You are on page 1of 6

PROPOSED FAÇADE, HOTEL INTERIOR AND MEP IMPROVEMENT WORKS TO

EXISTING CONSERVED SHOPHOUSES AT 28 ANN SIANG ROAD

Proposed by Dong Jian


Proposed Date 09/03/23
Item Digital Private Meter
Location For DB/BMST/01 & DB/KIT/02
Type Digtal
Code -
Quantity -
Lead Time Ex-Stock

IMAGE

Please refer to attachment

Brand CET
Description

Digital Private Meter

Specification
WISTEC ENGINEERS & ASSOCIATES
Please refer to attachment.
Signed: _______________
20.03.23
Date: _______________

*Client/Archi/I.D./C&S/________’s approval required.


Approved Date Amend and resubmit.
Approved By Approved with comments – no submission required.
Signature Approved for construction.

This approval does not absolve the Contractor from


complying with the requirements of the tender
specifications/drawings, submissions or nullify the
Consulting Engineer’s right to reject any such non-
compliance on site. Dimensional and positional correctness
and co-ordination with other services and building works
remain the responsibility of the Contractor.
PMC-53M-A
Digital Multifunction Meter

 IEC 62053-22 Class 0.5S  Large, Backlit LCD with Wide


 True RMS Measurements Viewing Angle
 THD with 31 Ind. Harmonics  Setpoint Alarms & SOE Logs
 K-Factor, Crest Factor and TDD  IP65 Enclosure with No Openings
 Unbalance & Phase Angles  Standard Tropicalization
 U and I Symmetrical Components  Industrial Grade Components
 Demands and Peak Demands  Extended Temperature
 Max/Min Log with Timestamp  Extended Warranty

Designed For Reliability Manufactured To Last


PMC-53M-A
Digital Multifunction Meter
Ease of use
 Large, backlit LCD display with wide viewing angle
 Intuitive user interface
 LED indicators for Energy Pulsing and Communication activities
 Password-protected setup via front panel or free PMC Setup software
 Easy installation with mounting clips, no tools required

Setpoints
 9 user programmable setpoints with extensive list of monitoring
parameters including Voltage, Current, Power, THD, … etc.
 Configurable thresholds, time delays and DO triggers

SOE Log
 100 events time-stamped to ±1ms resolution
 Setup changes, Setpoint and DI status changes and DO operations

Max/Min Log
 Max/Min Log with Timestamp for real-time measurements such as
The PMC-53M-A Digital Multifunction Meter is CET’s latest offer for the low-
Voltage, Current, In, Freq., kW, kvar, kVA, PF, Unbalance, K-factor, Crest
cost digital power/energy metering market. Housed in a standard DIN form
Factor and THD.
factor measuring 96x96x88mm, it is perfectly suited for industrial,  Configurable for This Month/Last Month or Before/Since Last Reset
commercial and utility applications. The PMC-53M-A features quality
construction, multifunction true RMS measurements and a large, backlit, 7- Diagnostics
segmant LCD. Compliance with the IEC 62053-22 Class 0.5S Standard, it is a  Frequency Out-of-Range, Loss of Voltage / Current
cost effective replacement for analog instrumentation that is capable of  kW Direction per phase and Total, Possible incorrect CT Polarity
displaying 3-phase measurements at once. It optionally provides four  Incorrect U & I Phase Sequence
Digital Inputs for status monitoring, two Relay Outputs for control and alarm
Communications
applications. The standard RS-485 port and Modbus RTU protocol support
 Optically isolated RS485 port at max. 38,400 bps
makes the PMC-53M-A a smart metering component of an intelligent,
 Standard Modbus RTU support
multifunction monitoring solution for any Energy Management System.
Real-time clock
Typical Applications
 Battery-backed Real-Time Clock with 25ppm accuracy (<2s per day)
 Industrial, Commercial and Utility Substation Metering
 Building, Factory and Process Automation System Integration
 Sub-metering and Cost Allocation  Supported by CET’s PecStar® iEMS and iEEM
 Energy Management and Power Quality Monitoring  Easy integration into other Automation, SCADA or BMS systems via
Features Summary Modbus RTU

