 3.0 1.8 to 4.4 2 0
(30 mm diameter trap)
Shower, bath 40 50 No Limit2) 1.8 to 9.0 No Limit 1.5
Bowl urinal 40 75 3.03) 1.8 to 9.0 No Limit4) 1.5
Trough urinal 50 75 3.03) 1.8 to 9.0 No Limit4) 1.5
5) 3)
Slab urinal 60 50 3.0 1.8 to 9.0 No Limit4) 1.5
2)
Kitchen sink 40 75 No Limit 1.8 to 9.0 No Limit 1.5
(40 mm diameter trap)
Household dishwasher 40 75 3.0 1.8 to 4.4 No Limit 1.5
or washing machine
WC with outlet up to 75 50 No Limit 1.8 Min. No Limit4) 1.5
6)
80 mm
WC with outlet greater 100 50 No Limit 1.8 Min. No Limit4) 1.5
6)
than 80 mm
Food waste disposal7) 40 Min. 758) 3.03) 13.5 Min. No Limit4) 1.5
8) 3)
Sanitary towel disposal 40 Min. 75 3.0 5.4 Min. No Limit4) 1.5
unit
Floor drain 50 50 No Limit3) 1.8 Min. No Limit 1.5
Floor drain 70 50 No Limit3) 1.8 Min. No Limit 1.5
Floor drain 100 50 No Limit3) 1.8 Min. No Limit 1.5
4 basins 50 75 4.0 1.8 to 4.4 0 0
Bowl urinals8) 50 75 No Limit3) 1.8 to 9.0 No Limit4) 1.5
Maximum of 8 WC’s6) 100 50 15.0 0.9 to 9.0 2 1.5
Up to 5 spray tap 30 Max. 50 4.53) 1.8 to 4.4 No Limit4) 0
basins9)
1) Steeper gradient permitted if pipe is less than maximum permitted length.
2) If length is greater than 3 m noisy discharge may result with an increased risk of blockage.
3) Should be as short as possible to limit problems with deposition.
4) Sharp throated bend should be avoided.
5) For slab urinal for up to 7 persons. Longer slabs to have more than one outlet.
6) Swept-entry branches serving WC’s.
7) Includes small potato-peeling machines.
8) Tubular not bottle or resealing traps.
9) Spray tap basin shall have flush-grated wastes without plugs.
Building Services Branch, ArchSD Page 32 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Table 9 - Limitations for ventilated branch discharge pipes in system III
Appliance Diameter Min. trap Max. length Pipe Max. number Max.
seal depth (L) of pipe gradient of bends drop (H)
from trap
outlet to stack
DN mm m % No. m
Washbasin, bidet 30 75 3.0 1.8 Min. 2 3.0
(30 mm diameter trap)
Washbasin, bidet 40 75 3.0 1.8 Min. No Limit 3.0
(30 mm diameter trap)
Shower, bath 40 50 No Limit2) 1.8 Min. No Limit No Limit
Bowl urinal 40 75 3.03) 1.8 Min. No Limit4) 3.0
Trough urinal 50 75 3.03) 1.8 Min. No Limit4) 3.0
Slab urinal5) 60 50 3.03) 1.8 Min. No Limit4) 3.0
Kitchen sink 40 75 No Limit2) 1.8 Min. No Limit No Limit
(40 mm diameter trap)
Household dishwasher 40 75 No Limit3) 1.8 Min. No Limit No Limit
or washing machine
WC with outlet up to 75 50 No Limit 1.8 Min. No Limit4) 1.5
6) and 14)
80 mm
WC with outlet greater 100 50 No Limit 1.8 Min. No Limit4) 1.5
6) and 14)
than 80 mm
Food waste disposal7) 40 Min. 758) 3.03) 13.5 Min. No Limit4) 3.0
8) 3)
Sanitary towel 40 Min. 75 3.0 5.4 Min. No Limit4) 3.0
disposal unit
Bath drain, floor drain 50 50 No Limit3) 1.8 Min. No Limit No Limit
Floor drain 70 50 No Limit3) 1.8 Min. No Limit No Limit
Floor drain 100 50 No Limit3) 1.8 Min. No Limit No Limit
5 basins 9) 50 75 7.0 1.8 to 4.4 2)
0
10 basins 9) and 10) 50 75 10.0 1.8 to 4.4 No Limit 0
Bowl urinals9) and 11) 50 75 No Limit3) 1.8 Min. No Limit4) No Limit
6)
More than 8 WC’s 100 50 No Limit 0.9 Min. No Limit No Limit
Up to 5 spray-tap 30 Max. 50 No Limit3) 1.8 to 4.4 No Limit4) 0
12)
basins
1) For maximum distance from trap to vent, see Figure 8.
