Professional Documents
Culture Documents
g
These instructions do not purport to cover all details or variations in equipment, nor to
provide for every possible contingency to be met during installation, operation, and
maintenance. The information is supplied for informational purposes only, and GE makes
no warranty as to the accuracy of the information included herein. Changes,
modifications and/or improvements to equipment and specifications are made
periodically and these changes may or may not be reflected herein. It is understood that
GE may make changes, modifications, or improvements to the equipment referenced
herein or to the document itself at any time. This document is intended for trained
personnel familiar with the GE products referenced herein.
GE may have patents or pending patent applications covering subject matter in this
document. The furnishing of this document does not provide any license whatsoever to
any of these patents.
This document contains proprietary information of General Electric Company, USA and
is furnished to its customer solely to assist that customer in the installation, testing,
operation, and/or maintenance of the equipment described. This document shall not be
reproduced in whole or in part nor shall its contents be disclosed to any third party
without the written approval of GE Energy.
GE provides the following document and the information included therein as is and
without warranty of any kind, expressed or implied, including but not limited to any
implied statutory warranty of merchantability or fitness for particular purpose.
Revised: 080225
Issued: 050203
Fax No.
Your Company’s Name and Address Job Site
Phone No.
GE Requisition No.
E-mail
Your Job Function / How You Use This Publication Publication No.
Address
General Rating
Excellent Good Fair Poor Additional Comments
Contents { { { { ____________________________________________________________
Organization { { { { ____________________________________________________________
Technical Accuracy { { { { ____________________________________________________________
Clarity { { { { ____________________________________________________________
Completeness { { { { ____________________________________________________________
Drawings / Figures { { { { ____________________________________________________________
Tables { { { { ____________________________________________________________
Referencing { { { { ____________________________________________________________
Readability { { { { ____________________________________________________________
Specific Suggestions (Corrections, information that could be expanded on, and such.)
Page No. Comments
_____ _________________________________________________________________________________
_____ _________________________________________________________________________________
_____ _________________________________________________________________________________
_____ _________________________________________________________________________________
_____ _________________________________________________________________________________
_____ _________________________________________________________________________________
Other Comments (What you like, what could be added, how to improve, and such.) ________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
Overall grade (Compared to publications from other manufacturers of similar products, how do you rate this publication?)
{ Superior { Comparable { Inferior { Do not know Comment ____________________________________________
____________________________ Place
stamp
____________________________ here.
____________________________
GE Energy
Documentation Design, Rm. 293
1501 Roanoke Blvd.
Salem, VA 24153-6492 USA
Index I-1
Introduction
Refer to Figure 1-1 and 1-2. This document provides recommended preventive maintenance, component
replacement, and general troubleshooting procedures for the LS2100 Static Starter
Control (LS2100).
Chapter 1 provides an overview of this document.
Section Page
Figure 1-2. 8.5 MVA LS2100 Static Starter Control Power Conversion Cabinet
Figure 1-4. 14 MVA LS2100 Static Starter Control Power Conversion Cabinet
From the Help menu (above), select Contents to access online help files, which
contain fault, function, and wizard information also provided in this manual.
Safety Equipment
Site-specific safety/confined space manual
Personal safety gear (for example; safety boots, safety glasses, hard-hat, high-
voltage gloves, face shield, safety jacket)
High voltage ac/dc detector (with an insulated pole of appropriate length)
Locks and tags, danger and caution tape
Protective grounding cables and grounding stick
Static-charge wrist straps
Note Please have the GE requisition or shop order number and the equipment serial
or model number available to exactly identify the equipment when calling. Serial
number is on the rating nameplate located on the inside of the control cabinet door.
Related Documents
For more information, refer to the LS2100 documents in Table 1-1, as applicable.
Printed wiring boards in the static starter are located in the control, and power
conversion cabinets. Refer to Table 1-2 for board locations, catalog numbers, and
individual board documents.
Document Distribution
GE Energy supplies product documents to its customers to support the equipment
provided for each requisition. The contract documents define the terms of the
document distribution.
If provided (per contract), the following documents contain requisition information
about the LS2100.
Requisition drawings, including outlines, layouts, and elementary diagrams
Renewal Parts listing
Note If differences exist between the general product documentation and the
requisition documentation, the requisition documentation should be considered the
more exact representation of your equipment or system configuration. Refer to the
section, How to Get Help for information on contacting GE to obtain any required
documentation.
