Professional Documents
Culture Documents
POWER CABLE
MULTI CORE, UNARMORED FIRE RESISTANCE
CU/MICA/XLPE/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-01-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
CONSTRUCTION:
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Insulation Mica impregnated Glass Tape + Cross linked polyethylene (XLPE) to IEC 60502-1.
Cabling Cores are assembled in a concentric layer laid up with non-hygroscopic filler if required and
assembly is wrapped with polyester tape.
Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1. The Color of the sheath is as per Dimension
sheet.
Printing on the sheath CU/MICA/XLPE/PVC NO OF CORES C X MM2 600/1000V MESC YEAR IEC 60502-1 IEC
60331 IEC 60332-3 CAT C LENGTH METER MARKING
Technical Data:
Operating Temperature -15°C to +90°C
Page 1 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, UNARMORED FIRE RESISTANCE
CU/MICA/XLPE/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-01-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
DIMENSIONAL DATA:
APPROX. OVERALL
THICKNESS (mm)
THICKNESS (mm)
APPROX. CABLE
OUTER SHEATH
OUTER SHEATH
WEIGHT (kg/km)
STRAND x DIA.
MESC CODE
INSULATION
SERIAL NO
SIZE (mm2)
DIA. (mm)
(n x mm)
COLOR
CORE
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 2 of 22
Middle East Specialized Cables (MESC)
POWER & CONTROL CABLE
MULTI CORE, LEAD SHEATHED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1, IEC 60331-21 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-02-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
CONSTRUCTION:
Conductor Sector shaped stranded annealed plain copper Class 2 as per IEC 60228.
Insulation Mica impregnated Glass Tape + Cross linked polyethylene (XLPE) to IEC 60502-1.
Cabling Cores are assembled in a concentric layer laid up with non-hygroscopic filer if required and
assembly is wrapped with polyester tape.
Inner Sheath Flame retardant PVC Type ST-2 to IEC 60502-1 in Black color.
Bedding Flame retardant PVC Type ST-2 to IEC 60502-1 in Black color.
Armor A single layer of galvanized steel wire armor to IEC 60502-1 is applied over the bedding.
Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1. The color of the sheath is as per dimension
sheet.
Printing on the sheath CU/MICA/XLPE/PVC/LC/PVC/GSWA/PVC NO. OF CORES C X ... MM2 600/1000V MESC
YEAR IEC 60502-1 IEC 60331 IEC 60332-3 CAT C LENGTH METER MARKING
Technical Data:
Operating Temperature -15°C to +90°C
Page 3 of 22
Middle East Specialized Cables (MESC)
POWER & CONTROL CABLE
MULTI CORE, LEAD SHEATHED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1, IEC 60331-21 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-02-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
DIMENSIONAL DATA:
THICKNESS (mm)
OUTER SHEATH
MIN. NO. OF. STRANDS
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
APPROX. CABLE
APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
BEDDING (mm)
LEAD SHEATH
SHEATH (mm)
SHEATH (mm)
MESC CODE
INSULATION
SERIAL NO.
SIZE (mm2)
DIA. OVER
BEDDING
COLOR
CORE
(mm)
(mm)
Nom.
Min.
R.2 76FG-03C02500-WLBK8-LO Black 3C 25 7 0.9 1.0 18.7 1.2 20.9 1.0 23.0 1.6 26.2 1.9 1.32 29.6 2681
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm, ± 3.0mm above 30mm & ± 3.5mm
above 50mm.
Page 4 of 22
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, ARMORED FIRE RESISTANCE CABLE
CU/MICA/XLPE/OA.SCR/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-03-00 Date: 08.12.2021 Customer Ref.: EMAIL DATED: 06.12.2021
CONSTRUCTION:
Conductor Stranded annealed plain copper to Class 2 of IEC 60228.
Insulation Mica impregnated Glass Tape + Cross linked polyethylene (XLPE) to EN 50290-2-29.
Two insulated conductor are uniformly twisted to form a pair with 10-14 twists per meter.
Pair Construction
Required number of twisted pairs are assembled with non-hygroscopic filler if required and
Cabling
assembly is wrapped with a polyester binder tape.
Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
Collective Screen
down in contact with a stranded tinned copper drain wire of 0.5mm² (7x0.3mm) run
longitudinally over the binder tape.
A single layer of galvanized steel wire armor to BS EN10257-1 is applied over the inner
Wire Armor
sheath.
Outer sheath Flame retardant PVC to BSEN 50290-2-22. The color of the sheath is as per dimension
sheet.
