Sensor description:
CTL-202FTS/1000
Type: CTL-202FTS/1000
Due to high current supply value, this sensor cannot be supplied directly by the fieldbox
witch is limited to 26mA max current output.
The output signal is a copy of the current so if the current is AC then the Signal will also
be AC.
Due to those limitations we need to use manufacturer sensor supply and signal
conditioning module: CTA215-24.
Sensor connections:
Linearity : 0,1 % FS
Power Supply: From 18V to 36 V DC
Signal Output: DC: 4 – 20 mA, Active, DC proportional to RMS value of input.
Load resistance: 0 to 500 Ohms Max
Certification: None = To be installed in a safe zone.
Calibration: Module is Factory calibrated and matched with the sensor; check that
both are marqued with the same Serial Number.
Page 2/3
INSTALLATION:
2 kinds of rigup are available according to the cable route, interferences and zoning
conditions:
If no interferences from rig power cables, Notable interferences from rig power
0-50 mV Max signal to ML unit cables, 4 – 20 mA Signal ( Less affected )
Page 3/3
Gstock References: