You are on page 1of 24

Middle East Specialized Cables (MESC)

POWER CABLE
MULTI CORE, UNARMORED FIRE RESISTANCE
CU/MICA/XLPE/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-01-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

CONSTRUCTION:
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation Mica impregnated Glass Tape + Cross linked polyethylene (XLPE) to IEC 60502-1.

Color Code 3C: Red, Yellow & Blue


4C: Red, Yellow, Blue & Black

Cabling Cores are assembled in a concentric layer laid up with non-hygroscopic filler if required and
assembly is wrapped with polyester tape.

Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1. The Color of the sheath is as per Dimension
sheet.

Printing on the sheath CU/MICA/XLPE/PVC NO OF CORES C X MM2 600/1000V MESC YEAR IEC 60502-1 IEC
60331 IEC 60332-3 CAT C LENGTH METER MARKING

Technical Data:
Operating Temperature -15°C to +90°C

Voltage Rating 600/1000 Volts as per IEC 60502-1

DC Cond. Res. at 20ºC Max. (Ω/km) 7.41 (2.5mm²), 4.61 (4mm²)

Voltage Withstand (V/Minute) 3500 VRMS / 5 or 8400 VDC / 5

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 CAT C

IEC 60331-21(750ºC @ 90 minutes)


Fire Resistance
Halogen Acid Gas (Outer Sheath) MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV Resistance (Outer Sheath) ISO 4892 (500Hrs)

Min. Bending Radius 12 x Cable Overall Diameter

Page 1 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, UNARMORED FIRE RESISTANCE
CU/MICA/XLPE/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-01-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

DIMENSIONAL DATA:

APPROX. OVERALL
THICKNESS (mm)
THICKNESS (mm)

APPROX. CABLE
OUTER SHEATH

OUTER SHEATH

WEIGHT (kg/km)
STRAND x DIA.
MESC CODE

INSULATION
SERIAL NO

SIZE (mm2)

DIA. (mm)
(n x mm)
COLOR

CORE

R.1 761G-03C00250-U0BK8-00 Black 3 2.5 7x0.67 0.7 1.8 12.8 202


H.6 761G-04C00400-U0BK8-00 Black 4 4 7x0.85 0.7 1.8 15.1 318

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 2 of 22
Middle East Specialized Cables (MESC)
POWER & CONTROL CABLE
MULTI CORE, LEAD SHEATHED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1, IEC 60331-21 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-02-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

CONSTRUCTION:
Conductor Sector shaped stranded annealed plain copper Class 2 as per IEC 60228.

Insulation Mica impregnated Glass Tape + Cross linked polyethylene (XLPE) to IEC 60502-1.

Color Code 3C: Red, Yellow & Blue.

Cabling Cores are assembled in a concentric layer laid up with non-hygroscopic filer if required and
assembly is wrapped with polyester tape.

Inner Sheath Flame retardant PVC Type ST-2 to IEC 60502-1 in Black color.

Lead Sheath Lead sheath to IEC 60502-1.

Bedding Flame retardant PVC Type ST-2 to IEC 60502-1 in Black color.

Armor A single layer of galvanized steel wire armor to IEC 60502-1 is applied over the bedding.

Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1. The color of the sheath is as per dimension
sheet.

Printing on the sheath CU/MICA/XLPE/PVC/LC/PVC/GSWA/PVC NO. OF CORES C X ... MM2 600/1000V MESC
YEAR IEC 60502-1 IEC 60331 IEC 60332-3 CAT C LENGTH METER MARKING

Technical Data:
Operating Temperature -15°C to +90°C

Voltage Rating 600/1000 Volts as per IEC 60502-1

DC Cond. Res. at 20ºC Max. (Ω/km) 0.727 (25mm2)

Voltage Withstand (V/Minute) 3500 VRMS / 5 or 8400 VDC / 5

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 CAT C

Fire Resistance IEC 60331-21(750ºC @ 90 minutes)

Halogen Acid Gas (Outer Sheath) MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV Resistance (Outer Sheath) ISO 4892 (500hrs)

Min. Bending Radius 20 x Cable Overall Diameter

Page 3 of 22
Middle East Specialized Cables (MESC)
POWER & CONTROL CABLE
MULTI CORE, LEAD SHEATHED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1, IEC 60331-21 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-02-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

DIMENSIONAL DATA:

THICKNESS (mm)
OUTER SHEATH
MIN. NO. OF. STRANDS

OVERALL DIA. (mm)


DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

APPROX. CABLE

APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH

BEDDING (mm)
LEAD SHEATH
SHEATH (mm)

SHEATH (mm)
MESC CODE

INSULATION
SERIAL NO.

