COMMENTS RESOLUTION SHEET (CRS)

CONTRACT NUMBER GC19101700

CONTRACT TITLE: EPIC FOR NEW SECONDARY SCHOOL IN DUKHAN TOWNSHIP

QATARENERGY EXTERNAL TRANSMITTAL REFERENCE, DATED: PID/GC19101700/EXT/TN/6086 Date: 23/07/2022

4088-9-MS-0365, Rev. 1, MATERIAL SUBMITTAL FOR IDEACUSTIC HIGH 16-


DOCUMENT NUMBER, REV & TITLE: Last Revision Status: 2
WALL CLADDING FOR AUDITORIUM

PREVIOUS ISSUED DOCUMENT NUMBER MADE VOID (IF ANY) NA

SR.
QATARENERGY COMMENTS CONTRACTOR'S RESPONSE REMARKS
NO
QatarEnergy
Section Comments
Engineer Ref id.
Contractor shall follow the material submittal index provided by
1 PIE5 Complied. Material submittal is revised.
QatarEnergy. Re-arrange the submittal properly.
Please see the attached project
Attach copy of project specifications. Complied. Project specification is attached.
specifications in page 23-25
Ideacustic high 16-wall cladding is directly imported from
spain on the recommendation of the acoustic consultant- Al
Attach list of similar projects (ongoing and completed)
Mana Associate. List of ongoing and completed project is
not available.
Ideacustic high 16-wall cladding is directly imported from
spain on the recommendation of the acoustic consultant- Al
Attach recent project previous approvals
Mana Associate. Previous approvals documents are not
available.
The material has no local supplier. It is imported directly
Attach a valid CR copy of local supplier
from Spain
MATERIAL SUBMITTAL

REF.:
CONTRACT NO. : GC19101700 4088-9-MS-0365 REV.: 2 Date: 16/10/2022

CONTRACT TITLE :
EPIC FOR NEW SECONDARY SCHOOL IN DUKHAN TOWNSHIP

MATERIAL SUBMITTAL FOR IDEACUSTIC HIGH 16 WALL


Proposed Material CLADDING FOR AUDITORIUM
:

Alternative : YES
4088-DESS-9-AC-0002
Ref. Drawing :
Architectural Specification 4088-DESS-9-A14-0001 &
Document/Spec. Reference : QCS 2014
Auditorium Acoustic Wall & Ceiling.
Location/Area of Use :
Manufacturer./Supplier Ideatec Advanced Acoustic Solutions
:
NO [not listed]
Vendor included in QP PVL : YES X
Specification Requirements
Remarks
Description Specified Proposed
Ideacustic High-16 Wall Architectural
Comply to
cladding Specification 4088-
Specification
DESS-9-A14-0001

Submitted By: Legend

Signature: C: Civil X M: Mechanical

Name: Girish G. Pillai I: Instrumentation E: Electrical

Designation: Project manager LS: Landscaping G: General


QP Comments:

Designation with Approved with


Approved Rejected Date
Reference Indicator Comments

Lead Project Engineer

Senior Project Engineer

Others
INDEX

1. CONTRACT DETAILS

2. COMPANY PROFILE

3. ISO CERTIFICATE

4. PROJECT SPECIFICATION

5. COMPLIANCE STATEMENT

6. TECHNICAL DATA SHEET

7. THIRD PARTY TEST REPORTS

8. COUNTRY OF ORIGIN

9. APPROVED SAMPLE

10. EMAIL CONFIRMATION

11. INSTALLATION MANUAL

12. AREA OF APPLICATION


1. CONTRACT DETAILS
EPIC FOR NEW SECONDARY SCHOOL AT
PROJECT TITLE : DUKHAN TOWNSHIP

CLIENT : QATARENERGY

CONTRACT NO : GC19701700

PROJECT NO : 4088

CONSULTANT /
DESIGNER : QATAR DESIGN CONSORTIUM

GALFAR AL MISNAD ENGINEERING &


MAIN CONTRACTOR : CONTRACTING W.L.L.
MATERIAL SUBMITTAL FOR
MATERIAL SUBMITTAL IDEACUSTICHIGH 16 WALL CLADDING
TITLE : FOR AUDITORIUM

DOCUMENT REF. NO : 4088-9-MS-0365

IDEATEC ADVANCED ACOUSTIC


MANUFACTURER : SOLUTIONS

IDEATEC ADVANCED ACOUSTIC


SUPPLIER : SOLUTIONS

AREA OF APPLICATION : AUDITORIUM ACOUSTIC WALL CLADDING


NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural Specification

Material Submittal for Ideacustic High 16-wall Cladding

COMPANY PROFILE
From Spain and with worldwide distribution, IDEATEC provides cutting-edge
products and solutions to the acoustic conditioning sector in all types of indoor
enclosures. Architects, engineers and installers will find in IDEATEC the best
solutions to complete with guarantees any acoustic project without renouncing to a
design that will not leave anyone indifferent.

With 30 years in the acoustics sector, IDEATEC designs, manufactures and markets
an extensive range of false ceilings, perforated wood cladding, and sound-absorbing
materials, as well as acoustic diffusers. In addition, its advanced FLEX solution,
available in all models, allows installation on curved surfaces, whether concave,
convex or undulating.

Innovative products composed of recycled polyester fiber and textiles multiply the
potential of IDEATEC acoustic solutions. Islands or clouds and suspended baffles,
panels, cylinders and semi-cylinders facilitate the acoustic conditioning of the
enclosure without the need for construction work.

In tune with our delivery times and the attention of our human team, we provide the
adequate service and support to watch over your interests and your reputation in
the market.