Catalog (Part)
Number Board/Module Cabinet Location Document
DS200ADMA Analog to Digital Daughter board Control GEI-100218
DS200DDTB Auxiliary I/O Terminal board Control GEI-100219
DS200DSPC Digital Signal Processor board Control GEI-100220
DS200FCGD Gate Distribution and Status board Control GEI-100221
DS200FCSA Current Sensor Interface board Power Conversion GEI-100222
DS200FGPA Static starter Gate Pulse Amplifier board Power Conversion GEI-100223
DS200FHVA High Voltage Gate Interface board (14 MVA) Power Conversion GEI-100224
IS200FHVB High Voltage Gate Interface board (8.5 MVA) Power Conversion GEI-100530
DS200NATO Voltage Feedback Scaling board Power Conversion GEI-100225
IS215UCVEH2 Unit Controller board Control GEH-6421
DS200VBPL Static Starter backplane Control GEI-100227
Introduction
Preventive maintenance helps to detect and correct conditions that could cause
equipment malfunction. This includes inspections for damage and wear, tests, and
cleaning of equipment at regular intervals. This chapter provides guidelines for
preventive maintenance and is organized as follows:
Section Page
Maintenance Schedule..............................................................................................2-2
Maintenance Record.................................................................................................2-2
Maintenance Procedures...........................................................................................2-2
Before Beginning .......................................................................................2-2
Procedure List ............................................................................................2-3
Fan Replacement Intervals .........................................................................2-3
Dust Removal.............................................................................................2-4
Cleaning Up Oil or Similar Fluids .............................................................2-5
Loose Connections .....................................................................................2-5
Damaged Insulation ...................................................................................2-6
Contactors and Relays................................................................................2-6
Printed Wiring Boards/Modules.................................................................2-6
Short-Circuit Damage...............................................................................................2-7
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 2 Preventive Maintenance • 2-1
Maintenance Schedule
For maximum benefit, preventive maintenance needs to be performed at scheduled
intervals by a qualified technician. The required frequency for each procedure
depends on:
• How much the equipment is used
Refer to GEH-6679, LS2100 • Ambient environmental conditions
User’s Guide for
environmental specifications. It is recommended that preventive maintenance be performed at least once every two
months in environments that do not meet specifications and on normally scheduled
shutdowns in environments that do meet the environmental specifications. The
schedule should include an inspection of wiring and components before re-applying
power.
Maintenance Record
GE recommends keeping a detailed record of maintenance (such as a log book) for
every static starter. This record serves two purposes:
• Verifies that all equipment is routinely checked
• Aids troubleshooting and prevention of equipment failure by providing a history
of equipment maintenance and problems
Maintenance Procedures
These procedures involve cleaning the equipment and checking for wear and damage
through visual inspection and functional tests.
Before Beginning
To prevent electric shock make sure all power supplies to
the static starter cabinets are turned off. Ground and
discharge equipment before performing any adjustments,
servicing, or other acts requiring physical contact with the
electrical components or wiring.
Before performing any procedures in this section, the static starter must be de-
energized. Do not deviate from the stated de-energizing procedures. If safety
requirements cannot be met completely, or if you do not understand them, do not
work on the equipment.
2-2 • Chapter 2 Preventive Maintenance LS2100 Reference and Troubleshooting Guide GEH-6680B
Procedure List
The following procedures should be performed at appropriate intervals determined
by the environment. Refer to subsequent sections in this chapter for detailed
procedures.
1. Remove dust and dirt from cabinets and electrical components.
2. Check all screw and bolt connections.
3. Inspect wiring for abrasive wear, burns, or melted wire insulation.
4. Inspect all boards: plugs, connectors, wiring, fiber-optic connections.
5. Inspect pumps and the muffin fans for correct operation and rotation.
6. Inspect dc output contactors.
7. Verify integrity and the proper operation of the space heaters (located in control
pump, and power conversion cabinets).
When inspections have been completed, energize the control system and verify its
correct operation. Use a pc or the keypad to communicate to the control and correct
all reported alarms and faults.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 2 Preventive Maintenance • 2-3
Dust Removal
Tracking involves a build-up Build-up of dust on components can increase operating temperature, thus reducing
of electrical charge along the their normal life. On standoff insulators, it can collect enough moisture to produce a
wire surface, which can cause current path from bus bars to chassis ground. Dust (especially metallic dust) on wire
intermittent problems that are surfaces can cause tracking between connector pins.
hard to find.
¾ To remove dust from the static starter components
1. Clean bus bars and standoff insulators with a clean dry cloth – do not use any
solvents.
2. Using a fine-filtered vacuum cleaner with a non-metallic nozzle, remove dust
and dirt from wiring and electrical components.
3. Inspect cabinet air filters, if equipped. Shake or vacuum filters clean, or replace,
as required.
After cleaning, examine the parts for pitting or other signs of metal deposits on
insulation or insulated parts. If parts are pitted, do not reuse.
2-4 • Chapter 2 Preventive Maintenance LS2100 Reference and Troubleshooting Guide GEH-6680B
Cleaning Up Oil or Similar Fluids
If oil or other similar fluids have accumulated inside the cabinets (such as from a
power device failure), clean them. Use a cleaner strong enough to remove
contaminates, but one that does not harm the components or leave a residue.
Other good products are • A recommended product is Axarel MicroCare 2200 (best for printed wiring
citrus-based solvents. boards and other delicate devices).
• After cleaning, examine the parts for pitting or other signs of metal deposits on
insulation or insulated parts. If parts are pitted, do not reuse.
• Contaminated Nomex insulation should not be reused.
Note Normal household cleaners (such as 409) may leave a salt residue behind, so
must not be used.
Loose Connections
Vibration during equipment operation can loosen mechanical and electrical
connections and cause intermittent equipment failure. Additionally, dust and
moisture in loose connections can cause loss of low-level signals at terminal boards
and also thermal runaway at bus connections.
¾ To check connections
1. Check all hardware and electrical connections by attempting to move the
device/wire, and tighten if needed.
2. Tighten or replace any loosened crimp-style lugs.
3. Tighten or replace all loose or missing hardware.
4. Inspect printed wiring boards for correct seating, and verify that any plugs,
wiring, and bus connectors are tight.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 2 Preventive Maintenance • 2-5
Damaged Insulation
Wires and cables with damaged insulation are dangerous when carrying electricity.
They can also intermittently short, causing equipment and functional failure.
2-6 • Chapter 2 Preventive Maintenance LS2100 Reference and Troubleshooting Guide GEH-6680B
Short-Circuit Damage
If a short-circuit occurs, overcurrent protective devices on the circuit should cut off
power to the equipment. This normally prevents electrical damage, except at the
point of the short. However, the heat produced by an electrical arc can carbonize
some organic insulating materials, which then lose insulating qualities.