SIZE (mm2)

DIA. OVER
BEDDING
COLOR

CORE

(mm)

(mm)

Nom.

Min.
R.2 76FG-03C02500-WLBK8-LO Black 3C 25 7 0.9 1.0 18.7 1.2 20.9 1.0 23.0 1.6 26.2 1.9 1.32 29.6 2681

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm, ± 3.0mm above 30mm & ± 3.5mm
above 50mm.

Page 4 of 22
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, ARMORED FIRE RESISTANCE CABLE
CU/MICA/XLPE/OA.SCR/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-03-00 Date: 08.12.2021 Customer Ref.: EMAIL DATED: 06.12.2021

CONSTRUCTION:
Conductor Stranded annealed plain copper to Class 2 of IEC 60228.

Insulation Mica impregnated Glass Tape + Cross linked polyethylene (XLPE) to EN 50290-2-29.

Single pair: Black & White


Color Code

Two insulated conductor are uniformly twisted to form a pair with 10-14 twists per meter.
Pair Construction

Required number of twisted pairs are assembled with non-hygroscopic filler if required and
Cabling
assembly is wrapped with a polyester binder tape.

Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
Collective Screen
down in contact with a stranded tinned copper drain wire of 0.5mm² (7x0.3mm) run
longitudinally over the binder tape.

Flame retardant PVC to BSEN 50290-2-22 in Black color.


Inner Sheathing

A single layer of galvanized steel wire armor to BS EN10257-1 is applied over the inner
Wire Armor
sheath.

Outer sheath Flame retardant PVC to BSEN 50290-2-22. The color of the sheath is as per dimension
sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/MICA/XLPE/PVC/GSWA/PVC SHIELDED NO. OF PAIRS


X 2 X MM2 500V MESC YEAR BS EN 50288-7 IEC 60331 IEC 60332-3 CAT C LENGTH
METER MARKING

Technical Data:
Operating temperature -15°C to 90°C

Voltage Rating 500 Volts

Conductor Resistance (at 20ºC) ≤ 12.34 (1.5mm2) Ω/km

Mutual Capacitance (at 1kHz) ≤ 120nF/km

Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance ≥ 1000MΩ-km at 20°C (500 VDC for 1 minute)

Dielectric Strength Test (core to core & 2000 VAC / 3000 VDC for 1 minute
core to screen)

Page 5 of 22
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, ARMORED FIRE RESISTANCE CABLE
CU/MICA/XLPE/OA.SCR/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-03-00 Date: 08.12.2021 Customer Ref.: EMAIL DATED: 06.12.2021

Flame Behavior Characteristics:


Flame Retardant (Outer Sheath) IEC 60332-3 CAT C

Fire Resistance IEC 60331-21(750ºC @ 90 minutes)

Halogen Acid Gas (Outer Sheath) MAX. 17 % (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV / Sunlight Resistance (Outer ISO 4892 (500hrs.)


Sheath)
Oil Resistance (Outer Sheath) EC 60811-404

Min. Bending Radius 12 x Cable Overall Diameter

DIMENSIONAL DATA:

DIA. OVER INNER SHEATH

APPROX. CABLE WEIGHT


OUTER SHEATH
DIA. OVER ARMOR (mm)
ARMOR WIRE DIA. (mm)

APPROX. OVERALL DIA.


THICKNESS
THICKNESS (mm)

THICKNESS (mm)
STAND No X mm
OUTER SHEATH

INNER SHEATH

(mm)
SIZE (mm²)
MESC CODE

INSULATION
PAIR/TRIAD
SERIAL NO

(kg/km)
COLOR

(mm)

(mm)
Nom

R.3 021G-01P00150-W0BK8-E5 Black 1P 1.5 7x0.53 0.44 0.9 9.3 0.9 11.1 1.3 Min
0.84 13.3 318

Note:
 The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 6 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-04-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

CONSTRUCTION
Conductor Stranded annealed plain copper as per Class 2 of IEC 60228.

Insulation Mica impregnated glass tape + Cross linked polyethylene (XLPE) to EN 50290-2-29.

Color Code Multi Pair: Black & White with each core numbered.

Pair Construction Two insulated conductor are uniformly twisted to form a pair with 10-14 twists per meter.

Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25%
with the metallic side down in contact with a stranded tinned copper drain wire of 0.5mm2
(7x0.3mm). All pair shields are electrically isolated from each other.