IDEATEC VISION

In Ideatec we firmly believe in bringing to each space the highest quality and
acoustic comfort, offering the best adapted and customized solutions.
NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural Specification

Material Submittal for Ideacustic High 16-wall Cladding

ISO CERTIFICATE
NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural Specification

Material Submittal for Ideacustic High 16 wall Cladding

PROJECT SPECIFICATION
Document Title: Doc No. 4088-DESS-9-A14-0001
ARCHITECTURAL
SPECIFICATIONS Rev.: 2
Date: 27.10.2021
Page: 75 of 107

10.16 ACOUSTIC MATERIALS

i. Contractor shall provide acoustic insulation to achieve rating suitable for school building materials
and application procedures which have been tested and rated by accredited testing laboratory.
Materials shall be certified by the manufacturer as complying with the rating indicated.

ii. Partitions designed to divide areas of a room and control the level of the noise or sound travelling
from one area to another a reduction of min 45dB. Acoustic barriers to be installed above the ceiling
levels also. Acoustic baffle are constructed using layers of high density gypsum boards on a
framework infilled with acoustic quilt to match the acoustic performance requirements.

iii. Acoustic vendor:


ECOPHON ITALY www.ecophon.it

SECTION 25 GLASS & GLAZING

11.0 GLASS & GLAZING


These Specifications shall be read in conjunction with the Section 25 of Qat ar Construction
Specifications. This section includes glazing for the following products and appli cations,
including those specified in other Sections where glazing requirements are specified by
reference to this
Section:
Windows
Doors
Glazed curtain walls
Glazed entrances
Balustrade Glazing

1. Definitions:

Glass Manufacturers: Firms that produce primary glass, fabricated glass, or both, as
defined in referenced glazing publications.
Glass Thicknesses: Indicated by thickness designations in millimeters according to ASTM C
1036.
Interspace: Space between lights of an insulating-glass unit.

2. Performance Requirements:

i. General: Installed glazing systems shall withstand normal thermal movement and
wind and impact loads (where applicable) without failure, including loss or glass
breakage attributable to the following: defective manufacture, fabrication, or
installation; failure of sealants or gaskets to remain watertight and airtight;
deterioration of glazing materials; or other defects in construction.

ii. Delegated Design: Design glass, including comprehensive engineering analysis by a


qualified professional engineer, using the following design criteria:

4088-DESS-9-A14-0001 REV. 2 Page 75 of 107


Document Title: Doc No. 4088-DESS-9-A14-0001
ARCHITECTURAL
SPECIFICATIONS Rev.: 2
Date: 27.10.2021
Page: 43 of 107

9.4 WARRANTY

All work shall be warranted by a FULL DOOR WARRANTY (from the date of installation) against
defect in materials and workmanship, including the following:
Any defect which may, in any way, impair or affect performance of the door for the purpose which
it is intended. Replacement under this warranty shall include hanging, installation of hardware, and
finishing.

9.5 DELIVERY, STORAGE AND HANDLING

a. No doors shall be delivered to the building until weatherproof storage space is available. Material
received at site shall be with original packing and labelled. It shall be kept intact under lock and key till
issued for use of site.
b. Store finished shop work in weather tight well ventilated structures or in space in existing buildings
designated by QP.
c. Protect shop work items from dampness both during and after delivery to site.
d. Do not install finished shop work in any room or space where concrete, masonry, or plaster work is
not completed and dry.
e. Factory finished doors shall be individually wrapped in polybags to protect the finish from damage by
contact with other doors.
f. Contractor shall use all means necessary to protect doors from damage prior to, during, and after
installation. All damaged doors shall be repaired or replaced by the contractor at no cost to the owner.

9.6 MATERIALS

9.6.1 Timber

All wooden finish shall be oak Timber. Oak shall be of quality as specified in BOQ and well-
seasoned. When a kind of timber is not specified, good quality oak wood shall be used. It shall have
uniform color, be free from defects such as cracks, dead knots, soft spongy spots and waves of
injurious open shapes. Grains shall be reasonably straight. The individual hard and sound knot shall
not be larger than 6 sq cm. The aggregate area of all knots shall not exceed 0.5% area of a piece. All
timber is sawn unless otherwise stated.

1. Moisture content of timber and shop work at the time of delivery to the site should be as
follows:

a) Moisture content to be 12 % minimum on 85 % of the work and a maximum of 15 % on the


remainder.

b) Exterior treated or untreated finished timber 100 mm or less in thickness, moisture


content to be 15 % minimum.

4088-DESS-9-A14-0001 REV. 2 Page 43 of 107


Document Title: Doc No. 4088-DESS-9-A14-0001
ARCHITECTURAL
SPECIFICATIONS Rev.: 2
Date: 27.10.2021
Page: 44 of 107

2. Members are to bear the grade mark, stamp, or other identifying marks indicating grades of materials,
and rules or standards under which produced.

3. Timber received at site shall be marked and stamped for approval prior to being used at site.

4. Size references, unless otherwise specified are nominal sizes, and actual sizes are to be within
manufacturing tolerances allowed by the standard under which the product is produced.

5. All timber shall be finished to required dimension and texture prior to being treated for chemical
preservation.

6. No making good of Timber with resin pockets shall be acceptable.

7. Discolored sapwood Timber shall not be accepted.

8. All softwood for permanent incorporation in the Works to be treated with preservative to provide
protection against damage from insect larvae, termites and fungal decay. Organic solvent type
preservatives are to contain a water repellent.

9. The preservative treatment is to be applied by pressure impregnation or the double vacuum


process. Dipping, deluging, spraying, brushing or other methods which only provide shallow
protection are not permitted.

10. The treatment is to be carried out under factory conditions at the source of supply of the timber
and the Contractor is to provide a Certificate of Impregnation when required by QP.

11. Treatment is to be carried out after all cutting and shaping has been completed. If subsequent
cutting of the timber is unavoidable all freshly exposed surfaces are to receive a liberal application
of the preservative recommended in the relevant treatment specification. Refer to BS 1282, BS
4072, BS 5268, BS 5589, BS 5666 and BS 5707.

9.6.2 Flush Doors

1. Doors shall be hollow core of specified thickness. They will have timber veneer finish matching finish
of existing Primary School doors . These shall be hot pressed and bonded with water resistant
formaldehyde synthetic resin of exterior quality as per BS specifications creating BWP ply faces. The
adhesive used for bonding cross band to core and face veneers to cross band shall conform to BS 1204
(Phenolic and Amino plastic). Ensure that the adhesives are unaffected by any timber treatment.