After repairing the cause of the short-circuit and before re-energizing the static
starter:
• Inspect the system thoroughly for damage to conductors, insulation, or
equipment. Replace, if found (refer to section, Damaged Insulation).
• Check insulation resistance.
• Inspect the overcurrent protection devices for damage to insulation and contacts
(refer to section, Contactors and Relays). Replace or repair, as needed.
• Check and replace any open fuses.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 2 Preventive Maintenance • 2-7
Notes
2-8 • Chapter 2 Preventive Maintenance LS2100 Reference and Troubleshooting Guide GEH-6680B
Chapter 3 Parts Replacement
Introduction
Replaceable parts of the LS2100 are located in the control, pump, and power
conversion cabinets. Some parts in the control cabinet are replaceable online
(energized). There are no online replaceable parts in the control or power conversion
cabinets. The information is organized as follows:
Section Page
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-1
Safety Precautions and Replacement Guidelines
With power applied, this equipment contains a potential
hazard of electric shock or burn. Only adequately trained
persons who are thoroughly familiar with the equipment and
the instructions should maintain this equipment.
To prevent electric shock while servicing the equipment,
personnel must understand and follow all safety requirements
for working around dangerous voltages. Make sure that all
power sources to the equipment are turned off, then ground
and discharge the equipment before performing any
adjustments, servicing, or other acts requiring physical
contact with the electrical components or wiring.
Before starting any replacement procedures, make sure that shutting down the
equipment does not interfere with plant operations.
Note It may be necessary to clean the static starter before beginning replacement
procedures. Clean the static starter per the sections, Dust Removal and Cleaning Up
Oil or Similar Fluids in Chapter 2.
Refer to section, The following are guidelines for performing any parts replacement procedure:
Equipment/Material Needed, • Strictly follow all safety precautions and lock-out/tag-out procedures.
in Chapter 1 for tools and
equipment needed to perform • Always install wiring in the routing as when it was removed. The wiring should
replacement procedures. be labeled before being disconnected so that it can be connected in the same
location. Wire routing is important due to interference and partial discharge
control.
• Follow the recommended torque requirements as in Table 3-1.
• Carefully terminate all fiber-optic cables and observe the minimum bend radius
of 2 in (52 mm) for all cables. (Refer to GEH-6678, LS2100 Installation and
Startup Guide, for complete fiber-optic cable recommendations.)
• Always reinstall any baffles, covers, or other items removed to gain access to
parts being replaced.
3-2 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
Control Cabinet
All boards and components must be replaced only when the LS2100 is de-energized.
See section De-energizing Procedure for the LS2100 Lineup.
Control power
circuit breakers
Control power
transformer and
power supply
Panel mounted
relays
VersaMax I/O
modules
Auxiliary I/O
Terminal
Board
Customer
terminal boards
Note For detailed control cabinet component layout information, refer to the device
nomenclature sticker, 151X1212CA01NP01, located on the back of the control
cabinet door.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-3
¾ To change the keypad
1. Disconnect all cables from the keypad.
2. Remove the keypad mounting screws and remove the keypad.
3. Orient new keypad in the same position as the one removed, and mount it with
the screws removed in step 2.
4. Tighten hardware per Table 3-1.
5. Reconnect all cables disconnected in Step 1.
6. Perform any necessary hardware verifications and tests. Refer to GEH-6678,
LS2100 Installation and Startup Guide.
¾ To replace boards
1. Replace the board per the replacement instructions in the applicable individual
board document (refer to Table 1-2 for document listing).
2. Perform any necessary hardware verifications and tests. Refer to GEH-6678,
LS2100 Installation and Startup Guide.
Note It is not safe to download the code to flash memory on the static starter while it
is in operation. At the end of the process, the system is reset and the static starter will
trip.
3-4 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
¾ To replace the control rack fan
1. Verify that the connector to the fan is correctly labeled, then disconnect it (see
Figure 3-2).
2. Remove the fan mounting hardware, then remove the fan. (Do not drop anything
into the control).
3. Orient the new fan in the same position as the one removed and set it into place.
4. Secure the new fan with the mounting hardware removed in step 2. Tighten per
Table 3-1.
5. Reconnect the connector that was disconnected in step 1.
6. Perform any necessary hardware verifications and tests. Refer to GEH-6678,
LS2100 Installation and Startup Guide.
Single muffin
fan
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-5
Pump Cabinet
The drive uses a liquid cooling system to transfer heat from heat producing devices
(such as Silicon Controlled Recifiers (SCR) and high wattage resistors) to a heat
exchanger.
The liquid cooling system is a closed-loop system with a covered reservoir for
makeup coolant (see Figure 3-3). Coolant circulates from the pump discharge, to the
heat exchanger, to the power conversion bridges, and returns to the pump. A portion
of the coolant bypasses to a deionizer system to maintain the coolant resistivity.