Technical Data:
Operating temperature -15°C to 90°C
Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad
Dielectric Strength Test (core to core & 2000 VAC / 3000 VDC for 1 minute
core to screen)
Page 5 of 22
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, ARMORED FIRE RESISTANCE CABLE
CU/MICA/XLPE/OA.SCR/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-03-00 Date: 08.12.2021 Customer Ref.: EMAIL DATED: 06.12.2021
DIMENSIONAL DATA:
THICKNESS (mm)
STAND No X mm
OUTER SHEATH
INNER SHEATH
(mm)
SIZE (mm²)
MESC CODE
INSULATION
PAIR/TRIAD
SERIAL NO
(kg/km)
COLOR
(mm)
(mm)
Nom
R.3 021G-01P00150-W0BK8-E5 Black 1P 1.5 7x0.53 0.44 0.9 9.3 0.9 11.1 1.3 Min
0.84 13.3 318
Note:
The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 6 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-04-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
CONSTRUCTION
Conductor Stranded annealed plain copper as per Class 2 of IEC 60228.
Insulation Mica impregnated glass tape + Cross linked polyethylene (XLPE) to EN 50290-2-29.
Color Code Multi Pair: Black & White with each core numbered.
Pair Construction Two insulated conductor are uniformly twisted to form a pair with 10-14 twists per meter.
Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25%
with the metallic side down in contact with a stranded tinned copper drain wire of 0.5mm2
(7x0.3mm). All pair shields are electrically isolated from each other.
Cabling Required number of individually screened pairs are assembled with non-hygroscopic filler
if required and the assembly is wrapped with a polyester binder tape.
Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic
side down in contact with a stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run
longitudinally over the binder tape.
Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the bedding.
Outer Sheath Flame retardant PVC to EN 50290-2-22. The color of the sheath is as per dimension
sheet.
Technical Data:
Operating Temperature -15°C to 90°C
Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)
Dielectric Strength Test (core to core & 2000 Vac / 3000 Vdc for 1 minute
core to screen)
Page 7 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-04-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
DIMENSIONAL DATA
THICKNESS (mm)
OUTER SHEATH
APPROX. OVERALL
DIA. OVER ARMOR
MESC CODE
THICKNESS (mm)
THICKNESS (mm)
BEDDING THICK.
APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
BEDDING (mm)
STRAND x DIA.
LEAD SHEATH
SHEATH (mm)
SHEATH (mm)
INSULATION
SIZE (mm2)
DIA. OVER
DIA. (mm)
(n x mm)
COLOR
PAIR
(mm)
(mm)
(mm)
SERIAL
NO.
Nom.
Min.
R.4 041G-12P00150-WLBK8-LV Black 12P 1.5 7X0.53 0.44 1.5 30.0 1.4 32.6 1.0 34.7 1.6 37.9 1.9 1.32 41.1 3842
Note:
The tolerance on the cable overall diameter shall be ± 2.0mm up to 30mm & ± 2.5mm above 30mm.
Page 8 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-05-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228
Insulation Mica impregnated Glass Tape + Cross linked polyethylene (XLPE) to EN 50290-2-29.
Color Code Multi pair: Black & White with each core numbering.
Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.
Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25% with
metallic side down in contact with a stranded annealed tinned copper drain wire of 0.5mm2
(7x0.3mm). All pair shields are electrically isolated from each other.
Cabling Required number of individually screened pair are assembled with non-hygroscopic filler if
required and the assembly is wrapped with a polyester binder tape.
Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic
side down in contact with a stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run
longitudinally over the binder tape.
Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the inner
sheath.
Outer Sheath Flame retardant PVC as per BS EN 50290-2-22. The color of the sheath is as per
dimension sheet.
Technical Data:
Operating temperature -15°C to 90°C
Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair)
Dielectric Strength Test (core to core & 2000 VAC / 3000 VDC for 1 minute
core to screen)
Page 9 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-05-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
DIMENSIONAL DATA:
THICKNESS (mm)
OUTER SHEATH
THICKNESS Min (mm)
APPROX OVERALL
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)
APPROX. CABLE
OUTER SHEATH
WEIGHT (kg/km)
DIAMETER(mm)
INNER SHEATH
STRAND x DIA.
SHEATH (mm)
MESC CODE
INSULATION
SERIAL NO
SIZE (mm2)
(n x mm)
COLOR
(mm)
(mm)
PAIR
Min at a
Nom
Pt.