2. Tolerance on width and height shall be + 2 mm. Tolerance on thickness shall be + 1 mm. Thickness of
shutter shall be uniform throughout. Variation permissible shall be 0.8 mm.

4088-DESS-9-A14-0001 REV. 2 Page 44 of 107


NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural Specification

Material Submittal for Ideacustic High 16-wall Cladding

COMPLIANCE STATEMENT
NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural
Specification COMPLIANCE STATEMENT
Material Submittal for Ideacustic High 16 (wall Cladding)

S/N Sections Project Specification Response Remarks


1 Section:10.16 Ideacustic's High 16 offers acoustic
solution for the most demanding
space. Its acoustic performance
Contractor shall provide acoustic insulation to
within a wide range of frequencies
achieve rating suitable for school building
makes it a refrenece product for
materials and application procedures which have
the sector professionals. The
been tested and rated by accredited testing Comply
Acoustic Material acoustic value of Ideacustic's High
laboratory.
16 will be enhance by placing
Materials shall be certified by the manufacturer as
50mm rockwool at the back.
complying with the rating indicated.
Material submittal for rockwool
will be submitted separately.

2 Section:9.6
All wooden finish shall be oak Timber. Oak shall be
of quality as specified in BOQ and wellseasoned.
Ideacustic's High 16 has an oak
When a kind of timber is not specified, good
color but it is of cheery timber.
quality oak wood shall be used. It shall Comply
a Sample presented to QatarEnergy
haveuniform color, be free from defects such as
is approved.
cracks, dead knots, soft spongy spots and waves of
Material
injurious open shapes.

Members are to bear the grade mark, stamp, or


other identifying marks indicating grades of
b Noted Comply
materials, and rules or standards under which
produced.
NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural Specification

Material Submittal for Ideacustic High 16-wall Cladding

TECHNICAL DATA SHEET


Technical data sheet
HIGH 16
Ideacustic
DESCRIPTION

Modules of 2430x160 and 16 mm of


thickness, slots of 2, 3 or 4 mm,
separated 16 mm and Ø10 mm
perforations in the back.

FLEX SOLUTION: radius from


1m. For smaller radius of
curvature, contact us.
ACOUSTIC TEST
α
1
STUDIED DATA
0,9

0,8 Sizes: 2430x296 mm


0,7 Thickness: 16 mm
0,6
Slots: 3 mm
0,5
Diameter: 10 mm
0,4
Density: 750 kg/m3 (+/-6%)
0,3

0,2
Weight: 9.26 kg/m2
*Weight will depend on the finishing and machining.
0,1

0
100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 F
(Hz)
21 cm high of Plenum + 4cm of rockwool 5 cm high of Plenum + 4 cm of rockwool

Medium absorptive coefficient αm = 0.75 αm = 0.85


Test sample.

Average absorptive coefficient αw = 0.80 αw = 0.85

Noise reduction coefficient NRC = 0.75 NRC = 0.80

TECHNICAL FEATURES ADDITIONAL FEATURES


Sizes 2430x160x16 mm. Washable Product Clean with a damp cloth.
Do not use chemical agents.
Tolerances Width: ± 1.5 mm ;
Length: ± 1.5 mm. Impact Resistance Depends on the support
material.
Perforation 7.72%
Scratching Resistance Depends on the finishing
Finishing Melamine, wood veneer or
material.
lacquered (RAL, Pantone or NCS).
Dirt Proof High resistance to dirt.
Water-resistant Ask for properties.
May vary with the
Absorptive Core 0.25 mm black acoustic finishing material.
fleece attached to the back. Environmentally friendly.
Recyclable
Fire-rated UNE 13501: B-s2,d0
Earthquake-resistant Possible to install an
*Ask for other finishes or sizes. anti-seismic system.

INSTALLATION STANDARD SYSTEM PRODUCT REMARKS


Walls & Suspended ceilings The goods should be stored in the jobsite at least 24h prior
to the installation. The temperature must be between 18º
and 25º and the relative humidity between 40% and 60%.

Double groove Tongue and groove


noise
under
Pol. Ind. Santa Fe // Comuna di Carrara, 10 control
ideatec
advanced acoustic solutions
03660 Novelda (Alicante) España
T. +34 965 609 046 // +34 965 609 162 // F. +34 965 609 163
www.ideatec.es // info@ideatec.es v2 2020.08.04
NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural Specification

Material Submittal for Ideacustic High 16-wall Cladding

TEST REPORT
Nº/Nr: 4193T20
Página 1 de 15
Page 1 of 15

SOLICITANTE:
APPLICANT:

IDEATEC ADVANCED SOLUTIONS, S.L.U.

ENSAYOS - TESTS:

Ensayos de Reacción al Fuego para productos de Construcción


Reaction to fire tests for building products

• Normas de ensayo: − UNE-EN 13823:2012+A1:2016


Test Standards: − EN ISO 11925-2:2020

• Material: Paneles de MDF ranurados y con orificios traseros.


Material: MDF panels grooved and with rear holes.
 Fabricante:
Ideatec Advanced Solutions, S.L.U.
Manufacturer:
 Referencia:
“FAMILIA IDEACUSTIC”
Reference:
Informe de Ensayo nº 4193T20
Página 2 de 15
Test Report Nr 4193T20
Page 2 of 15
SOLICITANTE - APPLICANT

IDEATEC ADVANCED SOLUTIONS, S.L.U.


C/ Comuna di Carrara, 10
03660 – NOVELDA (Alicante)
ç

Fecha de solicitud: 24-sep-20 Aceptación de presupuesto: 28-sep-20


Test application date: 24th-Sep-20 Budget acceptance date: 28th-Sep-20

MUESTRAS DE ENSAYO - TEST SPECIMEN

Tipo de muestra: Paneles de MDF ranurados y con orificios traseros.