2) If length is greater than 3 m noisy discharge may result with an increased risk of blockage.
3) Should be as short as possible to limit problems with deposition.
4) Sharp throated bends should be avoided.
5) For slab urinal for up to 7 persons. Longer slabs to have more than one outlet.
6) Swept-entry branches serving WC’s.
7) Includes small potato-peeling machines.
8) Tubular not bottle or resealing traps.
9) See Figure 9.
10) Every basin shall be individually ventilated.
11) Any number.
12) Spray tap basins shall have flush-grated wastes without plugs.
13) The size of ventilating pipes to branches from appliances can be DN 25 but, if they are longer than 15
m or contain more than five bends, a DN 30 pipe shall be used.
14) If the connection of the ventilating pipe is liable to blockage due to repeated splashing or submergence,
it should be DN 50, up to 50 mm above the spill-over level of the appliance.
Building Services Branch, ArchSD Page 33 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
3.2.7 Design Examples
Qtot = Qww + Qc + Qp
(i) Pipe 3
Continuity Equation: Q = V × A
Building Services Branch, ArchSD Page 35 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
m = Hydraulic mean depth = 1 × D/4 (Use 1/2 Bore)
i = Inclination or Fall of Pipe = 1:100 = 0.01
A = Sectional area (πD2/4) × Sectional area factor (0.5)
Hence, Q = [C ( m i )1/2 ] × A
Q = 0.001173 m3/s = 55×(1×D/4×0.01)1/2 × πD2/4×0.5
D5/2 = 0.00109
D = 0.065m
(ii) Pipe 4
Continuity Equation: Q = V × A
Hence, Q = [C ( m i )1/2 ] × A
Q = 0.000935 m3/s = 55× (1×D/4×0.01)1/2 ×πD2/4 × 0.5
D5/2 = 0.00087
D = 0.06m
Building Services Branch, ArchSD Page 36 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
4. Drainage System and Design – Below Ground Drainage
Notes:
Separate System
Advantage(s)
1. No risk for foul air passes through an unsealed rainwater gully trap
2. The sewage disposal plant size can be much smaller
3. The sewer purification cost is less
4. Pumping sot for sewage disposal is reduced as the surface water is
capable to flow by gravity to a nearby river
5. The risk of surface water disposal overloading is alleviated during heavy
rainfall because of separating from foul water disposal
Disadvantage(s)
1. Two sets of drains; increases the cost of building drainage
2. There is a risk of a wrong connection, e.g., a foul water branch drain may
be wrongly connected to a surface water drain
3. The foul water drain is not thoroughly flushed by rainwater
Building Services Branch, ArchSD Page 37 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Storm Foul
Location Water Classification Remarks
drain sewer
Rainwater *
Seawater used for the
Uncontaminated cooling water and the cooling of AC plants
*
like should be discharged
General directly
use Domestic wastewater *
Should be pre-treated,
where necessary, to
Commercial and industrial wastewater *
meet prescribed effluent
standards
Drainage outlets provided in covered
areas, including covered podiums and *
Covered other roofed areas
area Drainage in covered carparks, covered
lorry lading and unloading areas and * Via petrol interceptors
covered transport interchanges
Except in water
Swimming pool main drain, footbath
gathering grounds
main drain and swimming pool make-up *
where APs are advised
tank drain
Swimming to consult WSD
pool Swimming pool direct effluent from
*
routine operation (e.g. back washing)
Swimming pool direct effluent from
*
annual cleaning
Drainage outlets provided in open areas
and areas subjected to a substantial
amount of wind-blown rain, including *
open carparks, balconies, podiums,
Open area yards, etc.
Via a petrol interceptor
Drainage serving open transport that would allow storm
*
interchanges and cargo handling areas water bypass during
peak flow periods
Drainage outlets of verandas next to
kitchens and utilities rooms where a
Others *
substantial amount or wind-blown rain is
not expected
Building Services Branch, ArchSD Page 38 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
4.3 Storm Water System
After collecting the storm water from the roof down to the gully traps on ground
surface level by piping, the rainwater will be discharged by piping from the gully traps
to the manholes where considered as below ground system.