The liquid cooling system has the following features:
• Self-venting, closed-loop cooling system that uses a water and propylene glycol
mixture
• Full-capacity coolant circulation pump
• Redundant circulation pumps with automatic changeover and isolation valves
for maintenance
• Full capacity heat exchanger, either remote liquid-to-liquid or liquid-to-air with
cooling blower and optional redundant heat exchanger blowers with automatic
changeover
• Purity alarm monitor with digital resistance and temperature display and
contacts for alarm and trip
• Translucent coolant storage reservoir with cover and contacts for overflow
alarm, low-level alarm and low-level trip
• Deionizer system with isolation valve for maintenance
• Gauge pressure switch
• Pressure gauge
• Drain valves
• Temperature-regulating valve
3-6 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
CLF2: PUMP HIGH LEVEL FAULT
CAP VENT
(FILL
HERE)
MOTOR STARTERS-
M1-M4. M3 & M4 ARE
OPTIONAL WITH
COOLANT WATER TO AIR HEAT
RESERVOIR EXCHANGER
M1 M4
CLF1: PUMP
LOW LEVEL
FAULT
CTRS:
INLET
RESISTIVITY/
TEMPERATURE
OUTLET SENSOR
CWP1 PUMP1
DEIONIZER
FILTER
INLET
PRESSURE CHARCOAL
SWITCH FILTER
PRESSURE
GAUGE
CWP2 PUMP2
FLOW
FROM STRAINER
BRIDGE
3-WAY
DIVERTER
FLOW TO VALVE
BRIDGE
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-7
Routine Maintenance
Check the following items monthly to make sure the liquid cooling system is
properly maintained:
• Check the propylene glycol concentration and replenish the coolant, as
necessary.
• Keep the cooling system free from contamination.
• Keep the reservoir covered.
• Clean the strainers.
• Check the coolant resistivity. The life of the carbon filter and deionizer depends
upon the operating temperatures and quality of makeup coolant. If possible, they
should be replaced before the coolant reaches the 1-megohm/centimeter alarm
level.
• Check all hose connections for leaks. Repair any coolant leaks promptly. To
repair a leak in the 3/8-inch blue coolant hose, re-terminate the hose using two
stepless ear clamps of the type originally supplied with the drive (see Table 3-2).
Cut off the portion of the hose under the old clamps before making a new
connection. The hose itself may be replaced with the hose listed in Table 3-2.
Note Do not use an adjustable, radiator-type clamp on the 3/8-inch bridge hose. This
type of clamp is sharp and not perfectly round.
• Check the radiator on liquid-to-air heat exchangers. Remove any paper or debris
blocking the radiator.
• Check bridge clamp pressure (source bridge and load bridge).
3-8 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
Removal and Replacement Procedures
Carbon Filter and Deionizer Cartridge Replacement
Note Replace the carbon filter and deionizer cartridge as a pair.
Note All deionizers, regardless of the external cartridge configuration, use the same
mixed bed resin: Ionic NM-60/SG manufactured by Sybron Chemicals Inc.,
Birmingham, NJ 08011, USA. You may contact a local supplier for a new or
refurbished deionizer or purchase from GE Energy or the following supplier: (GE
part number 323A2419)
Water Chemistry Inc.
3404 Aerial Way Drive
Roanoke, VA 24018
Phone: (540) 989-0400
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-9
Filter Replacement
¾ To replace the filter
1. Replace the deionizer cartridge.
2. Unscrew the filter housing (see Figure 3-4).
3. Replace expended filter element with new AMETEK EPM-10 cartridge by
contacting:
AMETEK
Plymouth Products Inc.
502 Indiana Avenue, PO Box 1047
Sheboygan, WI 53082-1047
www.plymouthwater.com
Phone: 1 (800) 222-7558
Fax: (920) 457-6652
4. Open the ball valve on 3/8-inch supply line to the deionizer cartridge and filter
pair.
3-10 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
Strainer Cleaning
Open the drain valve on the strainer unit to flush debris from the strainer (see Figure
3-5).
Strainer
Drains
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-11
Coolant Pump Replacement
This equipment contains a potential hazard of electric shock
or burn. Only adequately trained persons who are
thoroughly familiar with the equipment and the instructions
should install or maintain this equipment.
Discharge
Supply valve valve
Remove
cover plate
½" bolts
3-12 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
Temperature-regulating Valve Replacement
Note This procedure will result in the loss of coolant. Replenish coolant per the
directions described previously in this manual.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-13
Unions
Orient to
manual
position
Temperature
regulating
valve
3-14 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
Power Conversion Cabinet
The power conversion cabinet(s) contains the Power Conversion Module (PCM), the
Gate Pulse Amplifier (FGPA) boards, current feedback (FCSA) boards, voltage
feedback (NATO) boards, source bridge line filter, and/or load bridge line filter.
Any parts replacement and troubleshooting inside the power conversion cabinet can
be done only if the LS2100 is de-energized and lock-out/tag-out procedures are
followed.
Source Line
Filter
Power Conversion
Module
Source Source
Bridge A Bridge B
Load
Bridge
Load Line
Filter
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-15
Source Line Filter
Power Conversion
Module
Source Bridge A
Source Bridge B
Figure 3-8A 14 MVA Power Conversion Cabinet, Front view – Source Bridge
3-16 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
Load Line Filter
Load Bridge B
Figure 3-8B 14 MVA Power Conversion Cabinet, Front view – Load Bridge
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-17
De-energizing Procedure for the LS2100 Lineup
Use the following procedure to de-energize the LS2100 before attempting to replace
a part inside the power conversion cabinet.
¾ To de-energize the LS2100 lineup
1. Follow all local established procedures for lock-out/tag-out.
2. Shut down all power supplies to the LS2100, including control, main ac input
and output. This typically includes opening the control power breaker (CB1),
generator disconnect switch (89SS), and isolation transformer switch (52SS).
3. Wait at least two minutes after the main ac power supply is turned OFF for all
capacitors in the circuits to discharge.
4. Verify that there is no voltage on any incoming terminals using a suitable
voltmeter.