Cabling Required number of individually screened pairs are assembled with non-hygroscopic filler
if required and the assembly is wrapped with a polyester binder tape.

Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic
side down in contact with a stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run
longitudinally over the binder tape.

Inner Sheath Flame retardant PVC to EN 50290-2-22 in Black color.

Lead Sheath Lead sheath to EN 50307.

Bedding Flame retardant PVC to EN 50290-2-22 in Black color.

Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the bedding.

Outer Sheath Flame retardant PVC to EN 50290-2-22. The color of the sheath is as per dimension
sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/MICA/XLPE/PVC/LC/PVC/GSWA/PVC SHIELDED NO


OF PAIRS X 2 X …MM2 500V MESC YEAR BS EN 50288-7 IEC 60331 IEC 60332-3
CAT C LENGTH METER MARKING

Technical Data:
Operating Temperature -15°C to 90°C

Voltage Rating 500V as per BS EN 50288-7

Conductor Resistance (at 20ºC) ≤ 12.34 (1.5mm2) Ω/km

Mutual Capacitance (at 1kHz) ≤ 120nF/km

Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance ≥ 1000MΩ-km at 20°C (500 VDC for 1 minute)

Dielectric Strength Test (core to core & 2000 Vac / 3000 Vdc for 1 minute
core to screen)

Page 7 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-04-00 Date: 08.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

Flame Behavior Characteristics:


Flame Retardant (Outer Sheath) IEC 60332-3 CAT C

Fire Resistance IEC 60331-21(750ºC @ 90 minutes)

Halogen Acid Gas (Outer Sheath) MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV Resistance (Outer Sheath) ISO 4892 (500 Hrs)

Oil Resistance (Outer Sheath) IEC 60811 - 404

Min. Bending Radius 20 x Cable Overall Diameter

DIMENSIONAL DATA

THICKNESS (mm)
OUTER SHEATH

APPROX. OVERALL
DIA. OVER ARMOR
MESC CODE

ARMOR WIRE DIA.


DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

BEDDING THICK.

APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH

BEDDING (mm)
STRAND x DIA.

LEAD SHEATH
SHEATH (mm)

SHEATH (mm)
INSULATION
SIZE (mm2)

DIA. OVER

DIA. (mm)
(n x mm)
COLOR

PAIR

(mm)

(mm)

(mm)
SERIAL
NO.

Nom.

Min.
R.4 041G-12P00150-WLBK8-LV Black 12P 1.5 7X0.53 0.44 1.5 30.0 1.4 32.6 1.0 34.7 1.6 37.9 1.9 1.32 41.1 3842

Note:
 The tolerance on the cable overall diameter shall be ± 2.0mm up to 30mm & ± 2.5mm above 30mm.

Page 8 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-05-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228

Insulation Mica impregnated Glass Tape + Cross linked polyethylene (XLPE) to EN 50290-2-29.

Color Code Multi pair: Black & White with each core numbering.

Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.

Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25% with
metallic side down in contact with a stranded annealed tinned copper drain wire of 0.5mm2
(7x0.3mm). All pair shields are electrically isolated from each other.

Cabling Required number of individually screened pair are assembled with non-hygroscopic filler if
required and the assembly is wrapped with a polyester binder tape.

Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic
side down in contact with a stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run
longitudinally over the binder tape.

Inner Sheath Flame retardant PVC as per BS EN 50290-2-22 in Black color.

Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the inner
sheath.

Outer Sheath Flame retardant PVC as per BS EN 50290-2-22. The color of the sheath is as per
dimension sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/MICA/XLPE/PVC/GSWA/PVC SHIELDED NO OF


PAIRS X 2 X … MM2 500V MESC YEAR BS EN 50288-7 IEC 60331 IEC 60332-3 CAT C
LENGTH METER MARKING

Technical Data:
Operating temperature -15°C to 90°C

Voltage Rating 500 Volts

Conductor Resistance ≤ 12.34 (1.5mm2) Ω/km

Mutual Capacitance (at 1kHz) ≤ 120nF/km

Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair)

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance ≥ 1000MΩ-km at 20°C (500 VDC for 1 minute)

Dielectric Strength Test (core to core & 2000 VAC / 3000 VDC for 1 minute
core to screen)

Page 9 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-05-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 CAT C

Fire Resistant IEC 60331-21(750ºC @ 90 minutes)

Halogen Acid Gas MAX. 17% (IEC 60754-1)

Limiting Oxygen Index ≥ 30% (ASTM D2863)

UV Resistance (Outer Sheath) ISO 4892(500Hrs)

Oil Resistance (Outer Sheath) IEC 60811 - 404

Min. Bending Radius 12 x Cable Overall Diameter

DIMENSIONAL DATA:

THICKNESS (mm)
OUTER SHEATH
THICKNESS Min (mm)

DIA. OVER ARMOR

APPROX OVERALL
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

APPROX. CABLE
OUTER SHEATH

WEIGHT (kg/km)
DIAMETER(mm)
INNER SHEATH
STRAND x DIA.