(A) All surface water from a building shall be discharged and connected by
rainwater pipe and drains within 30m of the building to the public sewer,
according to Cap.123I Reg. 41 on Disposal of surface water. Where there is
no such public sewer and no public channel or side channel in the street, the
surface water shall be conducted to a stream course or nullah subject to the
approval of SCCU or Building Authority.
i ΣσA
Q =
3600
(b) Combine Chezy Formula and Continuity Equation,
Qo = A C √HMD.S
Where Ao (cross sectional area of ¾ bore discharge),
C (Chezy Coefficient),
HMD (Hydraulic Mean Depth – on ¾ full) x D/4
Building Services Branch, ArchSD Page 39 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
From Figure (e), sectional area of ¾ bore discharge
Surface Wetted Hydraulic Mean
Proportional Section area
width perimeter mean depth depth
depth πD2/4
D πD D/4 D
0.05 0.436 0.144 0.019 0.130 0.034
0.10 0.600 0.205 0.052 0.254 0.068
0.15 0.714 0.253 0.094 0.371 0.103
0.20 0.800 0.295 0.142 0.482 0.104
0.25 0.866 0.333 0.196 0.587 0.177
0.30 0.917 0.369 0.252 0.684 0.216
0.35 0.954 0.403 0.312 0.774 0.257
0.40 0.980 0.436 0.373 0.857 0.299
0.45 0.995 0.468 0.436 0.932 0.345
0.50 1.000 0.500 0.500 1.000 0.393
0.55 0.995 0.532 0.564 1.059 0.445
0.60 0.980 0.564 0.625 1.111 0.502
0.65 0.954 0.597 0.688 1.153 0.567
0.70 0.917 0.631 0.748 1.185 0.641
0.75 0.866 0.667 0.805 1.207 0.730
0.80 0.800 0.705 0.858 1.217 0.842
0.85 0.714 0.747 0.906 1.123 0.996
0.90 0.600 0.795 0.948 1.192 1.241
0.95 0.436 0.856 0.981 1.146 1.768
1.00 0.000 1.000 1.000 1.000 ∞
Figure (e) - Geometrical functions for part-full circular sections
From Figure (f) graph C8, Value of Chezy’s coefficient with calculated
HMD known Qo = AoV
Building Services Branch, ArchSD Page 40 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Figure (f) – Coefficient of Friction chart
(C) For the selection of gully traps, according to Cap.123I, Reg. 58 on Gullies,
open trapped gullies should be used for outdoor rainwater collection and
covered with a suitable grating having openings equal to an area not less than
the cross sectional area of the outlet of the trap. Otherwise, sealed trapped
gullies should be used and adequate provision shall be made for the
ventilation of the space above the water level of the trap.
(D) After the rainwater collection by gully traps, the discharge shall be connected
to a manhole. Design of manhole shall comply with Cap.123I, Reg. 55 on
Manholes and cleaning eyes to be provided. Manholes shall be provided at
intervals not exceeding 60m in every drains and sewer. It shall also be
provided at major change in gradient or every change in direction in any
Building Services Branch, ArchSD Page 41 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
drains or sewer, except where: -
(b) the internal radius of the bend is not less than 6 times the internal
diameter of the drain or sewer; and
Type and drawings for standard manhole issued by DSD could be referred.
(E) A terminal manhole should be provided at the close proximity to the site
boundary for connecting to public sewer and drain. It is a demarcation
between the subject building development and the government. Terminal
manhole may not be required to be provided to storm water drainage system
if the connection to the public system is in exposed manner, for example
connected by open surface channel. As such, a catch pit is required for
collection.
4.3.3 Sizing of the Effective Volume (V) of Sump Pit for Pumped System
(A) Step 1: Determine the required discharge rainwater flow collected from Roof
floor and/or from the ground surface water by using Rational equation as
described above, i.e. Qin (litre/sec).
(B) Step 2: Identify the duty (Qout) in litre/sec of the sump pump (duty or standby)
for pumping away the rainwater from the sump pit by experience.
(C) Step 3: Counter-checking the duty cycle in a hour of the pump not more than
10 times for by the following simple equation:
V V
10 times x 60 min. ≦ +
Qin Qout - Qin
The effective volume (V) of the sump pit can be calculated.
4.4.1 Introduction
Building Services Branch, ArchSD Page 42 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
4.4.2 Building Soil and Waste Water from G/F
(A) All other underground drains must have an internal diameter of not less than
100mm if they carry soil water or trade effluent, and all systems must have
such means of access as may be necessary for inspection and maintenance,
which means the provision of rodding points, manholes and inspection
chamber.
(B) The position of internal manholes must be carefully considered for quickly
and easily accessible for the purpose of maintenance, inspection, testing,
cleaning and removal of any obstruction.
(C) The covers should be pressure tight to prevent sewer leaking out of the
chamber in the event of a blockage down stream.
(D) The sealed drainage systems are better used internally, and in critical areas
such as food preparation or chemical zones blockage indicators should be
fitted in the chambers.