Multifunction True RMS Measurements


Inputs and Outputs
 VLN, VLL per phase and Average Digital Inputs (Optional)
 Current per phase and Average with calculated Neutral Current  4 channels, volts free dry contact, 24VDC internally wetted
 kW, kvar, kVA, PF per phase and Total  1000Hz sampling for status monitoring with programmable debounce
 kWh, kvarh Import / Export / Net / Total and kVAh Total  Pulse counting with programmable weight for each channel for collecting
 Frequency WAGES (Water, Air, Gas, Electricity, Steam) information
 Device Operating Time (Running Hours)
 Optional DI Pulse Counters Digital Outputs (Optional)
 2 Form A mechanical relays for alarming and general purpose control
Enhanced Measurements
 5A @ 250VAC or 30VDC
 U and I THD, TOHD, TEHD and Individual Harmonics up to 31st
 Current TDD, TDD Odd, TDD Even, K-Factor and Crest Factor
 U and I Unbalance and Phase Angles
 Displacement PF
 Fundamental U, I and kW per phase
 Total Fundamental kW & Total Harmonic kW
 U and I Symmetrical Components
 kvarh Q1-Q4
 Demands, Predicted Demands and Peak Demands for kW/kvar/kVA Total
and per phase Current with Timestamp for This Month (or Since Last
Reset) and Last Month (or Before Last Reset)

Designed For Reliability Manufactured To Last


PMC-53M-A
Digital Multifunction Meter
Accuracy Standards of Compliance
Parameters Accuracy Resolution Safety Requirements
Voltage ±0.2% Reading + 0.05% F.S. 0.001V CE LVD 2014 / 35 / EU EN61010-1: 2010,
Current ±0.2% Reading + 0.05% F.S. 0.001A EN61010-2-030: 2010
kW, kvar, kVA ±0.5% Reading + 0.05% F.S. 0.001k Electrical safety in low voltage IEC 61557-12: 2008 (PMD)
kWh, kVAh IEC 62053-22 Class 0.5S 0.01kXh distribution systems up to
kvarh IEC 62053-23 Class 2 0.01kvarh 1000Vac and 1500 Vdc
P.F. ±0.5% 0.001 Insulation IEC 62052-11: 2003
Frequency ±0.02 Hz 0.01Hz AC Voltage: 2kV @ 1 minute
THD IEC 61000-4-7 Class B 0.001% Impulse voltage: 6kV, 1.2/50µs
K-Factor IEC 61000-4-7 Class B 0.1 Electromagnetic Compatibility
Phase angles ±1° 0.1° CE EMC Directive 2014 / 30 / EU (EN 61326: 2013)
Immunity Tests
Technical Specifications Electrostatic discharge EN 61000-4-2: 2009
Voltage Inputs (V1, V2, V3, VN) EN 61000-4-3: 2006+A1: 2008+A2:
Radiated fields
Standard Un 400VLN/690VLL 2010
Range 10V to 1.2Un Fast transients EN 61000‐4‐4: 2004+A1: 2010
Overload 1.2xUn continuous, 2xUn for 1s Surges EN 61000‐4‐5: 2006
Burden <0.02VA per phase Conducted disturbances EN 61000‐4‐6: 2009
Measurement Category CAT III up to 600VLL Magnetic Fields EN 61000‐4‐8: 2010
Frequency 45-65Hz V Dips, Interruptions & Variations EN 61000-4-11:2004
Current Inputs (I11, I12, I21, I22, I31, I32) Oscillatory waves EN 61000‐4‐12: 2006
Standard In 5A (5A/1A Auto-Scaling) Radio Disturbances CISPR 22:2006, Level B
Range 0.1% to 200% In Emission Tests
Starting Current 0.1% of In Limits and methods of
Overload 2xIn continuous, 20xIn for 1s measurement of electromagnetic
EN 55011: 2009 + A1: 2010
Measurement Category CAT III up to 600VLL disturbance characteristics of
(CISPR 11)
Burden <0.15VA per phase industrial, scientific and medical
Power Supply (L+, N-, GND) (ISM) radio-frequency equipment
Standard 95-250VAC/DC, ±10%, 47-440Hz Limits and methods of
Burden <2W measurement of radio EN 55022: 2010+AC: 2011
Overvoltage Category CAT III up to 300VLN disturbance characteristics of (CISPR 22)
Digital Inputs (DI1, DI2, DI3, DI4, DIC) information technology
Type Dry contact, 24VDC internally wetted equipment
Sampling 1000Hz Limits for harmonic current
Hysteresis 40ms minimum emissions for equipment with EN 61000-3-2: 2014
Digital Outputs (DO11, DO12, DO21, DO22) rated current ≤16 A
Type Form A Mechanical Relay Limitation of voltage fluctuations
Loading 5A @ 250VAC or 30VDC and flicker in low-voltage supply
EN 61000-3-3: 2013
Installation Torque systems for equipment with rated
Voltage / Current Inputs 1.3 N.m current ≤16 A
Power Supply, RS485, I/O 0.5 N.m Emission standard for industrial
EN 61000-6-4: 2007+A1: 2011
Environmental Conditions environments
Operating Temp. -25°C to 70°C Testing and measurement
Storage Temp. -40°C to 85°C techniques - Ring wave immunity EN 61000-4-12: 2006
Humidity 5% to 95% non-condensing test.
Atmospheric Pressure 70 kPa to 106 kPa Mechanical Tests
Mechanical Characteristics Spring Hammer Test IEC 62052-11: 2003
Panel Cutout 92x92 mm (3.62”x3.62”) Vibration Test IEC 62052-11: 2003
Unit Dimensions 96x96x88 mm Shock Test IEC 62052-11: 2003
IP Rating 65