R.5 041G-12P00150-W0BK8-E5 Black 12P 1.5 7X0.53 0.44 1.5 30.0 1.6 33.2 1.8 1.24 36.2 2028
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm, ± 3.0mm above 30mm & ± 3.5mm above
50mm.
Page 10 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-06-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
CONSTRUCTION:
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Cabling Cores are assembled in a concentric layer and laid up with non-hygroscopic filler if required
and assembly is wrapped with polyester binder tape.
Inner Sheath Flame retardant PVC Type ST-2 to IEC 60502-1 in Black color.
Bedding Flame retardant PVC Type ST-2 to IEC 60502-1 in Black color.
Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the bedding.
Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1. The color of the sheath is as per dimension
sheet.
Printing on the sheath CU/XLPE/PVC/LC/PVC/GSWA/PVC NO OF CORES C X ... MM2 600/1000V MESC YEAR
IEC 60502-1 IEC 60332-3 CAT C LENGTH METER MARKING
Technical Data:
Operating Temperature -15°C to +90°C
Page 11 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-06-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
DIMENSIONAL DATA:
THICKNESS (mm)
MIN. NO. OF STRANDS
OUTER SHEATH
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
BEDDING THICK.
APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
BEDDING (mm)
NO OF CORES
LEAD SHEATH
SHEATH (mm)
SHEATH (mm)
MESC CODE
INSULATION
SIZE (mm2)
DIA. OVER
DIA. (mm)
SERIAL
COLOR
(mm)
(mm)
(mm)
NO.
Nom.
Min.
H.1 7614-03C00400-WLBK8-LO Black 3C 4 7 0.7 1.0 10.7 1.2 12.9 1.0 15.0 1.25 17.5 1.8 1.24 20.5 1234
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 12 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR, INDIVIDUALLY & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-07-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
CONSTRUCTION
Conductor Stranded annealed plain copper as per Class 2 of IEC 60228.
Color Code Multi pair: Blue & White with each core numbered.
Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.
Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25% with
the metallic side down in contact with a stranded tinned copper drain wire of 0.5mm2
(7x0.3mm). All pair shields are electrically isolated from each other.
Cabling Required numbers of individually screened pair are assembled with non-hygroscopic filler if
required and the assembly is wrapped with a polyester binder tape.
Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
down in contact with a stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run
longitudinally over the binder tape.
Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the bedding.
Outer Sheath Flame retardant PVC to EN 50290-2-22. The color of the sheath is as per dimension sheet.
Technical Data:
Operating Temperature -15ºC to +90ºC
Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)
Dielectric Strength Test (core to core & 2000 VAC / 3000 VDC for 1 minute
core to screen)
Page 13 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR, INDIVIDUALLY & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-07-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
DIMENSIONAL DATA
THICKNESS (mm)
OUTER SHEATH
BEDDING THICKNESS
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
STRAND x DIA.
(n x mm) (nom.)
LEAD SHEATH
SHEATH (mm)
SHEATH (mm)
MESC CODE
INSULATION
SERIAL NO.
SIZE (mm2)
DIA. (mm)
COLOR
PAIR
(mm)
(mm)
(mm)
(mm)
Nom.
Min.
H.2 0414-08P00150-WLBK8-LV Black 8P 1.5 7x0.53 0.44 1.3 20.3 1.2 22.5 1.0 24.6 1.25 27.1 1.8 1.24 30.1 2234
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 14 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, UNARMORED FIRE RESISTANT
CU/MICA/XLPE/OA.SCR/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331-21 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-08-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
CONSTRUCTION:
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Insulation Mica impregnated Glass Tape + Cross linked polyethylene (XLPE) to EN 50290-2-29.
Pair Construction Two insulated conductor are uniformly twisted to form a pair with 10-14 twists per meter.
Cabling Required number of twisted pairs are assembled with non-hygroscopic filler if required and
the assembly is wrapped with a polyester binder tape.
Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
down in contact with a stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run
longitudinally over the binder tape.
Outer Sheath Flame retardant PVC as per BS EN 50290-2-22. The Color of the sheath is as per
Dimension sheet.
Technical Data:
Operating Temperature -15°C to 90°C
Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair)
Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)
Page 15 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, UNARMORED FIRE RESISTANT
CU/MICA/XLPE/OA.SCR/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331-21 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-08-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
DIMENSIONAL DATA:
THICKNESS (mm)
OUTER SHEATH
APPROX. OVERALL
MIN. INSULATION
THICKNESS (mm)
APPROX. CABLE
OUTER SHEATH
WEIGHT (kg/km)
STRAND x DIA.
