Technical Data Sheet

POWER CABLE SHIELDED SL2CXXMM2FRNC-S-BK-R


Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger Hochfrequenztechnik GmbH & Co. KG

Material
Item
1 Conductor Stranded, annealed copper wires, class 5 IEC 60228.
2 Insulation Flame retardant Polyolefin, red and white
3 Shield AL/PET Foil and annealed aluminium wires (4 and 6mm²) or copper wires (10 and
16mm²)
4 Jacket Halogen Free, black Polyolefin, UV resistant

Printing: Rosenberger SL2CXXMM2FRNC-S-BK-R “lot number” “length [m]”


“X” see table below

Electrical data and dimension


SL2C4MM2 SL2C6MM2 SL2C10MM2 SL2C16MM2 SL2C25MM2 SL2C35MM2
Part number
FRNC-S-BK-r FRNC-S-BK-r FRNC-S-BK-r FRNC-S-BK-r FRNC-S-BK-r FRNC-S-BK-r
Weight [kg/km] 124 160 315 475 861 1061
Conductor DC resistance [Ω/km] 4,95 3,30 1,91 1,21 0,78 0,55
Shield DC resistance [Ω/km] 4,95 4,95 1,91 1,21 1,21 1,21
Conductor size [mm²] 4 6 10 16 25 35
Shield size [mm²] 6* 6* 10 16 16 16
Insulation thickness [mm] 0,51 0,51 0,51 0,56 0,56 0,56
Jacket diameter [mm] 8,6 9,4 11,7 14,8 18,6 19,8
*aluminium wires

Rated Voltage max 600 V


Max. resistance (shield) 4.95 Ω/km
Inductance 0,6 µH/m

Mechanical data
Min. bending radius 5x Outer diameter

Environmental data
Temperature range - 40 °C to + 90 °C
UV resistance / Sunlight resistant acc. to UL 1581, 1200
Fire classification IEC 60332-3-24 (cat C)
CPR Dca
CE Low voltage directive compliant
RoHS (2011/65/EC) compliant
Halogen free

Draft Date Approved Date Rev. Engineering change number Name Date
RF_35/05.10/6.0

U. Ferraz 26.02.19 J. Gramsamer 21.11.19 100 19-0005 U. Ferraz 21.11.19

Rosenberger Hochfrequenztechnik GmbH & Co. KG Tel. : +49 8684 18-0 Page
P.O.Box 1260 D-84526 Tittmoning Germany Email : info@rosenberger.de
www.rosenberger.de 1/1
Technical Data Sheet

Power cable SLZ0035-XX-YY


Dieses Dokument ist urheberrechtlich geschützt ● This document is protected by copyright ● Rosenberger Hochfrequenztechnik GmbH & Co. KG

3 2 1
Description

Halogen free, flame retardant cable – double isolated - for connection of batteries, power distribution or
grounding. Suitable for indoor use only. Maximum Current handling acc. to DIN VDE 0298-4. (equal to type
H07Z-K)

Cable design
Conductor (1) stranded, annealed copper wire, class 5
Insulation (2) flame retardant Polyolefin
Sheath (3) flame retardant Polyolefin

Electrical data
Rated voltage 600 V

Mechanical and environmental data


Temperature range operation -40 °C to +90 °C
Flame resistance IEC 60332-3-24 (cat C), UL 1685 (vertical tray)
CPR rating Dca
Bending radius 5x cable outer diameter
Marking on jacket Manufacturer, date of manufacture, product No., length marking
CE low voltage directive compliant
RoHS compliant
REACH compliant

Available variants
Product number Cross DC Outer Sheath
section resistance diameter colour
SLZ0035-10-RD 1x10 mm² 1.91 Ω/km 9.0 mm red
SLZ0035-10-WH 1x10 mm² 1.91 Ω/km 9.0 mm white
SLZ0035-16-RD 1x16 mm² 1.21 Ω/km 10.0 mm red
SLZ0035-16-WH 1x16 mm² 1.21 Ω/km 10.0 mm white
SLZ0035-25-RD 1x25 mm² 0.78 Ω/km 10.5 mm red
SLZ0035-25-WH 1x25 mm² 0.78 Ω/km 10.5 mm white
SLZ0035-35-RD 1x35 mm² 0.55 Ω/km 11.0 mm red
SLZ0035-35-WH 1x35 mm² 0.55 Ω/km 11.0 mm white
SLZ0035-50-RD 1x50 mm² 0.39 Ω/km 13.0 mm red
SLZ0035-50-WH 1x50 mm² 0.39 Ω/km 13.0 mm white

Draft Date Approved Date Rev. Engineering change number Name Date
U. Ferraz 26.10.20 J. Gramsamer 30/07/21 300 21-0005 U. Ferraz 30/07/21
RF_35/06.10/1.0

While the information has been carefully compiled to the best of our knowledge, nothing is intended as representation or warranty on our part and no statement herein shall be
construed as recommendation to infringe existing patents. In the effort to improve our products, we reserve the right to make changes judged to be necessary.
Rosenberger Hochfrequenztechnik GmbH & Co. KG Page
Tel. : +49 8684 18-0
P.O.Box 1260 D-84526 Tittmoning Germany
Email : info@rosenberger.de
www.rosenberger.de 1/1