5. Ground all six phases of the source input and all three phases of the load output
power supply in the power conversion cabinet(s). The cables must be connected
to the PE GND bus located at the bottom, rear section of the power conversion
cabinet(s).
Pump Cabinet
Source Power Load Power
Conversion Conversion
Cabinet Cabinet
Control Cabinet
Pump Cabinet
Power Conversion
Cabinet
Control Cabinet
3-18 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
Table 3-3. Device Nomenclature Sticker Part Numbers
Note The clamp assembly is supported from the side frames of the bridge
independently of the SCR stacks.
This structure allows the clamp force to be completely removed with all components
intact. The heatsinks can then be moved laterally and the SCRs replaced like books
on a shelf.
The insulators and wire supports are positioned by roll pins in the bus bars and the
clamp pivot. In some cases, there are slots that permit removal when clamp force is
removed by sliding the component past the roll pin.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-19
.......
Insulator
Connection
for Liquid-
Coolant Hose
Clamp
Heatsink Head
Support
Clamp
Torque
Nut
Teflon
Insulator
Clamp Gap
3.2 mm (0.125")
Spring
Washers
47,500 N
(10,800lbs.)
44,000 Newtons
(10,000 Pounds) Detail of Clamp Pivot
Figure 3-11. Two SCRs and Typical Support, Front View
3-20 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
Liquid–Coolant
Hose to Heatsink
Heatsink
SCR
Capacitor
Assembly
I-Beam
Hose in Front of
SCR Support Heatsink Support
Capacitor Assembly
Figure 3-12. View of Bridge Showing Heatsink Array
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-21
SCR Replacement
Note For the 8.5 MVA LS2100, always replace SCRs as a matched pair. Purchase a
matched pair SCR parts kit from GE Energy (GE part number
151X1212BZ02SA01).
¾ To replace an SCR
1. Open the bridge module doors, left-hand door first, and support them in a full-
open position. Take care not to stress wire and fiber-optic cables at the hinge
and not to damage electronic components. (Refer to Figures 3-11 and 3-12).
2. Loosen the two clamp torque nuts to remove load from the SCR stack.
3. Remove the SCR as follows:
a. Unplug the gate and cathode leads at the FHVA/FHVB board.
b. Insert the heatsink spreader tool (GE part number 246B9953BPG1) on
opposite sides of the SCR (see Figure 3-13), then use it to remove pressure
from the SCR.
c. Grasp the SCR support and slide the SCR from the stack.
d. If the SCR sticks to the heatsink, rotate it to free it.
Heatsink *
Spreader
Tool
Heatsink
Support
* Points of Tool
On Opposite SCR Support
Sides of SCR
I-Beam
4. Clean the heatsink surface with fine abrasive paper, then wipe thoroughly with a
clean cloth. Hard cleaning may expose bare copper or aluminum, but this does
not impair performance.
5. For the 14 MVA LS2100: Remove the plastic SCR support from the old SCR
and install on the replacement SCR.
For the 8.5 MVA LS2100: Match the replacement SCR provided to the
replacement SCR support as follows:
246B9953ALP3 Eupec 4.25” diameter
246B9953ALP4 ABB 4.1” diameter
246B9953ALP5 Dynex 3.5” diameter
246B9953ALP6 ABB 3.3” diameter
Install the matching replacement SCR support on the replacement SCR.
6. Clean the replacement SCR mounting surface with fine abrasive paper to
remove oxides and wipe thoroughly with a clean cloth.
3-22 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
7. Lightly coat the surfaces with Novagard Versilube silicone lubricating grease
(GE part G322L).
8. Install the replacement SCR and position by snapping the SCR support onto the
heatsink support.
9. Connect the gate and cathode leads to the FHVA/FHVB board.
10. Remove the heatsink spreader tool.
11. Verify that all SCRs, insulators, and wire supports are in alignment within 2.2
mm (.09 in). The wire supports must be aligned vertically.
12. Tighten the torque clamp nuts until the clamp gap is 3.2 mm (.125 in).
13. The jam nuts are used to secure the Teflon™ rod insulator. Tighten against the
Teflon insulator one turn beyond hand tight.
7. If replacing one of the large, bridge heatsinks, remove the SCRs adjacent to the
heatsink, as described in the SCR replacement procedures.
8. If replacing one of the filter heatsinks, all SCRs may remain in place.
9. Remove the adjacent capacitor assembly.
10. Remove the locknuts and washers mounting the heatsink to the heatsink support.
11. Remove the stainless steel cap screw, spring, spacer and washers holding the
heatsink assembly to the I-beam using a 5/32” Allen wrench. Keep all hardware
for re-installation.
12. Remove the heatsink.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-23
¾ To install the heatsink
1. Replace the heatsink, and secure as follows:
a. Mount the heatsink to the I-beam by installing the stainless steel cap screw,
spring, spacer and washers as in Figure 3-14. Torque to 25 in-lbs.
b. Secure to the heatsink support by installing the flat washer first, followed by
the spring washer’s concave face against the flat washer.
c. Tighten the locknut against the spring washer, and then back off 1/2 turn.
2. Replace the capacitor assembly and snubber wires.
3. Replace the SCR as described in the SCR replacement procedure above.
4. Reconnect all hoses and remove hand clamps.
5. Reconnect all wires to the heatsink and capacitor assemblies.
6. Verify that all SCRs, insulators, and wire supports are in alignment within 2.2
mm (.09 in). The wire supports must be aligned vertically.