(n x mm) (nom.)
MESC CODE
SERIAL NO.
PAIR/TRIAD
SIZE (mm2)
DIA. (mm)
COLOR
Nom.
Min.
H.3 021G-01P00150-U0BK8-E5 Black 1P 1.5 7x0.53 0.44 1.1 0.67 9.3 101
H.4 021G-01P00150-U0BK8-E5 Black 1P 1.5 7x0.53 0.44 1.1 0.67 9.3 101
Note:
1. The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 16 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, UNARMORED FLAME RETARDANT
CU/XLPE/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-09-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Cabling Cores are assembled in a concentric layer and laid up with non-hygroscopic filler if required
and assembly is wrapped with polyester binder tape.
Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1.The color of the sheath shall as per
dimension sheet
Printing on the sheath CU/XLPE/PVC NO OF CORES C X MM2 600/1000V MESC YEAR IEC 60502-1 IEC 60332-3
CAT C LENGTH METER MARKING
Technical Data:
Page 17 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, UNARMORED FLAME RETARDANT
CU/XLPE/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-09-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
DIMENSIONAL DATA:
THICKNESS (mm)
OUTER SHEATH
MIN. NO. OF STRANDS
APPROX. OVERALL
THICKNESS (mm)
APPROX. CABLE
OUTER SHEATH
WEIGHT (kg/km)
MESC CODE
INSULATION
SERIAL NO.
SIZE (mm2)
DIA. (mm)
COLOR
CORE
Nom.
Min.
H.5 7614-04C00400-U0BK8-00 Black 4C 4 7 0.7 1.8 1.24 12.7 294
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm, ± 3.0mm above 30mm & ± 3.5mm above
50mm.
Page 18 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, ARMORED FLAME RETARDANT
CU/XLPE/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-10-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
CONSTRUCTION:
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Cabling Cores are assembled in a concentric layer and laid up with non-hygroscopic filler if required
and assembly is wrapped with polyester binder tape.
Inner Sheath Extruded PVC compatible with the operating temperature of the conductor in Black color.
Armor A single layer of galvanized steel wire armor to IEC 60502-1 is applied over the inner sheath.
Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1. The color of the sheath shall as per
dimension sheet
Printing on the sheath CU/XLPE/PVC/GSWA/PVC NO OF CORES C X MM2 600/1000V MESC YEAR IEC 60502-1
IEC 60332-3 CAT C LENGTH METER MARKING
Technical Data:
Operating Temperature -15°C to +90°C
Page 5 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, ARMORED FLAME RETARDANT
CU/XLPE/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-10-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021
DIMENSIONAL DATA:
THICKNESS (mm)
OUTER SHEATH
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
THICKNESS (mm)
APPROX. CABLE
OUTER SHEATH
NO. OF STRAND
WEIGHT (kg/km)
INNER SHEATH
SHEATH (mm)
MESC CODE
INSULATION
SIZE (mm2)
DIA. (mm)
SERIAL
COLOR
CORE
(mm)
(mm)
NO.
Nom
Min
H.7 7614-04C00400-W0BK8-00 Black 4C 4 7 0.7 1.0 11.7 0.9 13.5 1.8 1.24 16.7 575
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 5 of 22
Middle East Specialized Cables Co. Date: 07/12/2021
CONSTRUCTIONAL & TECHNICAL DATA SHEET
CABLE CODE 152G-01P20AWG-WLBK8-50
Customer PUNJ LLYOD LTD
MESC Ref. No. TD-207351-11-00
Item No. R.6
Reference Standard Unit EIA RS-485 APPLICATIONS
Size n x AWG 1P x 20AWG
Voltage grade 300V
CONDUCTOR CONSTRUCTION
Size 20AWG
Specification STRANDED ANNEALED TINNED CIRCULAR COPPER
Stranding n x mm 7 x 0.30