Type of specimen: MDF panels grooved and with rear holes.
Fabricante: Ideatec Advanced Solutions, S.L.U.
Manufacturer:
Referencia:
Reference: “FAMILIA IDEACUSTIC”

ENSAYOS REALIZADOS- TESTS PERFORMED


Norma de ensayo Fecha de ensayo
Test standard Test date
20-nov-20
UNE-EN 13823:2012+A1:2016
20th-Nov-20
30-nov-20
EN ISO 11925-2:2020
30th-Nov-20

Contenido del informe - Content of the report

1.- Muestras de ensayo ................................................................................................... Página 3


Test specimens ............................................................................................................. Page 3
2.- Ensayos realizados ................................................................................................... Página 4
Tests performed ............................................................................................................. Page 4
3.- Resultados ................................................................................................... Página 4
Results ............................................................................................................. Page 4
ANEXO 1: Documentación Técnica ........................................................................................ Página 10
ANNEX 1: Technical Documentation ................................................................................................ Page 10
ANEXO 2: Fotografías ........................................................................................ Página 15
ANNEX 2: Photographs ................................................................................................ Page 15

El presente informe se emite en cumplimiento con los requisitos del Sistema de Gestión de la Calidad de AFITI. Si desea formular
cualquier comentario o reclamación en referencia al mismo, contacte con nuestro Departamento de Calidad en el email
calidad@afiti.com.
Los resultados de este Informe de Ensayo hacen referencia única y exclusivamente a las muestras ensayadas, y no al producto en
general.
La información contenida en este Informe de Ensayo tiene carácter confidencial, por lo que el Laboratorio no facilitará a terceros
información relativa a este Informe de Ensayo, salvo que lo autorice el Solicitante.
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio.
The issuance of this report has been performed in compliance with the requirements of AFITI's Quality System. For any comment or claim in
relation with this work, you can address our Quality Department at calidad@afiti.com
The results of this report of test make sole and exclusive reference to the specimens tested and not to the product in general. DOCUMENTO FIRMADO
DIGITALMENTE
The information held in this Report of test is of a confidential nature, meaning the Laboratory shall not provide information in relation to this report
DIGITALLY SIGNED toDOCUMENT
third parties, except with the authorisation of the Applicant.
It is not allowed to reproduce partially this Test Report without laboratory's written approval.
Informe de Ensayo nº
4193T20
Test Report Nr

1.- MUESTRAS DE ENSAYO - TEST SPECIMENS


Recepción: 13-nov-20
Reception: 30th-Nov-20
Unidades: 5 muestras de 1500 mm x 1000 mm x 16 mm con ranurado de 31/m2
5 muestras de 1500 mm x 495 mm x 16 mm con ranurado de 31/m2
5 muestras de 1500 mm x 1000 mm x 16 mm con ranurado de 125/m2
5 muestras de 1500 mm x 495 mm x 16 mm con ranurado de 125/m2

Units: 5 specimens of 1500 mm x 1000 mm x 16 mm with grooved of 31/m2


5 specimens of 1500 mm x 495 mm x 16 mm with grooved of 31/m2
5 specimens of 1500 mm x 1000 mm x 16 mm with grooved of 125/m2
5 specimens of 1500 mm x 495 mm x 16 mm with grooved of 125/m2

− Las muestras se reciben en un palet de madera, envuelto en plástico.


Specimens are received in a pallet, wrapped in film.
− Las muestras han sido enviadas por el solicitante. Las muestras han sido preparadas para ensayo
por el laboratorio
− Specimens have been sent by applicant. Specimens have been prepared for tests by laboratory.

Documentación - Documentation

La memoria técnica incluida en el presente informe ha sido recepcionada en fecha 26-nov-20


Technical documentation included in this report has been received on 26th-Nov-20.

Descripción - Description

Paneles de MDF con un espesor de 16 mm, con una densidad de 750 kg/m3 de color marrón y
aspecto liso, con ranuras y orificios traseros recubiertos por su cara expuesta con una melanina de
color roble, con un espesor de 0,1 mm y un gramaje de 0,07 kg/m2 y aspecto liso. Por su cara no
expuesta el tablero de MDF está recubierto por un velo acústico con un espesor de 0,22 mm, un
gramaje de 0,061 kg/m2 y aspecto rugoso.
Los paneles se fijan al sustrato mediante unos rastreles de acero de sección 25 mm x 17 mm,
colocados en sentido horizontal cada 500 mm.

MDF panels with a thickness of 16 mm, with a density of 750 kg/m3 on brown colour and smooth aspect with
grooves and rear holes covered by exposed face with a melamine on oak colour, with a thickness of 0,1 mm
and a weight of 0,07kg/m2and smooth aspect. By the not exposed face the MDF panels are covered with
acoustic veil with a thickness of 0,22 mm and a weight of 0,061 kg/m2.
Panels are fixed to substrate by a steel strips with section 25 mm x 17 mm, fixed on horizontal position each
500 mm.

Las principales características descriptivas de la muestra han sido suministradas por el solicitante.
Dicha información se incluye en el Anexo 1 del presente Informe de Ensayo.
Specimen’s main characteristics have been sent by the applicant. This information is included in the Annex 1.

Información sobre el destino de aplicación de las muestras (material).


Information about the destination (destiny) of (material) application of the specimens.

Revestimiento de paredes y techos para el acondicionamiento acústico.


Walls and ceilings covering for acoustic conditioning.
DOCUMENTO FIRMADO
DIGITALMENTE
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 3 de 15
DIGITALLY SIGNED DOCUMENT

It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 3 of 15
Informe de Ensayo nº
4193T20
Test Report Nr

2.- ENSAYOS REALIZADOS - TESTS PERFORMED

Ensayos según normas:


Tests according to standards:

− UNE-EN 13823:2012+A1:2016, “Ensayos de reacción al fuego de productos de construcción-


Productos de construcción excluyendo revestimientos de suelos expuestos al ataque térmico
provocado por un único objeto ardiendo.”
UNE-EN 13823:2012 “Reaction to fire tests for products. Building products excluding floorings exposed to the
thermal attack by a single burning item”.
− EN ISO 11925-2:2020, “Ensayos de reacción al fuego de los materiales de construcción.
Inflamabilidad de los productos de construcción cuando se someten a la acción directa de la llama.
Parte 2: Ensayo con una fuente de llama única”.
EN ISO 11925-2:2020“Reaction to fire tests for building products. Ignitability of building products subjected to
direct impingement of flame. Part 2: Single flame source test”.