(A) The design of the foul underground drainage external to the building should
follow the same rules as that of the internal system. Fewer manholes will be
required as there are likely to be fewer branch connections, consequently
fewer blockages may be experience due to the greater and more continuous
flow within the system.
(B) The positioning of access points and manholes must again be carefully
considered; they should not be positioned in roads or car parks, or in any
position where they may become inaccessible either due to obstructions,
traffic movement or hidden by landscaping or detritus. The gradient and
direction of the drainage routing should be taken account of the natural
ground contours and the existing potential clashing with other utilities.
(A) The drainage systems sometimes flow or discharge under the gravity free fall.
For example, drainage points below the sewer main and basement floor
toilets and kitchen where the employment of a sump and pump system is
under no other alternative choices to alleviate the drainage problem.
(B) The depression in a basement floor where water collects is known as a sump
Elevator pits are drained in this manner. Other countries like USA may term
this as a subdrain system.
(C) The wastes from a subdrain flow by gravity into a receiving tank, the
Building Services Branch, ArchSD Page 43 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
contents of which are automatically lifted and discharged into the gravity
drainage system. If the subdrain receives wastes containing oil, gasoline or
other flammable liquids, the discharge must first go through an oil interceptor
before entering the receiving basin. When the receiving basin collects the
discharge of sanitary wastes, it is called an ejector basin and the automatic
lifting and discharge equipment is called an ejector pump.
(A) Manhole
(a) Manholes are required to be employed to join the drain pipes are
change pipe direction at the underground. Most of the manholes, are
formed by reinforced concrete. Benching is provided inside the
manhole to guide the water flow. It is in fact a set of open channels
connecting the inlet pipes to the outlet pipe. The size of the manhole
depends on the number of inlet pipes and size of the outlet pipe. Also,
the depth of a manhole depends on the depth of the drain pipe which is
related to the length and gradient fall of the underground pipe.
(b) Terminal manholes are provided at the close proximity to the site
boundary for connecting to the public sewer and drain. It is a
demarcation between the private development and the government.
(c) Tyepe and size for the manhole could be referred DSD Standard
Drawings..
(a) The previous above ground drainage section has already described the
pipework materials of Bitumen coated cast iron pipe to BS EN877,
Hubless epoxy coated cast iron pipe, Galvanized Steel (GI) Pipe to BS
EN 10255 and Unplasticized PVC (uPVC) pipe to BS 4514. In this
section, Concrete and Vitrified Clay pipes would be desired.
(b) Concrete and Vitrified Clay pipes are usually used in civil works or
Building Services Branch, ArchSD Page 44 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
underground building drainage system but outside building structure.
Concrete pipe to BS 5911 are usually used in storm water drainage
system since concrete pipe with large size is not expensive. However,
protection should be applied when the underground pipe subjects to
heavy loading from ground surface (e.g. vehicles). A Vitrified Clay
pipe to BS EN 295 is usually adopted in underground drainage system
for conveying sewage water due to its good resistance to corrosion.
However, it is also a brittle material and requires good protection to
heavy loading.
(A) The layout of the system should be as simple and direct as possible and the
number of bends, traps and manholes kept to a minimum.
(B) The pipes should be laid in straight lines, from point to point.
(C) The pipes should be non-absorbent, durable, smooth in bore and of adequate
strength.
(E) Foul water drains should be well ventilated, to prevent the accumulation of
foul gases and fluctuation of air pressure within the pipe, which could lead to
the unsealing of gully or W.C. traps.
(F) All the parts of the drainage system should be accessible for inspection and
cleaning.
(G) The pipes should be laid to a self-cleansing gradient, which will prevent the
settlement of solid matter, which might lead to a blockage.
(H) The velocity of flow should not be less than 0.75m/s, which will prevent the
stranding of solid matter. A maximum velocity of 2m/s is acceptable, but the
upper limit is not considered important and on slopping sites the drain may
be allowed to follow the fall of the land. Large diameter sewers, however,
require ramps to restrict the fall on sloping sites, to permit workmen to make
necessary inspections and repairs.
(I) A foul water drain should never run at more than 90 per cent of its capacity.
This is equivalent to running at a depth of low equal to three-quarters of the
bore. This maximum discharge, together with adequate ventilation, will
prevent the possibility of compression of air in the drain, which could cause
unsealing of traps. Surface water drains may be designed to run at full bore.
Building Services Branch, ArchSD Page 45 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(J) Pipes should not pass under a building unless absolutely necessary and pipes
should not be laid close to building foundations.
(K) Pipes should not pass near trees because of the possibility of damage by the
roots.
(L) Where possible, flexible joints should be used and pipes under buildings
should have flexible joints and means of access.