INSULATION MICA IMPREGNATED GLASS TAPE + XLPE
Thickness mm 0.80
Conductor Colour Coding SINGLE PAIR - WHITE/BLUE STRIPE AND BLUE/WHITE STRIPE
Pair/triad cables SINGLE PAIR
Pair/Triad Construction PAIR TWISTED WITH 10 to 12 TWISTS PER METER
Overall Screen ALUMINIUM BACKED MYLAR TAPE + TINNED COPPER BRAID
Thickness & Overlap mm/% 0.025/25 OF ALUMINIUM BACKED MYLAR TAPE
Drain Wire Material & Size n x mm TINNED COPPER (7 x 0.3 = 20AWG)
INNER JACKET FLAME RETARDANT PVC IN BLACK COLOR
Thickness mm 1.0
Diameter over inner jacket mm 12.1
LEAD SHEATH LEAD SHEATH
Thickness mm 1.1
Diameter over lead sheath mm 14.3
BEDDING FLAME RETARDANT PVC IN BLACK COLOR
Thickness mm 1.0
Diameter over bedding mm 16.4
ARMOR Material GALVANIZED STEEL WIRE
Armor wire diameter mm 1.25
Diameter over armor mm 18.9
OUTER JACKET/COLOR FLAME RETARDANT PVC IN BLACK COLOR
Thickness mm 1.6
Overall diameter mm 22.5 ± 2.5mm
Cable Weight (Approx.) kg/km 1414
Standard Length meter AS PER DRUM SCHEDULE
Embossing text at evey meter TYPE CM RS 485 1 X 2 X 20AWG LC/SWA/PVC 300V MESC YEAR LENGTH
METER MARKING
Cond. Res. at 20ºC (Nominal) Ω/km 37.43
Velocity of Propogation (Nominal) % 66
Mutual Capacitance at 1kHz (Nominal) nF/km Core to core: 42 Core to screen: 75.5
Insulation Resistance (minimum) MΩ-km 1000
Nominal Impedance Ω 120
Bending Radius mm 402
Operating Temperature °C -15 to +90
FLAMMABILITY CHARACTERISTICS
Flammability Test IEC 60332-1
Fire Resistance (Circuit Integrity Test) IEC 60331-21(180mins. @ 750ºC)
Oxygen Index to ASTM D2863 % MIN. 30
HCL Gas Emission to IEC 60754-1 % MAX.17
NOTE: Non-hygroscopic filler should provide if required
Middle East Specialized Cables (MESC) Date: 07/12/2021
CONSTRUCTIONAL & TECHNICAL DATA SHEET
CABLE CODE 152G-01P20AWG-U2BK8-50
Customer PUNJ LLYOD LTD
MESC Ref. No. TD-207351-12-00
Item No. R.7
Reference Standard Unit EIA RS-485 APPLICATIONS
Size n x AWG 1P x 20AWG
Voltage grade 300V
CONDUCTOR CONSTRUCTION
Size 20AWG
Specification STRANDED ANNEALED TINNED CIRCULAR COPPER
Stranding n x mm 7 x 0.30
INSULATION MICA IMPREGNATED GLASS TAPE + XLPE
Thickness mm 0.8
Conductor Colour Coding SINGLE PAIR: WHITE/BLUE Stipe and BLUE/WHITE Stripe;
Single pair/triad cables ONE PAIR
Pair/Triad Construction PAIR TWISTED WITH 10 to 12 TWISTS PER METER
Overall Screen ALUMINIUM BACKED MYLAR TAPE + TINNED COPPER BRAID COVERAGE
Thickness & Overlap mm/% 0.025/25 OF ALUMINIUM BACKED MYLAR TAPE
Drain Wire Material & Size n x mm TINNED COPPER (7x0.3mm = 20AWG )
INNER JACKET NA
Thickness mm NA
Diameter over inner jacket mm NA
ARMOR Material NA
Armor wire diameter mm NA
Diameter over armor mm NA
OUTER JACKET/COLOR FLAME RETARDANT PVC IN BLACK COLOR
Thickness mm 1.2
Overall diameter mm 12.1 ± 2.5mm
Cable Weight (Approx.) kg/km 180
Standard Length meter AS PER DRUM SCHEDULE
Embossing text at evey meter RS485 1PR20AWG PVC 300V MESC YEAR LENGTH
METER MARKING
Cond. Res. at 20ºC (Nominal) Ω/km 37.43
Velocity of Propogation (Nominal) % 66
Mutual Capacitance at 1kHz (Nominal) nF/km Core to core: 42 Core to screen: 75.5
Insulation Resistance (minimum) MΩ-km 1000
Nominal Impedance Ω 120
Bending Radius mm 221
Temperature Range °C -15º to +90º
FLAMMABILITY CHARACTERISTICS
Flammability Test IEC 60332-1
Fire Resistance (Circuit Integrity Test) IEC 60331-21(180mins. @ 750ºC)
Oxygen Index to ASTM D2863 % MIN. 30
HCL Gas Emission to IEC 60754-1 % ≤ 17% (IEC 60754-1)
NOTE: Non-hygroscopic filler should provide if required
TC-F-TD-06-R0-MAR-20