7. Tighten the torque clamp nuts until the clamp gap is 3.2 mm (.125 in).
8. The jam nuts are used to secure the Teflon rod insulator. Tighten against the
Teflon insulator one turn beyond hand tight.
9. Check for leaks after power to the pump panel is restored.
3-24 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
AC Line Filters
The 8.5 MVA LS2100 contains both source and load AC line filters in a single
power conversion cabinet. In the 14MVA LS2100, the load and source filters are in
separate cabinets (see Figure 3-9).
¾ To replace a fuse
1. Verify that the static starter has been properly de-energized per the section, De-
energizing Procedure for Power Conversion Cabinet.
2. Remove any lexan covers as needed to access the fuse to be replaced.
3. Remove the pin that holds the blown fuse indicator switch in place and pull the
end of the switch from the fuse.
4. Pull the fuse out of the fuse holder.
Note Replacement fuse must be of the same voltage and current parameters as the
fuse removed. Refer to the renewal parts list for the correct part number fuse.
5. Orient the new fuse in the same position as the one removed and set it into the
fuse holder.
6. Reconnect the blown fuse indicator switch to the new fuse.
7. Reset the red indicator tab of the blown fuse indicator switch.
8. Re-install any lexan covers removed in step 2.
9. Perform any necessary hardware verifications and tests. Refer to GEH-6678,
LS2100 Installation and Startup Guide.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-25
VersaMax® Micro PLC for Pump Panel I/O
The VersaMax Micro programmable logic control (PLC) processes the LS2100
pump panel inputs and outputs. It has input provisions for hard-wired run commands
from the MK6 when requested by the customer. The status of the input devices is
transmitted through Modbus serial communication to the UCVE. The UCVE then
sends the status information to the DSPC where the pump panel control program is
executed.
3-26 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
The PLC receives control commands to energize the outputs from the UCVE control
program through serial Modbus communication. All the control logic, driving the
PLC control outputs, is executed in the UCVE controller.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-27
Downloading the requisition software
The hardware and software configuration is standard for both crossover and non-
crossover LS2100 units. The configuration is stored in the PLC during the final test
in the Salem factory.
Use the following instructions to store the VersaMax Micro PLC configuration
software in the event of a PLC replacement or if instructed by Salem’s Static Starter
Engineering.
Requirements:
VersaPro 2.01 Software IC641VPP700 (Professional) or
IC641VPS002 (Standard)
GE Fanuc Part number:
The professional package could be used
for both LM90/30 and Versamax Micro.
The standard can be used only for
VersaMax Micro.
Connecting Cable between the GE Fanuc IC 200 CBL500
Laptop and VersaMax Micro PCL
Comm1
3-28 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
Using VersaPro® to store the VersaMax Micro PLC
configuration
¾ To store VersaMax Micro PLC configuration software
2. From the Main menu, select Folder, then click Restore. The Restore
Folder dialog box displays.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-29
3. Click the Source File Path and Name browse icon to find the
Ls2100_Vmax01.flb file.
3-30 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
6. Click the Destination Path browse icon to find the directory and restore the
PLC configuration software.
7. Select a directory in which you want to restore the PLC configuration (example:
c:\site\master\ls2100).
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-31
9. Connect the GE Fanuc IC200CBL500 cable from the pc Comm Port 1 or 2 to
the PLC Comm Port 1.
10. Create a communication device to establish the serial communication between
the configuring pc and the PLC.
a. From the Main menu select Tools, then Communications Setup.
b. From the Communications Setup window, select the Ports tab and
check that the COM1 and COM2 port settings display.
c. In the configuration pc, verify that the used COM port settings match those
in the indicated screen.
d. Verify that the selected device has the used COM port (i.e., the
®
Cimplicity ControlSerial device uses COM1).
11. From the Main menu, select PLC, then click Connect .
3-32 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
12. From the Connect window, select one of the serial communication devices
(i.e., CimplicityControlSerial). Click Connect to establish communication.
13. Once the connection is established, the Versamax PLC status information
displays.
14. From the Main menu, select PLC, then click Store…
If the PLC is not in the RUN mode, the following message displays.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-33
15. Click the Stop PLC icon to place the PLC in STOP mode.
16. From the Main menu, select PLC, then click Store…
17. The Store Folder to PLC window displays. Select all three options, then click
OK.
3-34 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
18. To view the log information, click the General tab.
Disregard the four warnings that generate when the storing process ends.
LS2100 Reference and Troubleshooting Guide GEH-6680B Chapter 3 Parts Replacement • 3-35
Notes
3-36 • Chapter 3 Parts Replacement LS2100 Reference and Troubleshooting Guide GEH-6680B
Chapter 4 Troubleshooting
Introduction
Troubleshooting the LS2100 includes:
General troubleshooting, which has no specific fault code or indication
Specific troubleshooting, which displays a specific fault number/name on the keypad
The information is organized as follows:
Section Page
Introduction ............................................................................................................................4-1
General Troubleshooting ........................................................................................................4-2
Specific Fault Troubleshooting...............................................................................................4-8
Types of Faults .........................................................................................................4-8
Fault Indications .......................................................................................................4-8
Viewing and Resetting Faults on the Keypad/DDI ..................................................4-9
Static Starter faults, LED indication on DSPC 1. For DSPC, see section Specific Fault Troubleshooting
board
Keypad/DDI problems 2. Keypad/DDI display off
3. Error messages displayed
4. Keypad/DDI ineffective - no errors displayed
5. Parameter changes ineffective
6. Diagnostics do not perform
Board failures, power supply failures, fan failures 7. Power supply fuses blowing
8. MOV failures
9. Repetitive board failures
10. Fan or fan power supply failures
Noise, wiring, power supplies, and similar 16. Noise or random nuisance faults
problem 17. Wiring procedures
4) Diagnostics do not 1. Check that the particular function is available (refer to the Custom Software
perform Descriptions).