SHEATH (mm)
MESC CODE

INSULATION
SERIAL NO

SIZE (mm2)

(n x mm)
COLOR

(mm)

(mm)
PAIR

Min at a
Nom

Pt.
R.5 041G-12P00150-W0BK8-E5 Black 12P 1.5 7X0.53 0.44 1.5 30.0 1.6 33.2 1.8 1.24 36.2 2028

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm, ± 3.0mm above 30mm & ± 3.5mm above
50mm.

Page 10 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-06-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

CONSTRUCTION:
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation Cross-linked polyethylene XLPE to IEC 60502-1.

Color Code 3C: Red, Yellow & Blue

Cabling Cores are assembled in a concentric layer and laid up with non-hygroscopic filler if required
and assembly is wrapped with polyester binder tape.

Inner Sheath Flame retardant PVC Type ST-2 to IEC 60502-1 in Black color.

Lead Sheath Lead sheath to IEC 60502-1.

Bedding Flame retardant PVC Type ST-2 to IEC 60502-1 in Black color.

Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the bedding.

Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1. The color of the sheath is as per dimension
sheet.

Printing on the sheath CU/XLPE/PVC/LC/PVC/GSWA/PVC NO OF CORES C X ... MM2 600/1000V MESC YEAR
IEC 60502-1 IEC 60332-3 CAT C LENGTH METER MARKING

Technical Data:
Operating Temperature -15°C to +90°C

Voltage Rating 600/1000 Volts as per IEC 60502-1

DC Cond. Res. at 20ºC Max. (Ω/km) 4.61 (4mm2)

Voltage Withstand (V/Minute) 3500 VRMS / 5 or 8400 VDC / 5

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 CAT C

Halogen Acid Gas (Outer Sheath) MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV Resistance (Outer Sheath) ISO 4892 (500 Hrs.)

Min. Bending Radius 20 x Cable Overall Diameter

Page 11 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-06-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

DIMENSIONAL DATA:

THICKNESS (mm)
MIN. NO. OF STRANDS

OUTER SHEATH

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

BEDDING THICK.

APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH

BEDDING (mm)
NO OF CORES

LEAD SHEATH
SHEATH (mm)

SHEATH (mm)
MESC CODE

INSULATION
SIZE (mm2)

DIA. OVER

DIA. (mm)
SERIAL

COLOR

(mm)

(mm)

(mm)
NO.

Nom.

Min.
H.1 7614-03C00400-WLBK8-LO Black 3C 4 7 0.7 1.0 10.7 1.2 12.9 1.0 15.0 1.25 17.5 1.8 1.24 20.5 1234

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 12 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR, INDIVIDUALLY & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-07-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

CONSTRUCTION
Conductor Stranded annealed plain copper as per Class 2 of IEC 60228.

Insulation Cross linked Polyethylene (XLPE) to EN 50290-2-29.

Color Code Multi pair: Blue & White with each core numbered.

Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.

Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25% with
the metallic side down in contact with a stranded tinned copper drain wire of 0.5mm2
(7x0.3mm). All pair shields are electrically isolated from each other.

Cabling Required numbers of individually screened pair are assembled with non-hygroscopic filler if
required and the assembly is wrapped with a polyester binder tape.

Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
down in contact with a stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run
longitudinally over the binder tape.

Inner Sheath Flame retardant PVC to EN 50290-2-22 in Black color.

Lead Sheath Lead sheath to EN 50307.

Bedding Flame retardant PVC to EN 50290-2-22 in Black color.

Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the bedding.

