You are on page 1of 2

FRT-XH

CU / XLPE / LSZH ( SINGLE CORE )


XLPE Insulated, LSZH Sheathed Cable, 600/1000V, IEC60502-1

Component
1. Plain Annealed Copper Wire
2. Cross-linked Polyethylene Compound
3. Low Smoke Zero Halogen
(LSZH) Compound

3 2 1

CONSTRUCTION REFERENCE STANDARDS


Conductor: Plain Annealed Copper, Class 2 Design Specification: IEC60502-1
Stranded Circular or Compacted
Conductor: IEC60228, BS EN60228
Insulation: Cross-linked Polyethylene (XLPE)
Compound Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Insulation Colour: Natural Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2


IEC60754-1, IEC60754-2
Outer Sheath: Low Smoke Zero Halogen (LSZH) BS EN60754-1, BS EN60754-2
Compound with Anti-Termite
Characteristic and UV Resistant
INSTALLATION REFERENCE
Outer Sheath Colour: Black Min. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50


ELECTRICAL CHARACTERISTICS
Operating Voltage: 600/1000V

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

Nominal No. and Diameter Radial Thickness Cable Overall Approximate


Conductor Area of Wires of Insulation Diameter Weight
(mm2) (no./mm) (mm) (mm) (kg/km)

1 x 1.5 7 / 0.53 0.7 6.1 75


1 x 2.5 7 / 0.67 0.7 6.5 89
1x4 7 / 0.85 0.7 7.1 110
1x6 7 / 1.04 0.7 7.6 136
1 x 10 7 / 1.35 0.7 8.6 186
1 x 16 7 / 1.70 0.7 9.6 254
1 x 25 7 / 2.14 0.9 11.3 367
1 x 35 7 / 2.52 0.9 12.5 472
1 x 50 19 / 1.78 1.0 14.1 612
SINGLE CORE

1 x 70 19 / 2.14 1.1 16.1 837


1 x 95 19 / 2.52 1.1 18.2 1114
1 x 120 37 / 2.03 1.2 20.0 1374
1 x 150 37 / 2.25 1.4 22.2 1675
1 x 185 37 / 2.52 1.6 24.4 2066
1 x 240 61 / 2.25 1.7 27.5 2661
1 x 300 61 / 2.52 1.8 30.3 3291
1 x 400 61 / 2.85 2.0 33.9 4159
1 x 500 61 / 3.20 2.2 37.6 5188
1 x 630 127 / 2.52 2.4 42.4 6638
1 x 800 127 / 2.85 2.6 47.3 8394
1 x 1000 127 / 3.20 2.8 52.4 10479
# For current rating and voltage drop, please refer to Table B1.4 and B2.4 on Page 36. Table 14

14 | www.taisin.com.my
APPENDIX B IEC60502-1
BS EN50525-3-41
Table B1.4: Current Carrying Capacity ( IN AMPERES ) *based on
600/1000V
Single-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, unarmoured, application
BS7889
with or without sheath (PVC / LSZH) cables
Ambient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W

Reference Method A Reference Method B Reference Method C Reference Method F Reference Method G
(enclosed in conduit (enclosed in conduit (clipped direct) (in free air or on a perforated cable tray etc, (in free air)
in thermally insulating on a wall or horizontal or vertical etc)
wall etc) in trunking etc)
Conductor Touching Spaced by One Cable Diameter
Cross-
Sectional
Area 2 Cables, 3 or 4 Cables, 2 Cables, 3 or 4 Cables, 2 Cables, 3 or 4 Cables, 2 Cables, 3 Cables, 3 Cables, 2 Cables, Single-Phase
Single-Phase 3-Phase a.c. Single-Phase 3-Phase a.c. Single-Phase 3-Phase Single-Phase 3-Phase 3-Phase a.c. or d.c., or
a.c. or d.c. a.c. or d.c. a.c. or d.c. a.c. Flat and a.c. or d.c. a.c. Flat a.c. Trefoil 3 Cables, 3-Phase a.c. Flat
Flat and Touching or Flat
Touching Trefoil Horizontal Vertical

mm2 A A A A A A A A A A A

1.0 14 13 17 15 19 17.5 – – – – –
1.5 19 17 23 20 25 23 – – – – –
2.5 26 23 31 28 34 31 – – – – –
4 35 31 42 37 46 41 – – – – –
6 45 40 54 48 59 54 – – – – –
10 61 54 75 66 81 74 – – – – –
16 81 73 100 88 109 99 – – – – –
25 106 95 133 117 143 130 161 141 135 182 161
35 131 117 164 144 176 161 200 176 169 226 201
50 158 141 198 175 228 209 242 216 207 275 246
70 200 179 253 222 293 268 310 279 268 353 318
95 241 216 306 269 355 326 377 342 328 430 389
120 278 249 354 312 413 379 437 400 383 500 454
150 318 285 393 342 476 436 504 464 444 577 527
185 362 324 449 384 545 500 575 533 510 661 605
240 424 380 528 450 644 590 679 634 607 781 719
300 486 435 603 514 743 681 783 736 703 902 833
400 – – 683 584 868 793 940 868 823 1085 1008
500 – – 783 666 990 904 1083 998 946 1253 1169
630 – – 900 764 1130 1033 1254 1151 1088 1454 1362
800 – – – – 1288 1179 1358 1275 1214 1581 1485
1000 – – – – 1443 1323 1520 1436 1349 1775 1671

Note: 1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the
conductor operating temperature.
2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the
equivalent table for 70ºC thermoplastic insulated cables must be used.