2. Check DSPC board for proper operation.
3. Replace DSPC board or keypad/DDI.
5) Power supply fuses 1. Check that the fuses are correct size.
blowing 2. Check for any shorted or overloaded power supplies - refer to problem 16.
7) Repetitive board failures 1. Check for damage caused by airborne chemical contamination or foreign objects.
2. Check all connections at all terminal boards.
3. Check that all boards are properly inserted into the backplane.
4. Check the power supply.
5. Check that all voltages are correct.
6. Check for moisture.
8) Serial link does not 1. Check that correct serial link cable is being used.
function properly 2. Check the Static Starter's baud rate compared to serial link device (hard reset must
be performed afterward if baud rate is changed).
3. Check serial link connections at terminal board.
4. Check/replace the DSPC.
9) Erratic operation 1. Check power supplies for magnitude and ripple – refer to problem 16.
2. Check connections on all cables and boards.
3. Tighten all connections on terminal boards and all power connections.
4. Confirm correct hardware jumper settings per the Custom Software.
5. Check all parameters per the software test data sheet or Custom Software.
6. Check for noisy ground connections.
11) Noise/random nuisance 1. Check that any dc supply voltages are not used externally.
faults 2. Check for suppression on all relays, contactors, and starters.
3. Check all power supplies.
12) Wiring procedures 1. Check the wire sizes on the ac and dc power connections.
2. Check that the control wires (24 V dc, 115 V ac) do not run in the same conduit or
run parallel closer than 4 inches to the power wires, causing noise pickup.
3. Check that all signal wires are twisted-pair, shielded and that shields are grounded
at the Static Starter end only.
4. Check that signal wires are not grounded at more than one end or other than the
Static Starter end only.
5. Check that the signal wires do not run in the same conduit, parallel, or closer than
4 inches to the power wires.
6. Check that there is only one system ground.
7. Check that the ground bus is large enough to prevent voltage drops or noise
pickup.
13) Checking power Check the LEDs on the power supply module for proper voltage indications.
supplies
UCVE board not responding Lost communication to the Board LEDs are dark Possible problem with
DSPC board not responding board power supply of the board
Keypad screen blank Impossible to communicate Verify power supply and
to the board from the keypad the backplane
UCVE board does not Communication problems When PC hooked up to the Check integrity of the
communicate with the PC with the controller controller it is not possible to ENET cable
and the keypad read or change of any of the
parameters
UCVE board is working but DSPC LEDs are dark Board LEDs do not indicate Check power supply to the
DSPC does not indicate that Processor LED does not any communication between board (verify backplane)
it is responding indicate that the card is DSPC and UCVE boards
active
When communicating to the When using a trend recorder Lack of feedback values Verify NATO and FCSA
Static Starter with the there are no feedback boards
toolbox there are no values from the static starter Verify DSPC and UCVE
feedback values for current boards
and volts
Sync Trip Flt When static starter A problem with ac power Check incoming ac
commanded to RUN it trips supply to the bridge amplitude on all three
on PLL_Loss phases
No communication from the Controller is not responding It is not possible to send a Replace the keypad
keypad to the controller to the commands from the command to the controller Replace the cable from the
keypad from the keypad keypad to the backplane
PLC Heart beat fault UCVE does not Trip - VersaMax PLC Check for 5Vdc at pins 5
communicate with PLC heartbeat & 7 on VersaMax PLC
Alarm coolant Temp alarm Port-2. If 5 V is not
present, the PLC needs
Alarm pump resistivity replacement or factory
alarm repair.
Trip resistivity Trip
Trip pump high level trip
Source/load line filter Rise in coolant temperature Dis -colorisation of line filter Check for proper coolant flow in
resistors gets over resistors the heat sink of the filter
heated Smoke from filter cabinet resistors.
Check for proper coolant circuit
connection to the line filters
resistors heat sink.
Check for proper operation of
temperature regulating valve.
Check for the proper flow of
external cooling water (under
customer scope) in heat
exchanger (W-W)
High-level of harmonic High level of harmonic noise Verify the ac input voltage Verify ac line filter fuses
disturbances at the ac detected by other users waveform using the scope Verify ac line filter resistors and
incoming line There is no indication that capacitors
ac line filter is actively
working in the circuit – no
heat generated by the
resistors
Ac line filter resistor When static starter under Use meter to verify integrity Replace capacitor if shorted
problem load, there is an intensive of the line filter capacitors
heat generated by the ac
line filter unit
FGPA board is not All yellow LEDs are not lit Check gating LEDs on ESEL Replace FGPA board
generating gate pulses Bridge does not work – no Check fibre-optic cables
output current; from FCGD board
Use oscilloscope to verify
bridge proper gating
SCR is not conducting SCR is not conducting but is Verify the 10 – 20 Ohm Replace gate leads or
not shorted resistance between Gate SCR
and Cathode
Types of Faults
There are currently two types of fault conditions:
• Alarm faults indicate conditions that you should note, but that are not serious
enough to automatically shut down or trip the static starter. If the condition goes
away, some alarm faults clear themselves and the display then identifies the
alarm as brief. Otherwise, you must stop the static starter to clear this type of
fault.
• Trip faults indicate a more serious condition that needs to be corrected.