Outer Sheath Flame retardant PVC to EN 50290-2-22. The color of the sheath is as per dimension sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/XLPE/PVC/LC/PVC/GSWA/PVC SHIELDED NO. OF


PAIRS X 2 X … MM2 500V MESC YEAR BS EN 50288-7 IEC 60332-3 CAT C LENGTH
METER MARKING

Technical Data:
Operating Temperature -15ºC to +90ºC

Voltage Rating 500 Volts

Conductor Resistance ≤ 12.34 (1.5mm2) Ω/km at 20ºC

Mutual Capacitance (at 1kHz) ≤ 120nF/km

Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance ≥ 1000MΩ-km at 20°C (500 VDC for 1 minute)

Dielectric Strength Test (core to core & 2000 VAC / 3000 VDC for 1 minute
core to screen)

Page 13 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR, INDIVIDUALLY & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-07-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

Flame Behavior Characteristics:


Flame Retardant (Outer Sheath) IEC 60332-3 CAT C

Halogen Acid Gas (Outer Sheath) MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV Resistance (Outer Sheath) ISO 4892(500Hrs)

Oil Resistance (Outer Sheath) IEC 60811-404

Min. Bending Radius 20 x Cable Overall Diameter

DIMENSIONAL DATA

THICKNESS (mm)
OUTER SHEATH
BEDDING THICKNESS

DIA. OVER BEDDING

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH
STRAND x DIA.
(n x mm) (nom.)

LEAD SHEATH
SHEATH (mm)

SHEATH (mm)
MESC CODE

INSULATION
SERIAL NO.

SIZE (mm2)

DIA. (mm)
COLOR

PAIR

(mm)

(mm)

(mm)

(mm)

Nom.

Min.
H.2 0414-08P00150-WLBK8-LV Black 8P 1.5 7x0.53 0.44 1.3 20.3 1.2 22.5 1.0 24.6 1.25 27.1 1.8 1.24 30.1 2234

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 14 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, UNARMORED FIRE RESISTANT
CU/MICA/XLPE/OA.SCR/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331-21 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-08-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

CONSTRUCTION:
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation Mica impregnated Glass Tape + Cross linked polyethylene (XLPE) to EN 50290-2-29.

Color Code Single pair: Black & White.

Pair Construction Two insulated conductor are uniformly twisted to form a pair with 10-14 twists per meter.

Cabling Required number of twisted pairs are assembled with non-hygroscopic filler if required and
the assembly is wrapped with a polyester binder tape.

Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
down in contact with a stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run
longitudinally over the binder tape.

Outer Sheath Flame retardant PVC as per BS EN 50290-2-22. The Color of the sheath is as per
Dimension sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/MICA/XLPE/PVC SHIELDED NO OF PAIRS X 2 X …


MM2 500V MESC YEAR BS EN 50288-7 IEC60331 IEC 60332-3 CAT C LENGTH METER
MARKING

Technical Data:
Operating Temperature -15°C to 90°C

Voltage Rating 500V

Conductor Resistance ≤ 12.34 (1.5 mm2) Ω/km at 20ºC

Mutual Capacitance (at 1kHz) ≤ 120nF/km

Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair)

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance Constant ≥ 1000MΩ-km at 20°C (500 VDC for 1 minute)

Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)

Page 15 of 22
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, UNARMORED FIRE RESISTANT
CU/MICA/XLPE/OA.SCR/PVC
SPECIFICATION: BS EN 50288-7, IEC 60331-21 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-08-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

Flame Behavior Characteristics:


Flame Retardant (Outer Sheath) IEC 60332-3 CAT C

Fire Resistance IEC 60331-21(750ºC @ 90 minutes)

Halogen Acid Gas (Outer Sheath) MAX. 17 % (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV / Sunlight Resistance (Outer ISO 4892 (500hrs.)


Sheath)
Oil Resistance (Outer Sheath) EC 60811-404

Min. Bending Radius 12 x Cable Overall Diameter

DIMENSIONAL DATA:

THICKNESS (mm)
OUTER SHEATH

APPROX. OVERALL
MIN. INSULATION
THICKNESS (mm)

APPROX. CABLE
OUTER SHEATH

WEIGHT (kg/km)
STRAND x DIA.
(n x mm) (nom.)
MESC CODE
SERIAL NO.

PAIR/TRIAD

SIZE (mm2)

DIA. (mm)
COLOR

Nom.

Min.

H.3 021G-01P00150-U0BK8-E5 Black 1P 1.5 7x0.53 0.44 1.1 0.67 9.3 101

H.4 021G-01P00150-U0BK8-E5 Black 1P 1.5 7x0.53 0.44 1.1 0.67 9.3 101
Note:
1. The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 16 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, UNARMORED FLAME RETARDANT
CU/XLPE/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-09-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation Cross linked polyethylene (XLPE) to IEC 60502-1.

Color Code 4C: Red, Yellow, Blue & Black.