La Norma utilizada para la realización del acondicionamiento de las muestras ha sido la Norma
UNE-EN 13238:2011 “Ensayos de reacción al fuego para productos de construcción. Procedimiento
de acondicionamiento y reglas generales para la selección de sustratos”.
The Standard used for the conditioning has been UNE-EN 13238:2011 Standard “Reaction to fire tests for building
products. Conditioning procedures and general rules for selection of substrates”.

3.- RESULTADOS – RESULTS

3.1.- ENSAYO SEGÚN UNE-EN 13823:2012+A1:2016 – TEST ACCORDING TO UNE-EN 13823:2012+A1:2016

Condiciones de Ensayo - Test conditions

Acondicionamiento de las muestras Temperatura (ºC)


23±2
Specimens conditioning Temperature
Humedad (%)
50±5
Humidity
Entre 96 y
Tiempo de acondicionamiento (h) 336
Conditioning time Between 96
and 336

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 4 de 15
It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 4 of 15
Informe de Ensayo nº
4193T20
Test Report Nr

Disposición de las muestras durante el ensayo – Mounting of specimens during the test
Tipo de material Paneles de MDF ranurados y con orificios traseros.
Kind of material MDF panels grooved and with rear holes.
Condiciones de exposición Superficie expuesta
Conditions Surface exposed
Sustrato utilizado Placa de yeso laminado normalizado
Substrate used Standard gypsum plasterboard
Tipo de fijación Atornillado con rastreles de acero de 25 mm x 17 mm.
Kind of fixing Screwed with steel strips of 25 mm x 17 mm
Modo de fijación Sin juntas. Con hueco de separación de 17 mm.
Way of fixing Without joints. With air gap of 17 mm.
Cara expuesta Cara ranurada
Exposed face Grooved face

Expresión de resultados - Test results

A continuación se muestran los valores numéricos y los gráficos obtenidos en los ensayos
realizados.
Hereafter, numerical values and graphs obtained during the test are shown.

Valores numéricos – Numerical values


Muestra nº- Specimen Nr.
T4193F T4193G T4193H
THR600s (MJ)
[Cantidad total de calor desprendido de la muestra] 4,2 5,8 6,9
[Total heat release]
FIGRA 0,2 (W/s)
[Valor máximo del cociente de la velocidad de
41,25 50,59 67,45
desprendimiento de calor por la muestra ]
[Maximum of the quotient of heat release rate from the specimen]
TSP600s (m2)
[Producción total de humo de la muestra] 84,8 113,1 152,3
[Total smoke production]
SMOGRA (m2/s2)
[Tasa de producción de humo] 8,23 15,42 19,71
[Smoke growth rate]
LFS
[Propagación lateral de la llama a lo largo del ala de la
no no no
muestra]
[Lateral flame spread on the long specimen wing]
Caida de gotas inflamadas
no no no
Falling of flaming drops
Tiempo de persistencia de gotas inflamadas (s)
Time of flaming drops persistence (s) ----- ----- ----

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 5 de 15
It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 5 of 15
Informe de Ensayo nº
4193T20
Test Report Nr

Gráficos – Graphs

30 500
450
25 400
THRta (MJ)

TSPta (m²)
20 350
300
15 250
200
10
150
5 100
50
0 0
0 300 600 900 1200 1500 1800 0 300 600 900 1200 1500 1800
Tiempo (s) Tiempo (s)
T4193F T4193G T4193H T4193F T4193G T4193H

35 0,70
0,60

SPRav (m²/s)
30
HRRav (kW)

25 0,50

20 0,40
0,30
15
0,20
10
0,10
5
0,00
0
0 300 600 900 1200 1500 1800
0 300 600 900 1200 1500Tiempo
1800
(s) Tiempo (s)
T4193F T4193G T4193H
T4193F T4193G T4193H

80 25
SMOGRA (m²/s²)

70
FIGRA (W/s)

20
60
50 15
40
30 10
20
5
10
0 0
0 300 600 900 1200 1500 1800 0 300 600 900 1200 1500 1800
Tiempo (s) Tiempo (s)
T4193F T4193G T4193H T4193F T4193G T4193H

HRR ≡ Desprendimiento de calor (valor medio, valor Light Signal ≡ Señal de receptor de
total) luz.
SPR ≡ Producción de humo (valor medio, valor total)

Valores medios obtenidos – Average values


Valores medios
Average
THR600s (MJ) [Cantidad total de calor desprendido de la muestra]
5,6
[Total heat release]
FIGRA 0,2(W/s) [Valor máximo del cociente de la velocidad de
desprendimiento de calor por la muestra]
53,10
[Maximum of the quotient of heat release rate from the
specimen]
TSP600s (m2) [Producción total de humo de la muestra]
116,7
[Total smoke production]
2 2
SMOGRA (m /s ) [Tasa de producción de humo]
14,45
[Smoke growth rate]
LFS [Propagación lateral de la llama a lo largo del ala de la
muestra]  Sí  No
[Lateral flame spread on the long specimen wing]
Caida de gotas inflamadas
 Sí  No
Falling of flaming drops
Tiempo de persistencia de gotas inflamadas (s)
---
Time of flaming drops persistence (s)
DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 6 de 15
It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 6 of 15
Informe de Ensayo nº
4193T20
Test Report Nr

Observaciones durante el ensayo – Observations during the test

Durante la realización del ensayo no aparecen llamaradas súbitas, no se aprecian humos


procedentes de la muestra que no entren en el colector, ni distorsión ni derrumbamiento de la
misma. No se produce caída de gotas inflamadas.
There are no sudden flames during the test, no smoke entering into the hook, neither falling of the material.
There is no falling of flaming drops.