(M) Where pipes pass through walls, relieving arch or lintel should be provided in
the wall above the pipes to prevent the wall load bearing on the pipe.
(N) Bends in pipes should have a large radius of between 215 and 750mm for
100mm diameter pipes and between 225 and 900mm for 150mm diameter
pipes.
(P) Drain pipes should be at least 900mm below roads and at least 600mm below
fields and gardens.
(Q) Where pipes are not under a road and the depth below ground is less than
600mm, 2 pre-cast concrete slabs should be laid over the pipes, so that the
load transmitted to the pipe walls is at points of about 22.30hr and 13.30hr.
There should be a minimum thickness of 150mm of soil, free from large
stones, building rubbish, tree roots, vegetable matter and large lumps of clay.
Alternatively, broken stone or gravel 10mm nominal single size may be
placed between the concrete slabs and the top of the pipe.
(A) Start at the first manhole at the head of the main drainage route.
(B) Look at the most convenient last manhole position with regard to the
Government sewer and drain positions.
(C) Layout the manholes-try the simplest layout with the minimum number.
(D) Link up the manhole with drains or sewers with consideration to the
followings:
(F) The drain/sewer should always design on the gravity drainage system. Avoid
the sump and pump system unless this is the last solution.
(G) The drain/sewer should always design on the gravity drainage system. Avoid
the sump and pump system unless this is the last manhole.
(H) Sizing the drain-size, levels, check cross over drain/sewers, penetration
through the beams and structure.
(A) Manhole sizes, back drop manholes requirements, provision inside the last
manholes.
(A) Flow rates (L/s): these have been established for each section of
above-ground drainage for foul water systems.
(B) Gradient: this is generally derived from the topography of the site with any
allowance for limiting velocity taken up with backdrops as necessary.
(C) Length (m): the distance between one below-ground drainage connection and
the next.
(D) Velocity (m/s): there are distinct limits to the allowable velocity of effluent in
a below-ground system. For general design work, a velocity of not less than
0.6m/s and more normally 1m/s should be taken for a pipe running full. Since
the outflow is variable, it should be noted that the velocity could fall as low
as 0.4m/s at quarter depth and this would be the limiting “self-cleaning”
velocity. However it is also essential to avoid scouring and velocities in
excess of 3 m/s should be avoided by the use of backdrop manholes.
Building Services Branch, ArchSD Page 47 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(E) Invert level (m)
(F) Material: the material used will affect the performance of the drain due to its
surface roughness. For more detail, please refer to previous above-ground
drainage section 2.26 Hydraulic Calculation.
(A) Example 1
What velocity and total capacity will be given by a 100 mm drain at 1/3
depth, laid to a gradient of 1 in 50?
Solution
(B) Example 2
Solution:
V = 1 m/s
C = 55
HMD = 0.15/4 = 0.0375
V2 12
s = = = 0.0088
C2 × HMD 552 × 0.0375
Gradient = 1/0.0088, i.e. 1 in 113
(C) Example 3
Data: 20 houses
4 persons / house
Building Services Branch, ArchSD Page 48 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
460 L/head/day
Maximum rate of flow is L/s from 4 to 6 times
Av. rate of flow = half consumption in L/head/day x population
Solution:
V2 12
s = = = 0.01185
C2 × HMD 552 × 0.0279
Gradient = 1/0.01185, i.e. 1 in 84.3
(D) Example 4
Block 1 Block 2
MH MH
Block 3 Block 4
Calculate the size of pipe necessary to take the foul flow from 4 blocks of
flats, each having 74 families. Assume 3.5 persons per flat, water
consumption 460 L/head/day and a maximum flow of 6 times the average.
The pipe will be laid a fall to produce a velocity of 1 m/s when full.
Building Services Branch, ArchSD Page 49 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Solution:
V2 12
s = = = 0.01185
C2 × HMD 552 × 0.075
Gradient = 1/0.0044, i.e. 1 in 227
Average flow – The average flow rate / person over 24 hours appears to be
about 19 L, but calculations cannot be based on this assumption as the bulk
of the flow occurs during a few hours of the day only (9 a.m. to 3 p.m.). It
is suggested that in the absence of other information, assume that half the
daily flow occurs over 6 hours period, e.g. say 230 in 6 hours (average).