Table B2.4: Voltage Drop ( IN mV/A/m )


Single-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, unarmoured, with or without sheath (PVC / LSZH) cables
Ambient temperature: 30ºC, Conductor operating temperature: 90ºC

2 Cables, Single-Phase a.c. 3 or 4 Cables, 3-Phase a.c.

Conductor Reference Methods Reference Methods C, F & G Reference Methods Reference Methods C, F & G
Cross- 2 Cables A&B (clipped direct, on tray or in free air) A&B (clipped direct, on tray or in free air)
Sectional d.c. (enclosed in (enclosed in
Area conduit or Cables Cables conduit or Cables Touching, Cables Touching, Cables Spaced*,
trunking) Touching Spaced* trunking) Trefoil Flat Flat

mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m

1.0 46 46 46 46 40 40 40 40
1.5 31 31 31 31 27 27 27 27
2.5 19 19 19 19 16 16 16 16
4 12 12 12 12 10 10 10 10
6 7.9 7.9 7.9 7.9 6.8 6.8 6.8 6.8
10 4.7 4.7 4.7 4.7 4.0 4.0 4.0 4.0
16 2.9 2.9 2.9 2.9 2.5 2.5 2.5 2.5
r x z r x z r x z r x z r x z r x z r x z
25 1.85 1.85 0.31 1.90 1.85 0.190 1.85 1.85 0.28 1.85 1.60 0.27 1.65 1.60 0.165 1.60 1.60 0.190 1.60 1.60 0.27 1.65
35 1.35 1.35 0.29 1.35 1.35 0.180 1.35 1.35 0.27 1.35 1.15 0.25 1.15 1.15 0.155 1.15 1.15 0.180 1.15 1.15 0.26 1.20
50 0.99 1.00 0.29 1.05 0.99 0.180 1.00 0.99 0.27 1.00 0.87 0.25 0.90 0.86 0.155 0.87 0.86 0.180 0.87 0.86 0.26 0.89
70 0.68 0.70 0.28 0.75 0.68 0.175 0.71 0.68 0.26 0.73 0.60 0.24 0.65 0.59 0.150 0.61 0.59 0.175 0.62 0.59 0.25 0.65
95 0.49 0.51 0.27 0.58 0.49 0.170 0.52 0.49 0.26 0.56 0.44 0.23 0.50 0.43 0.145 0.45 0.43 0.170 0.46 0.43 0.25 0.49
120 0.39 0.41 0.26 0.48 0.39 0.165 0.43 0.39 0.25 0.47 0.35 0.23 0.42 0.34 0.140 0.37 0.34 0.165 0.38 0.34 0.24 0.42
150 0.32 0.33 0.26 0.43 0.32 0.165 0.36 0.32 0.25 0.41 0.29 0.23 0.37 0.28 0.140 0.31 0.28 0.165 0.32 0.28 0.24 0.37
185 0.25 0.27 0.26 0.37 0.26 0.165 0.30 0.25 0.25 0.36 0.23 0.23 0.32 0.22 0.140 0.26 0.22 0.165 0.28 0.22 0.24 0.33
240 0.190 0.21 0.26 0.33 0.20 0.160 0.25 0.195 0.25 0.31 0.185 0.22 0.29 0.170 0.140 0.22 0.170 0.165 0.24 0.17 0.24 0.29
300 0.155 0.175 0.25 0.31 0.160 0.160 0.22 0.155 0.25 0.29 0.150 0.22 0.27 0.140 0.140 0.195 0.135 0.160 0.21 0.135 0.24 0.27
400 0.120 0.140 0.25 0.29 0.130 0.155 0.20 0.125 0.24 0.27 0.125 0.22 0.25 0.110 0.135 0.175 0.110 0.160 0.195 0.110 0.24 0.26
500 0.093 0.120 0.25 0.28 0.105 0.155 0.185 0.098 0.24 0.26 0.100 0.22 0.24 0.090 0.135 0.160 0.088 0.160 0.180 0.085 0.24 0.25
630 0.072 0.100 0.25 0.27 0.086 0.155 0.175 0.078 0.24 0.25 0.088 0.21 0.23 0.074 0.135 0.150 0.071 0.160 0.170 0.068 0.23 0.24
800 0.056 – 0.072 0.150 0.170 0.064 0.24 0.25 – 0.062 0.130 0.145 0.059 0.155 0.165 0.055 0.23 0.24
1000 0.045 – 0.063 0.150 0.165 0.054 0.24 0.24 – 0.055 0.130 0.140 0.050 0.155 0.165 0.047 0.23 0.24

Note: *Spacings larger than one cable diameter will result in a larger voltage drop.

36 | www.taisin.com.my