3.2.- ENSAYO SEGÚN EN ISO 11925-2:2020 – EN ISO 11925-2:2020 TEST

Condiciones de Ensayo - Test conditions

Acondicionamiento de las muestras Temperatura (ºC)


23±2
Specimen conditioning Temperature
Humedad (%)
50±5
Humidity
Tiempo de acondicionamiento (h)
336
Conditioning time

Disposición de las muestras durante el ensayo – Mounting of specimens during the test
Tipo de material Paneles de MDF ranurados y con orificios traseros.
Kind of material MDF panels grooved and with rear holes.

Condiciones de exposición Superficie expuesta


Conditions Surface exposed

Sustrato utilizado Placa de yeso laminado normalizado


Substrate used Standard gypsum plasterboard

Tipo de fijación Atornillado con rastreles de acero de 25 mm x 17 mm.


Kind of fixing Screwed with steel strips of 25 mm x 17 mm

Modo de fijación Sin juntas. Con hueco de separación de 17 mm.


Way of fixing Without joints. With air gap of 17 mm.

Cara expuesta Cara ranurada


Exposed face Grooved face

Tiempo de aplicación de llama (s)


30
Time of flame application (s)

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 7 de 15
It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 7 of 15
Informe de Ensayo nº
4193T20
Test Report Nr

Expresión de resultados. Superficie expuesta


Test results. Surface exposure

Muestra nº - Specimen Nr

T4193I-1

T4193I-2

T4193I-3

T4193I-4

T4193I-5

T4193I-6
Inicio de ignición (sí/no) no no no no no no
Ignition (yes/no) non non non non non non

Tiempo inicio de ignición (s)


--- --- --- --- --- ---
Start time of ignition (s)
Propagación vertical de la llama superior a
no no no no no no
150 mm (sí/no)
non non non non non non
Vertical spread of flame upper 150 mm (yes/no)
Ignición del papel de filtro (sí/no) no no no no no no
Ignition of filter paper (yes/no) non non non non non non

Observaciones durante el ensayo – Observations during the test

Se observan humos blancos, grises, densos y abundantes. No se produce persistencia de la


combustión ni puntos de ignición tras el ensayo. Las muestras se carbonizan en la zona de
aplicación de la llama.
White, grey dense and abundant smokes are observed. There is not combustion persistence or ignition
points after test. The specimens are charred in the zone of application of flame.

“Los resultados del ensayo corresponden al comportamiento de muestras de ensayo de un producto,


bajo las condiciones propias del ensayo. No pretende constituir el único criterio de valoración del
riesgo potencial de incendio que puede conllevar el uso del producto.”
“The test results related to the behaviour of the test specimens of a product under the particular conditions of
the test; they are not intended to be the sole criterion for assessing the potential fire hazard of the product in
use”.

Toledo, 02 de diciembre de 2020


Toledo, 2nd of december of 2020

Fdo.: David Sáez García


Director Técnico del Laboratorio
de Reacción al Fuego
Technical Director of Fire Reaction Laboratory

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 8 de 15
It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 8 of 15
Informe de Ensayo nº
4193T20
Test Report Nr

Anexos
Annexes
DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 9 de 15
It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 9 of 15
Anexo 1. Documentación Técnica Informe de Ensayo nº
4193T20-3
Annex 1. Technical Documentation Test Report Nr

DOCUMENTO FIRMADO
DIGITALMENTE
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 10 de 15
DIGITALLY SIGNED DOCUMENT

It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 10 of 15
Anexo 1. Documentación Técnica Informe de Ensayo nº
4193T20-3
Annex 1. Technical Documentation Test Report Nr

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 11 de 15
It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 11 of 15
Anexo 1. Documentación Técnica Informe de Ensayo nº
4193T20-3
Annex 1. Technical Documentation Test Report Nr

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 12 de 15
It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 12 of 15
Anexo 1. Documentación Técnica Informe de Ensayo nº
4193T20-3
Annex 1. Technical Documentation Test Report Nr

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 13 de 15
It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 13 of 15
Anexo 1. Documentación Técnica Informe de Ensayo nº
4193T20-3
Annex 1. Technical Documentation Test Report Nr

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 14 de 15
It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 14 of 15
Anexo 2. Fotografías Informe de Ensayo nº
4193T20
Annex 2. Photographs Test Report Nr

T4193F T4193F

Fotografía nº 1 Fotografía nº 2
Vista completa del ala larga Detalle del borde lateral
de la muestra T4193F de la muestra T4193F
Complete view of the long wing of the specimen T4193F Detail of the lateral vertical edge of the specimen T4193F

T4193G T4193H

Fotografía nº 3 Fotografía nº 4
Detalle del borde lateral Detalle del borde lateral
de la muestra T4193G de la muestra T4193H
Detail of the lateral vertical edge of the specimen T4193G Detail of the lateral vertical edge of the specimen T4193H

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Ensayo no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 15 de 15
It is not allowed to reproduce partially this Test Report without laboratory's written approval. Page 15 of 15
Nº/Nr: 4193T20-2
Página 1 de 7
Page 1 of 7

SOLICITANTE:
APPLICANT:

IDEATEC ADVANCED SOLUTIONS, S.L.U.

CLASIFICACIÓN DE LA REACCIÓN AL FUEGO SEGÚN NORMA


UNE-EN 13501-1:2019
REACTION TO FIRE CLASSIFICATION ACCORDING TO STANDARD
UNE-EN 13501-1:2019.

• Material: Paneles de MDF ranurados y con orificios traseros.


Material : MDF panels grooved and with rear holes.

 Fabricante: Ideatec Advanced Solutions, S.L.U.


Manufacturer :
Gama de producto:
Product family
Según información incluida en página 5 de 7 (Tabla 1)
According to information included on page 5 of 7 (table 1)
Informe de Clasificación nº 4193T20-2
Página 2 de 7
Classification Report Nr 4193T20-2
Page 2 of 7

CLASIFICACIÓN DE LA REACCIÓN AL FUEGO SEGÚN


NORMA UNE-EN 13501-1:2019
REACTION TO FIRE CLASSIFICATION ACCO RDING TO UNE-EN 13501-1:2019 STANDARD

Solicitante: IDEATEC ADVANCED SOLUTIONS, S.L.U.