(E) Example 5
Building Services Branch, ArchSD Page 50 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(a) Design Flow Calculation by Discharge Unit for Manhole 1 (refer to
Section 2.2.7)
(b) Pipe work sizing for pipe work connecting from Manhole 1 to Manhole
2 (Pipe 5)
ks 2.51v
V = √ (8g D s) log ( + )
3.7D D√(2g D s)
Assume the effective roughness of ks = 1.0mm and clean water
with a viscosity of V = 1.31*10-6
Hence, Q = [ C ( m i )1/2 ] × A
where, C = Chezy Coefficient / Constant = 58
m = Hydraulic mean depth = 1 × D/4 (Use 1/2 Bore)
i = Inclination or Fall of Pipe = 1:40 = 0.03
A = Sectional area of pipe (πD2/4)×Sect area factor (0.5)
(c) Pipe work sizing for pipe work connecting from Manhole 2 to Manhole
3 (Pipe 6)
Building Services Branch, ArchSD Page 52 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(i) Method 1, By Colebrook-White Equation,
ks 2.51v
V = √ (8g D s) log ( + )
3.7D D√(2g D s)
Assume the effective roughness of ks = 1.0mm and clean water
with a viscosity of v = 1.31*10-6
Hence, Q = [ C ( m i )1/2 ] × A
where, C = Chezy Coefficient / Constant = 55
m = Hydraulic mean depth = 1 × D/4 (Use 1/2 Bore)
i = Inclination or Fall of Pipe = 1:40 = 0.03
A = Sectional area of pipe (πD2/4)×Sect area factor (0.5)
Building Services Branch, ArchSD Page 53 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
5. Other Drainage Accessories
A grease trap is a device used for removing oil and grease from wastewaters. Oil and
grease in wastewater arising from normal operations of restaurants and food
processing factories will need to be separated out by means of grease traps, before the
wastewater is discharged from the premises to the sewer system. The oil and grease
intercepted by grease traps, usually known as grease trap waste, needs to be removed
regularly in order to ensure the proper functioning of the grease traps.
Building Services Branch, ArchSD Page 54 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
5.1.2 Grease Trap Capacity Requirements
A B C D
Example Internal Dimensions
Average Minimum
Kitchen Floor (mm)
Hourly Water 2 Grease Trap
Area (m ) Total
Use (L) Capacity (L) Length Width
Depth
0 - 125 250 1200 525 600
250 8 490 1450 700 725
500 16 790 1700 825 850
750 24 1,050 1800 875 1000
1,000 32 1,220 1950 950 1000
Note that the length and width dimensions given in the table do not include
wall and cover thickness for concrete grease traps (typically 150 mm). For
steel traps, wall thicknesses can be ignored.
(A) A new restaurant is planned with 30 m2 of kitchen floor area. From the table
above, the grease trap capacity required is just under 1,220 L; approximately
1180 L.
(B) Food processing factories may require additional capacity or more advanced
equipment for grease and oil removal and are recommended to seek expert
advice in any case.
(C) Column D of the table gives examples of grease trap dimensions that will
provide both the required capacity and the length, width and depth
relationships.
(D) In fact, there are many combinations of length, width and depth that will
meet the dimensional criteria for a given grease trap capacity. But the liquid
depth must be no greater than 1200 mm (and the total depth no greater than
1800 mm) for grease traps in the size range considered here.
Building Services Branch, ArchSD Page 55 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
5.2 Petrol / Oil Interceptor
(d) any matter likely to injure any drain or sewer or to interfere with the
free flow of its contents or to affect prejudicially the treatment or
disposal of its contents.
The Building Authority may require the owner of the building to provide
neutralizing tanks, cooling tanks, petrol intercepting traps, grease traps or
other suitable provision.
(C) In additional, Practice Note for Authorized Persons & Registered Structural
Engineers (PNAP) 124 also stipulates the requirement of the petrol/oil
interceptor. It states the arrangement for the treatment of effluent in flatted
factory & single occupancy factory and the type of treatment for different
kinds of effluent. In fact, the servicing and parking of vehicles are required to
provide a petrol interceptor.
Building Services Branch, ArchSD Page 57 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
Building Services Branch, ArchSD Page 58 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
6. Legislations for Drainage System Design
(1) Every ventilating pipe for any drain or sewer shall be carried up to a
height not less than 1 m above the roof of the building to which it is
fixed or, where such building has a pitched roof, above the eaves of
such building. (L.N. 294 of 1976)
(2) No ventilating pipe shall be so fixed as to permit the escape of foul air
from any drain, sewer, soil pipe or waste pipe into any building.
(3) Soil pipes or waste pipes may be carried up to a suitable height above
the building to which they are fixed to act as ventilating pipes for any
drain or sewer.
(4) The internal diameter of every ventilating pipe and of every soil pipe or
waste pipe which, under paragraph (3), is acting as a ventilating pipe,
shall be not less than 80 mm. (L.N. 294 of 1976)
(5) The open end of every ventilating pipe shall be provided with a suitable
grating having apertures of an aggregate area not less than the sectional
area of the pipe.