Therefore, it trips the static starter. The static starter should not be restarted until
the condition is corrected.
You can clear most faults by selecting Clear Faults on the static starter’s keypad or
in the (optional) toolbox program.
Fault Indications
The DSPC board is the The static starter indicates a fault condition on the keypad, toolbox display, and on
DS200DSPC Digital Signal the DSPC board.
Processor, located in the
On the keypad, a fault icon appears in the right side of the display: The operator can
static starter control rack.
then use the keypad to access the fault/alarm description (see Figure 4-1) and to clear
the fault.
Abbreviated Description
Fault No.
ACTIVE FAULT DISPLAY
Fault Icon:
50 Trip HtSink temp low, B
108 DC bus voltage low Flashing = fault
12 Trip Gnd flt, Not flashing (on steady) = alarm
113 Trip Invalid board set
--- RESET FAULTS NOW ---
Fault Behavior
The toolbox uses a Windows-based pc display. When a fault occurs, the word
Alarm or Trip appears in the lower right corner of the screen. You can view a
description and clear the fault using the toolbox functions. Refer to GEH-6414.
The DSPC Fault LED displays at the front of the static starter’s control rack. This
red indicator is on solid for a fault and flashes for an alarm. A fault is identified by
an assigned number and abbreviated description. Both of these are displayed when
an operator examines a fault using the keypad or the toolbox.
2. To view detail on a particular fault, select that fault (listed on the Active Fault
Display screen) by pressing Enter. The following screen displays.
block
Instruction blocks contain basic control functions, which are connected together
during configuration to form the required machine or process control. Blocks can
perform math computations, sequencing, or regulator (continuous) control.
board
Printed wiring board or card.
bus
Upper bar for power transfer, also an electrical path for transmitting and receiving
data.
DDI/keypad
Diagnostic Display/Interface that is also referred to as the keypad that provides
exciter status icons and displays fault information. It can also be used to check
firmware and hardware versions, run the exciter, set parameters, reset the exciter,
and provide other control functions.
device
A configurable component of a control system.
fault code
A message from the controller to the HMI indicating a system warning or failure.
firmware
The set of executable software that is stored in memory chips that hold their content
without electrical power, such as EEPROM or Flash.
gating
Controlling the conduction of the power SCRs with an input pulse train (or a
voltage).
HMI
Human Machine Interface, usually a PC running Windows NT and CIMPLICITY
HMI software.
I/O
Input/output interfaces that allow the flow of data into and out of a device.
line filter
Filter networks across the three-phase input lines to the static starter to minimize the
voltage spikes that result from the abrupt decay of current during SCR
commutations.
Modbus
A serial communication protocol developed by Modicon for use between PLCs and
other computers.
redundant
A system consisting of duplicated components (boards or modules), which can
transfer functionality from a failed component to one of the duplicate components
without loss of the entire system’s functionality.
signal
The basic unit for variable information in the controller.
toolbox
A Windows NT -based software package used to configure the EX2100 and Mark VI
turbine controller.
V/Hz
V/Hz is the ratio of generator voltage to the frequency; this is limited to prevent
overfluxing the generator.
Index F
fan replacement intervals 2-3
faults
indications 4-10
trip 4-10
types 4-10
viewing and resetting 4-11
A H
AC line filters 3-23, 4-8 heatsink
alarm faults 4-10, 4-11 installing 3-22
help
B how to get 1-5
Boards
Digital Signal Processor 1-6 K
Gate Pulse Amplifier 1-6 keypad
printed wiring 1-6, 2-5, 2-6 changing 3-4
UCVE 3-24, 4-7 viewing and resetting faults 4-11
bridge
assemblies 2-4
L
Power Conversion 3-6
structure overview 3-17 loose connections 2-5
LS2100
C catalog numbers 1-5, 1-6
de-energize lineup 3-3, 3-16
cabinet printed wiring boards 1-6, 2-6
control 2-3, 3-3, 3-16 standard configuration file 3-26
pump 1-1, 2-3, 3-1
cleaning
M
strainer 3-11
communication motor starters
serial 3-24, 3-30, 3-31 M1 3-13
contactors and relays 2-6, 2-7 M2 3-13
control maintenance
cabinet 2-3, 3-3, 3-16 cleaning boards 2-5
power circuit breakers 3-3 cleaning up oil 2-5
controller 3-25, 4-7 contactors and relays 2-6
Control System Toolbox 1-3, 1-6 dust removal 2-4
fan replacement 2-3
D loose connections 2-5
procedures 2-2
damage pump cabinet 3-8
insulation 2-6 record 2-2
short-circuit 2-7 schedule 2-2
documents
distribution 1-5
related 1-5
dust removal 2-4, 3-2
R
reference 1-1, 1-3, 4-3
related documents 1-5
document distribution 1-5
replacement
boards 3-4
carbon filter 3-8, 3-9
control rack fan 3-5
coolant pump 3-12
deionizer cartridge 3-9
filter 3-10
heatsink and capacitor assembly 3-21
parts 3-1
SCR 3-20, 3-21
temperature-regulating valve 3-13
S
safety
equipment 1-4
guidelines 3-2
silicon controlled rectifiers (SCR) 3-6, 3-17, 3-20
software
downloading 3-26
spare parts
description 3-8
number 3-8
static starter 1-1, 2-2, 4-10
T
Toolbox
help 1-3
troubleshooting
general 4-2
quick reference guide 4-3
specific fault 4-10
typical maintenance tools 1-4
V
VersaMax 3-24, 3-26