Designed For Reliability Manufactured To Last


PMC-53M-A
Digital Multifunction Meter
Device View and Dimensions Ordering Information

Contact us

Designed For Reliability Manufactured To Last


Test Report
Date: 2016-11-07 Page 1 of 20
No.: DMA000192

Applicant: Ceiec Electric Technology Inc.


8/F, Westside, Building 201, Terra Industrial & Tradepark,
Che Gong Miao, Shenzhen, Guangdong, P.R.China 518040

Description of Sample(s): Submitted sample(s) said to be


Product: PMC-53A Series Intelligent
Multifunction Meter Ceiec
Brand Name: Electric Technology
Model Number: PMC-53M-A5925E-A1-B1

Date Sample(s) Received: 2016-09-23

Date Tested: 2016-09-27 to 2016-11-03

Investigation Requested: FCC Part 15 Subpart B

Conclusion(s): The submitted product COMPLIED with the requirements of


Federal Communications Commission [FCC] Rules and
Regulations Part 15. The tests were performed in accordance
with the standards described above and on Section 2.2 in this
Test Report.

Remark(s): For additional model(s) details, see page 3

LONG Yun Jian, Along


Authorized Signatory
ElectroMagnetic Compatibility Department
For and on behalf of
The Hong Kong Standards and Testing Centre Ltd.
The Hong Kong Standards and Testing Centre Limited
Head Office: 10 Dai Wang Street, Taipo Industrial Estate, Tai Po, N.T., Hong Kong
Unit B, 10/F, Block 1, Tai Ping Industrial Centre, No. 57 Ting Kok Road, Tai Po, N.T., Hong Kong
Tel: +852 2666 1888 Fax: +852 2664 4353 Email: hkstc@hkstc.org Website: www.stc-group.org
This report shall not be reproduced unless with prior written approval from The Hong Kong Standards and Testing Centre Limited.
For Conditions of Issuance of this test report, please refer to “Conditions of Issuance of Test Reports” section or Website.

You might also like