Cabling Cores are assembled in a concentric layer and laid up with non-hygroscopic filler if required
and assembly is wrapped with polyester binder tape.

Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1.The color of the sheath shall as per
dimension sheet

Printing on the sheath CU/XLPE/PVC NO OF CORES C X MM2 600/1000V MESC YEAR IEC 60502-1 IEC 60332-3
CAT C LENGTH METER MARKING

Technical Data:

Operating temperature -15°C to 90°C

Voltage Rating 600/1000 Volts as per IEC 60502-1

DC Cond. Res. at 20ºC Max. (Ω/km) ≤ 4.61(4mm²)

Voltage Withstand (V/Minute) 3500 VRMS / 5 or 8400 VDC / 5

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 (CAT C)

Halogen Acid Gas (Outer Sheath) MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV Resistance (Outer Sheath) ISO 4892 (500Hrs)

Min. Bending Radius 12 x Cable Overall Diameter

Page 17 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, UNARMORED FLAME RETARDANT
CU/XLPE/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-09-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

DIMENSIONAL DATA:

THICKNESS (mm)
OUTER SHEATH
MIN. NO. OF STRANDS

APPROX. OVERALL
THICKNESS (mm)

APPROX. CABLE
OUTER SHEATH

WEIGHT (kg/km)
MESC CODE

INSULATION
SERIAL NO.

SIZE (mm2)

DIA. (mm)
COLOR

CORE

Nom.

Min.
H.5 7614-04C00400-U0BK8-00 Black 4C 4 7 0.7 1.8 1.24 12.7 294

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm, ± 3.0mm above 30mm & ± 3.5mm above
50mm.

Page 18 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, ARMORED FLAME RETARDANT
CU/XLPE/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-10-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

CONSTRUCTION:
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation Cross linked polyethylene (XLPE) to IEC 60502-1.

Color Code 4C: Red, Yellow, Blue & Black

Cabling Cores are assembled in a concentric layer and laid up with non-hygroscopic filler if required
and assembly is wrapped with polyester binder tape.

Inner Sheath Extruded PVC compatible with the operating temperature of the conductor in Black color.

Armor A single layer of galvanized steel wire armor to IEC 60502-1 is applied over the inner sheath.

Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1. The color of the sheath shall as per
dimension sheet

Printing on the sheath CU/XLPE/PVC/GSWA/PVC NO OF CORES C X MM2 600/1000V MESC YEAR IEC 60502-1
IEC 60332-3 CAT C LENGTH METER MARKING

Technical Data:
Operating Temperature -15°C to +90°C

Voltage Rating 600/1000 Volts as per IEC 60502-1

DC Cond. Res. at 20ºC Max. (Ω/km) ≤ 4.61 (4mm2)

Voltage Withstand (V/Minute) 3500 VRMS / 5 or 8400 VDC / 5

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 (CAT C)

Halogen Acid Gas (Outer Sheath) MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV Resistance (Outer Sheath) ISO 4892 (500Hrs)

Min. Bending Radius 12 x Cable Overall Diameter

Page 5 of 22
Middle East Specialized Cables (MESC)
POWER CABLE
MULTI CORE, ARMORED FLAME RETARDANT
CU/XLPE/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-207351-10-00 Date: 07.12.2021 Inq. Ref.: EMAIL DATED: 06.12.2021

DIMENSIONAL DATA:

THICKNESS (mm)
OUTER SHEATH

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
THICKNESS (mm)

DIA. OVER INNER


THICKNESS (mm)

APPROX. CABLE
OUTER SHEATH

NO. OF STRAND

WEIGHT (kg/km)
INNER SHEATH

SHEATH (mm)
MESC CODE

INSULATION
SIZE (mm2)

DIA. (mm)
SERIAL

COLOR

CORE

(mm)

(mm)
NO.

Nom

Min
H.7 7614-04C00400-W0BK8-00 Black 4C 4 7 0.7 1.0 11.7 0.9 13.5 1.8 1.24 16.7 575

