UNIT STATUS REPORT

UNIT UMA 12

Outdoor Conditions 92 °F / 42 % RH

Diagnostic: Duct Static Pressure Failure Normal

Diagnostic: Outdoor Air Temperature Source Failure Normal

Diagnostic: Space Temperature Source Failure Normal

Cooling Output Command 24%

Heat Cool Mode Request Cool

Heating Output Command 0%

Supply Fan Speed Command 90%

Occupied Cooling Setpoint 73.0 °F

Occupied Heating Setpoint 70.0 °F

Occupied Offset 1.5 °F

Occupied Standby Offset 4.0 °F

Space Temperature Setpoint Active 73.0 °F

Unoccupied Cooling Setpoint 80.0 °F

Unoccupied Heating Setpoint 65.0 °F

Outdoor Air Temperature BAS 73.0 °F

Discharge Air Heating Setpoint BAS 80.0 °F

Duct Static Pressure Setpoint BAS 1.400 in(H2O)

Mixed Air Temperature Local 74.7 °F

Outdoor Air Temperature Local 32.0 °F

Discharge Air Temperature Setpoint Local 55.0 °F


55.0 °F

Discharge Air Temperature Setpoint Pgain 2

Heat Cool Mode Active Cool

Heat Output 1. Off

Heat Output 2. Off

Mixed Air Low Limit Active Off

Reset Filter Alarm Normal

Startup Delay Completed On

Supply Fan Start Stop Command. On

Supply Fan Status. On

Controller Time Jan 18, 2023, 01:49 PM

Firmware Revision 8.02.002

Location Label UMA-12

Model Name UC400

Outdoor Air Temperature Active 73.0 °F

Dirty Filter Alarm In Alarm

Supply Fan Failure Reset Normal

Filter Timer Reset Accumulating