(6) Ventilating pipes shall not be used for the carriage of surface water.
(1) (a) Every rain water pipe which discharges to a drain which is
connected to a public sewer provided for the carriage of surface
water shall-
(c) Every rain water pipe which discharges, through a cast iron
conductor, to the side channel in a street shall be provided, at the
foot thereof, with a shoe so as to ensure that any surface water
discharged from the pipe will discharge directly into the
conductor.
(2) The number and size of rain water pipes provided for any building shall
be calculated at the rate of 700 square millimetres of pipe to every 10
square metres of horizontal roofed-over surface.
(3) Save as provided in regulation 33, the diameter of every rain water pipe
shall be not less than 65 mm.
(4) Rain water pipes shall not be connected with any soil pipe, waste pipe
or ventilating pipe.
(5) Where a rain water pipe discharges, across any footpath, to the side
channel of a street, it shall discharge through a cast iron conductor.
6.1.3 Cap 123I Reg.33 Rain water pipes for verandahs or balconies
(1) Any rain water pipe provided for the carriage of surface water from a
verandah or balcony shall, where there is, at a suitable position, a rain
water pipe provided for the carriage of surface water from the roof of
the building, be connected to such pipe.
(2) Where a rain water pipe provided for the carriage of surface water from
a verandah or balcony discharges to the side channel in a street or is, in
accordance with paragraph (1), connected to a rain water pipe which so
discharges, the internal diameter of the rain water pipe from the
verandah or balcony shall be not more than 40 mm.
(1) Every soil pipe, waste pipe, anti-syphonage pipe, ventilating pipe,
overflow pipe and every pipe connected with any drain provided for the
carriage of foul water shall be-
(2) Every rain water pipe shall be constructed of cast iron, copper or other
approved material. (L.N. 295 of 1986)
(3) All such materials shall be sound and free from defects.
Building Services Branch, ArchSD Page 60 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
6.1.5 Cap.123I Reg.35 Connexions of pipes, etc.
(1) Every soil pipe, waste pipe and rain water pipe shall be securely fixed
to the wall of the building for which it is provided.
(2) Any hole which is made in any floor or wall in order to admit any such
pipe shall be properly filled in and sealed round the pipe.
Where a soil pipe, waste pipe, anti-syphonage pipe, ventilating pipe, or rain
water pipe is fixed in a duct within a building, access panels shall be
provided of such size and so situated that adequate access is available to all
pipe connexions within the duct.
(2) The size of eaves gutters shall be calculated at the rate of 700 mm2 of
cross sectional area of gutter to every 7 m2 of horizontal roofed-over
surface. (L.N. 294 of 1976)
Every building shall be provided with such pipes, drains and channels as are
necessary for the disposal of all foul water and surface water from the
building.
(1) Save as provided in paragraph (2), all surface water from a building
shall, if there is a public sewer, provided for the carriage of surface
water, at a suitable level and position within 30 m of the building, be
conducted, by means of rain water pipes and drains provided for the
Building Services Branch, ArchSD Page 61 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
carriage of surface water, to such public sewer or, where there is no
such public sewer, shall be conducted, to the satisfaction of the
Building Authority, to a public channel provided for the carriage of
surface water or to the side channel in a street. (L.N. 294 of 1976)
(2) Where there is no such public sewer and no public channel or side
channel in a street, such surface water shall be conducted, to the
satisfaction of the Building Authority, to a stream course or nullah.
6.1.11 Cap 123I Reg. 42 Pipes carrying surface water not to discharge across
surface of footpath
No pipe provided for the carriage of surface water from a building shall
discharge across the surface of any footpath in a street.
(1) Covered drains (except covered drains provided for the carriage of
sub-soil water) and covered sewers shall be made with good sound
pipes of glazed earthenware, stone ware, concrete, cast iron or other
approved material.
(2) Drains and sewers above the ground shall be laid with cast iron pipes or
other approved materials. (L.N. 361 of 1980)
(3) All pipes used in the construction of any drain or sewer shall-
(c) be impervious.
(4) Cast iron sewage pipes shall be protected against rust and corrosion by
a suitable asphaltic coating.
(a) in the case of pipes with a diameter not exceeding 150 mm, have
a thickness equal to not less than one-ninth of the diameter of the
pipe; and
(b) in the case of pipes with a diameter exceeding 150 mm, have a
thickness equal to not less than one-twelfth of the diameter of the
pipe. (L.N. 294 of 1976)
Building Services Branch, ArchSD Page 62 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
6.1.14 Cap. 123I Reg. 45 Sub-soil water drains
Drains provided for the carriage of sub-soil water shall be constructed with
clay field pipes or other suitable pipes and shall be laid to adequate falls.