Applicant : C/ Comuna di Carrara, 10
03660 – NOVELDA (Alicante)

Laboratorio emisor: AFITI-LICOF


Issuer Laboratory: Organismo notificado nº:
1168
Notified body Nr

Producto: Paneles de MDF ranurados y con orificios traseros.


Product : MDF panels grooved and with rear holes.
Fabricante
Ideatec Advanced Solutions, S.L.U.
Manufacturer :
Referencia: Según información incluida en página 5 de 7 (Tabla 1)
Reference : Information included on page 5 of 7 (table 1)

Informe de Clasificación nº:


4193T20-2
Classification Report Nr:
Fecha de emisión: 2-dic-20
Date of issue : 2nd-Dec-20

Contenido del inform e - Content of the report

1.- Objeto del informe ........................................................................................ Página 3


Aim of the report ........................................................................................ Page 3
2.- Detalles del producto objeto de clasificación .......................................................... Página 3
Details of classified product ........................................................................................ Page 3
3.- Informes y resultados de ensayo en los .................................................................. Página 3
que se basa la clasificación.
Reports and test results in support of this classification ................................................... Page 3
4.- Clasificación y campo de aplicación ......................................................................... Página 6
Classification and field of application ............................................................................. Page 6
5.- Limitaciones ........................................................................................ Página 7
Limitations ........................................................................................ Page 7

La información contenida en este Informe de Clasificación tiene carácter confidencial, por lo que el Laboratorio no facilitará a
terceros información relativa a este Informe, salvo que lo autorice el Solicitante.
El presente Informe de Clasificación no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio
The information held in this Classification Report is a confidential nature, meaning the Laboratory shall not provide information DOCUMENTO
in relation to FIRMADO
this
DIGITALMENTE
report to third parties, except with the authorisation of the Applicant. DIGITALLY SIGNED DOCUMENT

It is not allowed to reproduce partially this Classification Report without the Laboratory’s written approval.
Informe de Clasificación nº
4193T20-2
Classification Report Nr

1.- OBJETO DEL INFORME – AIM OF THE REPORT


Este Informe de Clasificación define la clasificación de la Reacción al Fuego asignada a la gama de
paneles de MDF ranurados y con orificios traseros de acuerdo con los procedimientos establecidos
en la norma UNE-EN 13501-1:2019 “Clasificación en función del comportamiento frente al Fuego de
productos de construcción y elementos para edificación. Parte 1: Clasificación a partir de datos obtenidos
en ensayos de Reacción al Fuego”.
This Classification report defines the Reaction to Fire classification of the product of MDF panels grooved and with
rear holes by the applicant on the basis of the procedures established in UNE-EN 13501-1:2019 “Fire classification
of construction products and building elements-Part 1: Classification using data from reaction to fire tests”.

2.- DETALLES DEL PRODUCTO OBJETO DE CLASIFICACIÓN


DETAILS OF CLASSIFIED PRODUCT
2.1.- GENERAL – GENERAL
La gama de productos definida por el solicitante según información incluida en página 5 de 7
(Tabla 1) se define como paneles de MDF ranurados y con orificios traseros según la
especificación técnica correspondiente.
The product family defined by applicant according information included in page 5 of 7 (Table 1) is defined as
MDF panels grooved and with rear holes according to the relevant technical specification.

2.2.- DESCRIPCIÓN – DESCRIPTION


La gama de productos está completamente descrita en el informe de ensayo y en el informe que
incluye el campo de aplicación extendido de resultados de ensayo [Informe EXAP] en los que se
basa esta clasificación. Dichos informes se identifican en el capítulo 3 del presente informe.
The product family is fully described on the test report and the extended applications report [EXAP report]
classification is based on. These reports are indicated on chapter 3 of this report.

3.- INFORMES Y RESULTADOS DE ENSAYO EN LOS QUE SE BASA LA CLASIFICACIÓN.


REPORTS AND TEST RESULTS IN SUPPORT OF THIS CLASSIFICATION.
3.1.- ENSAYOS – TEST

Informes de ensayo – Test reports


Norma de
Laboratorio emisor Solicitante Informes ensayo
Condición final de uso
Issuer laboratory Applicant Reports Test standard
End use application
AFITI-LICOF IDEATEC ADVANCED Nº/ Nr: 4193T20 Revestimiento de UNE-EN
Pol. Ind. Sta. Mª de SOLUTIONS, S.L.U. F. emisión: 13823:2012
paredes y techos para
Benquerencia C/ Comuna di 4-dic-20 +A1:2016
el acondicionamiento
C/ Río Estenilla, s/n Carrara, 10 Date of issue: acústico.
45007-TOLEDO 03660 – NOVELDA 4th-Dec-20 Walls and ceilings
(Alicante) F ensayo:20-nov-20 covering for acoustic
Organismo Test date: conditioning.
notificado nº: th
20 -Nov-20
Notified body Nr: F ensayo: 30-nov-20 EN ISO 11925-
1168 Test date: 30th-Nov-20 2:2020

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe de Clasificación no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 3 de 7
It is not allowed to reproduce partially this Classification Report without the Laboratory’s written approval. Page 3 of 7
Informe de Clasificación nº
4193T20-2
Classification Report Nr

Resultados de ensayo – Test results

Informe de ensayo nº
4193T20
Test report Nr

Resultados
Results
Media de
Parámetros que
Número parámetro
se tienen que
Método de ensayo Parámetro de continuo (m)
cumplir
Test method Parameters ensayos Continuous
Compliance with
Nr. test parameter mean
parameters
(m)
No aplicable
FIGRA0,2MJ (W/s) 53,10 Non applicable
No aplicable No aplicable
FIGRA0,4MJ (W/s)
Non applicable Non applicable
No aplicable  Sí  No
LSF < borde
Non applicable  Yes  No
UNE-EN No aplicable
THR600s (MJ) 5,6
13823:2012+A1:2016 1 Non applicable
S.B.I. No aplicable
SMOGRA (m2/s2) 14,45
Non applicable
No aplicable
TSP600 s (m2) 116,7
Non applicable
Gotas/ partículas en
No aplicable  Sí  No
llamas
Non applicable  Yes  No
Drops / Particles flamed