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 5 of 22
Middle East Specialized Cables Co. Date: 07/12/2021
CONSTRUCTIONAL & TECHNICAL DATA SHEET
CABLE CODE 152G-01P20AWG-WLBK8-50
Customer PUNJ LLYOD LTD
MESC Ref. No. TD-207351-11-00
Item No. R.6
Reference Standard Unit EIA RS-485 APPLICATIONS
Size n x AWG 1P x 20AWG
Voltage grade 300V
CONDUCTOR CONSTRUCTION
Size 20AWG
Specification STRANDED ANNEALED TINNED CIRCULAR COPPER
Stranding n x mm 7 x 0.30
INSULATION MICA IMPREGNATED GLASS TAPE + XLPE
Thickness mm 0.80
Conductor Colour Coding SINGLE PAIR - WHITE/BLUE STRIPE AND BLUE/WHITE STRIPE
Pair/triad cables SINGLE PAIR
Pair/Triad Construction PAIR TWISTED WITH 10 to 12 TWISTS PER METER
Overall Screen ALUMINIUM BACKED MYLAR TAPE + TINNED COPPER BRAID
Thickness & Overlap mm/% 0.025/25 OF ALUMINIUM BACKED MYLAR TAPE
Drain Wire Material & Size n x mm TINNED COPPER (7 x 0.3 = 20AWG)
INNER JACKET FLAME RETARDANT PVC IN BLACK COLOR
Thickness mm 1.0
Diameter over inner jacket mm 12.1
LEAD SHEATH LEAD SHEATH
Thickness mm 1.1
Diameter over lead sheath mm 14.3
BEDDING FLAME RETARDANT PVC IN BLACK COLOR
Thickness mm 1.0
Diameter over bedding mm 16.4
ARMOR Material GALVANIZED STEEL WIRE
Armor wire diameter mm 1.25
Diameter over armor mm 18.9
OUTER JACKET/COLOR FLAME RETARDANT PVC IN BLACK COLOR
Thickness mm 1.6
Overall diameter mm 22.5 ± 2.5mm
Cable Weight (Approx.) kg/km 1414
Standard Length meter AS PER DRUM SCHEDULE
Embossing text at evey meter TYPE CM RS 485 1 X 2 X 20AWG LC/SWA/PVC 300V MESC YEAR LENGTH
METER MARKING
Cond. Res. at 20ºC (Nominal) Ω/km 37.43
Velocity of Propogation (Nominal) % 66
Mutual Capacitance at 1kHz (Nominal) nF/km Core to core: 42 Core to screen: 75.5
Insulation Resistance (minimum) MΩ-km 1000
Nominal Impedance Ω 120
Bending Radius mm 402
Operating Temperature °C -15 to +90
FLAMMABILITY CHARACTERISTICS
Flammability Test IEC 60332-1
Fire Resistance (Circuit Integrity Test) IEC 60331-21(180mins. @ 750ºC)
Oxygen Index to ASTM D2863 % MIN. 30
HCL Gas Emission to IEC 60754-1 % MAX.17
NOTE: Non-hygroscopic filler should provide if required
Middle East Specialized Cables (MESC) Date: 07/12/2021
CONSTRUCTIONAL & TECHNICAL DATA SHEET
CABLE CODE 152G-01P20AWG-U2BK8-50
Customer PUNJ LLYOD LTD
MESC Ref. No. TD-207351-12-00
Item No. R.7
Reference Standard Unit EIA RS-485 APPLICATIONS
Size n x AWG 1P x 20AWG
Voltage grade 300V
CONDUCTOR CONSTRUCTION
Size 20AWG
Specification STRANDED ANNEALED TINNED CIRCULAR COPPER
Stranding n x mm 7 x 0.30
INSULATION MICA IMPREGNATED GLASS TAPE + XLPE
Thickness mm 0.8
Conductor Colour Coding SINGLE PAIR: WHITE/BLUE Stipe and BLUE/WHITE Stripe;
Single pair/triad cables ONE PAIR
Pair/Triad Construction PAIR TWISTED WITH 10 to 12 TWISTS PER METER
Overall Screen ALUMINIUM BACKED MYLAR TAPE + TINNED COPPER BRAID COVERAGE
Thickness & Overlap mm/% 0.025/25 OF ALUMINIUM BACKED MYLAR TAPE
Drain Wire Material & Size n x mm TINNED COPPER (7x0.3mm = 20AWG )
INNER JACKET NA
Thickness mm NA
Diameter over inner jacket mm NA
ARMOR Material NA
Armor wire diameter mm NA
Diameter over armor mm NA
OUTER JACKET/COLOR FLAME RETARDANT PVC IN BLACK COLOR
Thickness mm 1.2
Overall diameter mm 12.1 ± 2.5mm
Cable Weight (Approx.) kg/km 180
Standard Length meter AS PER DRUM SCHEDULE
Embossing text at evey meter RS485 1PR20AWG PVC 300V MESC YEAR LENGTH
METER MARKING
Cond. Res. at 20ºC (Nominal) Ω/km 37.43
Velocity of Propogation (Nominal) % 66
Mutual Capacitance at 1kHz (Nominal) nF/km Core to core: 42 Core to screen: 75.5
Insulation Resistance (minimum) MΩ-km 1000
Nominal Impedance Ω 120
Bending Radius mm 221
Temperature Range °C -15º to +90º
FLAMMABILITY CHARACTERISTICS
Flammability Test IEC 60332-1
Fire Resistance (Circuit Integrity Test) IEC 60331-21(180mins. @ 750ºC)
Oxygen Index to ASTM D2863 % MIN. 30
HCL Gas Emission to IEC 60754-1 % ≤ 17% (IEC 60754-1)
NOTE: Non-hygroscopic filler should provide if required
TC-F-TD-06-R0-MAR-20