All drains and sewers shall be of adequate, but not excessive, size for the
purpose for which they are provided: Provided that no covered drain shall
have an internal diameter of less than 100 mm.
(1) All drains and sewers (except drains provided for the carriage of
sub-soil water) and traps shall be firmly laid on a bed of concrete not
less than 100 mm in thickness and at least 150 mm wider than the
diameter of the pipe or trap, and shall be haunched with concrete so
that the full width of the bed is carried up to the level of the horizontal
diameter of the pipe and from that point splayed up on both sides of the
pipe from the full width of the bed to meet the pipe barrel tangentially.
(L.N. 294 of 1976)
(2) All drains and sewers shall be supported along the full length of the
barrels and not by the sockets.
(3) Where any drain or sewer is laid in soft and yielding ground-
(a) adequate support shall be provided for such drain or sewer; and
(b) save where the same are provided for the carriage of sub-soil
water, the pipes shall be completely surrounded by at least 100
mm of concrete. (L.N. 294 of 1976)
(4) Cast iron pipes above the ground may be carried on adequate piers or
other sufficient supports, if such support is provided at each joint.
(1) The junction of a single branch drain with another drain at an angle of
not more than 45o in the direction of flow may be made by means of a
purpose-made Y junction.
(2) The junction of every other branch drain with another drain shall be
made within a manhole, obliquely at an angle of not more than 60o in
the direction of flow of such other drain, and shall be above the invert
of such other drain.
6.1.18 Cap. 123I Reg. 54 Drains and sewer under buildings, etc.
(1) All drains and sewers under a building shall be laid in straight lines and
shall be laid with cast iron sewage pipes.
Building Services Branch, ArchSD Page 63 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(2) Where any drain or sewer is laid through any building, or where any
building is constructed over any drain or sewer, relieving arches or
beams shall be provided to protect such drain or sewer and to prevent
any load from the building being transmitted to such drain or sewer.
(ii) the internal radius of the bend is not less than 6 times the
internal diameter of the drain or sewer; and
(1) Every manhole shall be of such size and form as to allow ready access
for rodding and shall be constructed of-
(3) Benchings shall be formed above the level of every drainage channel in
a manhole to fall towards such channel at a gradient of 1 in 2.
(4) The benchings and all the internal faces of every manhole shall be
rendered with cement mortar so as to provide a smooth and impervious
surface.
(5) Every drainage channel in a manhole shall be not less than half round
glazed earthenware or cement rendered, and shall have a diameter not
less than that of the largest drainage inlet into and not more than that of
the outlet from the manhole.
(6) Every drainage inlet to a manhole shall discharge into the drainage
channel therein with properly made bends constructed within the
benching of the manhole.
Building Services Branch, ArchSD Page 64 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(7) Every manhole shall be fitted, on a level with the ground surface, with
a cast iron airtight cover of adequate strength and approved design:
Provided that every manhole inside or under a building shall be fitted
with a double-sealed cast iron airtight cover. (L.N. 361 of 1980)
(d) to an inlet to a drain used solely for the conveyance of rain water
from a roof.
(1) Every drain provided for the carriage of foul water shall be ventilated
at its highest point by means of a ventilating pipe having an internal
diameter of not less than 50 mm. (L.N. 294 of 1976)
(3) Branch drains shall be ventilated at their highest point, if the Building
Authority so requires.
(1) Open trapped gullies shall be covered with a suitable grating having
openings equal to an area not less than the cross sectional area of the
outlet of the trap.
(2) Where sealed trapped gullies are used, adequate provision shall be
made for the ventilation of the space above the water level of the trap.
(2) Suitable grilles shall be provided to prevent sand, silt and other debris
from entering any public sewer, public channel, nullah or stream
course.
Building Services Branch, ArchSD Page 65 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009
(3) A cover in a foot-path to a channel for the carriage of surface water
shall be flush with the path surface and any hole in such cover or
between such cover and another shall not exceed 20 mm in one
dimension. (L.N. 366 of 1984)
(1) The ground surface of every external area of every building unless
landscaped shall be suitably paved.
(2) Such surface paving shall be laid to fall at a gradient of not less than 1
in 80 to a gully trap or drainage channels connected to a surface water
drain.
Building Services Branch, ArchSD Page 66 of 66 Filecode: Design Guide for Drainage Installation.doc
Design Guide for Drainage Installation YCW/CL
Issue Date: 18 May 2009