Middle East Specialized Cables Company

Inquiry Ref. : E mail date: 06.12.2021 MESC Doc. No.: TC-207351-01-00


TECHNICAL
Project Name: EXPANSION AND CLARIFICATION Date: 08.12.2021
REVAMPING OF AHMADI DEPOT
Serial FINAL DECISION BY
No. CUSTOMER REQUIREMENTS MESC CLARIFICATION PURCHASER

No specification is attached to refer, hence MESC offered


as per BOQ description, details follow below,

Item no: R.1 (3CX2.5 SQ.MM-UNARMOURED)


CU/MICA/XLPE/PVC – 600/1000V as per IEC 60502-1.

Item no: R.2 (3CX25 SQ.MM-ARMOURED)


CU/MICA/XLPE/PVC/LC/PVC/GSWA/PVC – 600/1000V as
per IEC 60502-1.

Item no: R.3 (1PX1.5 SQ.MM-ARMOURED)


CU/MICA/XLPE/OS/PVC/GSWA/PVC – 500V as per BS
EN 50288-7.
(Cable description in BOQ given as un-armoured, but code
given with SWA armour, however MESC offer with
armoured)

Item no: R.4 (12PX1.5 SQ.MM-ARMOURED)


CU/MICA/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC – 500V
as per BS EN 50288-7.

Item no: R.5 (12PX1.5 SQ.MM-ARMOURED)


CU/MICA/XLPE/IS/OS/PVC/GSWA/PVC – 500V as per BS
EN 50288-7.

Item no: R.6 (1PX20AWG-ARMOURED)


CU/MICA/XLPE/PVC/LC/PVC/GSWA/PVC (O/A shielded &
O/A ATC braided) – 300V as per EIA RS-485 applications
1 Offered cables & gen to BS EN 50288-7.
(MESC offered RS-485 Fire resistant cables with minimum
conductor size of 20AWG, 24AWG with fire resistant is not
in MESC scope)

Item no: R.7 (1PX20AWG-UNARMOURED)


CU/MICA/XLPE/PVC (O/A shielded & O/A ATC braided) –
300V as per EIA RS-485 applications & gen to BS EN
50288-7.
(BOQ given with Silicon rubber, RS-485 fire resistant cable
with silicone rubber insulation will not meet the electrical
parameters as per EIA RS-485 applications standard,
however MESC offered with MICA+XLPE insulation for
meeting electrical parameters and also considered 20AWG
as per above point)

Item no: H.1 (3CX4 SQ.MM-ARMOURED)


CU/XLPE/PVC/LC/PVC/GSWA/PVC – 600/1000V as per
IEC 60502-1.

Item no: H.2 (8PX1.5 SQ.MM-ARMOURED)


CU/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC – 500V as per
BS EN 50288-7.

Item no: H.3 & H.4 (1PX1.5 SQ.MM-UNARMOURED)


CU/MICA/XLPE/OS/PVC - 500V as per BS EN 50288-7.
(BOQ given with silicone rubber, but MESC offered by
considering alternate material MICA+XLPE instead of
silicon rubber)
Page 1 of 2
TC-F-TD-06-R0-MAR-20

Middle East Specialized Cables Company

Item no: H.5 (4CX4 SQ.MM-UNARMOURED)


CU/XLPE/PVC – 600/1000V as per IEC 60502-1.

Item no: H.6 (4CX4 SQ.MM-UNARMOURED)


CU/MICA/XLPE/PVC – 600/1000V as per IEC 60502-1.

Item no: H.7 (4CX4 SQ.MM-ARMOURED)


CU/XLPE/PVC/GSWA/PVC – 600/1000V as per IEC
60502-1.
Prepared by: Approved by:

Technical Engineer Sr. Technical Manager – MESC Group

Page 2 of 2

You might also like