Resultados
Results
Media de
Parámetros que
Número parámetro
se tienen que
Método de ensayo Parámetro de continuo (m)
cumplir
Test method Parameters ensayos Continuous
Compliance with
Nr. test parameter mean
parameters
(m)
EN ISO 11925-2:2020
Exposición = 30 s No aplicable  Sí  No
Fs ≤ 150 mm
Esposure =30 s Non applicable  Yes  No
1
Inflamación del
Gotas/partículas en llamas No aplicable  Sí  No
papel de filtro
Drops / Particles flamed Non applicable  Yes  No
Ignition of filter paper

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT

El presente Informe de Clasificación no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 4 de 7
It is not allowed to reproduce partially this Classification Report without the Laboratory’s written approval. Page 4 of 7
Informe de Clasificación nº
4193T20-2
Classification Report Nr

3.2.- CAMPO DE APLICACIÓN EXTENDIDO DE RESULTADOS


EXTEND APPLICATION FIELD

Informes – Reports

Laboratorio emisor Solicitante Informes Norma


Issue laboratory Applicant Reports Standard
AFITI-LICOF IDEATEC ADVANCED Nº: EXAP-4193T20 - UNE-EN 15725:2011
Pol. Ind. Sta. Mª de SOLUTIONS, S.L.U.
Benquerencia C/ Comuna di Carrara, 10 F. emisión: 2-dic-20
C/ Río Estenilla, s/n 03660 – NOVELDA Date of issue: 2nd-Dec-20
45007 – TOLEDO (Alicante)

Organismo notificado nº
Notified body Nr:
1168

Campo de aplicación extendido de los resultados de ensayo


Extended application field of test results

A continuación se muestra el rango permitido de variabilidad para los distintos parámetros del
producto/condiciones finales de uso. El resto de parámetros deben mantenerse conforme a lo
descrito en los informes de ensayo de referencia.
Hereafter it is shown the range of variation allowed for the different parameters of the product/end use
conditions. Rest of parameters shall be kept as described on the referenced test reports.

-Tabla 1-
-Table 1-

Gama de productos
Product family
Tipo de producto Paneles de MDF ranurados y con orificios traseros.
Type of product MDF panels grooved and with rear holes.
Referencia comercial
Commercial trade name “ FAMILIA IDEACUSTIC”

Ranurado por m2 Resultados válidos para ranurados por m2 [31- 125]


Grooved by m2 Results valid for grooved by m2 [31 – 125]

Sustratos de placa de yeso laminado con densidad igual o superior a


525,5 kg/m3.
Sustrato
Substrate
Sustratos con una euroclase A1 ó A2-s1,d0.
Substrates of gypsumplasterboard with density equal or higher to 525,5 kg/m3.
Substrates with a euroclass A1 or A2-s1,d0.

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT

El presente Informe de Clasificación no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 5 de 7
It is not allowed to reproduce partially this Classification Report without the Laboratory’s written approval. Page 5 of 7
Informe de Clasificación nº
4193T20-2
Classification Report Nr

4.- CLASIFICACIÓN Y CAMPO DE APLICACIÓN


CLASSIFICATION AND FIELD OF APPLICATION

4.1.- NORMA DE CLASIFICACIÓN – CLASSIFICATION STANDARD

La clasificación de la reacción al fuego se ha realizado de acuerdo con lo establecido en la


norma UNE-EN 13501-1:2019.
Reaction to Fire classification according to UNE-EN 13501-1:2019 standard.

4.2.- CLASIFICACIÓN – CLASSIFICATION

La gama de productos de paneles de MDF ranurados y con orificios traseros (ver Tabla 1)
presenta la siguiente clasificación:
Product family of MDF panels grooved and with rear holes (see table 1) reaches the following
classification:

Clasificación de la Reacción al Fuego – Reaction to fire classification

Comportamiento al
Producción de humo Gotas inflamadas
Fuego
Smoke production Flaming droplets
Fire behaviour
B  s 2 , d 0

B – s2 , d0
4.3.- CAMPO DE APLICACIÓN – FIELD OF APPLICATION

Según lo establecido en el informe técnico EXAP nº EXAP-4193T20, la gama de productos (ver


tabla 1), tiene el siguiente campo de aplicación.
According to Technical Report EXAP nr. 4193T20, the product family (see Table 1), has the following field
of application.

La clasificación obtenida sigue siendo válida para las siguientes variaciones en las características
de la muestra, sin que la realización de estas modificaciones suponga la ejecución de nuevos
ensayos.
Classification obtained is valid for the following simple characteristic variations, without further testing
needed.
Característica/Propiedad Variación permitida
Characteristic/Property Range allowed
− Tipo de producto Paneles de MDF ranurados y con orificios traseros.
Kind of product MDF panels grooved and with rear holes.

− Ranurado por m2 Resultados válidos para ranurados por m2 [31- 125]


Grooved by m2 Results valid for grooved by m2 [31 – 125]
Sustratos de placa de yeso laminado con densidad igual o
superior a 525,5 kg/m3.
− Sustrato Sustratos con una euroclase A1 ó A2-s1,d0.
Substrate Substrates of gypsumplasterboard with density equal or higher to
525,5 kg/m3.
Substrates with a euroclass A1 or A2-s1,d0 DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT

El presente Informe de Clasificación no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 6 de 7
It is not allowed to reproduce partially this Classification Report without the Laboratory’s written approval. Page 6 of 7
Informe de Clasificación nº
4193T20-2
Classification Report Nr

5.- LIMITACIONES - LIMITATIONS

Este informe no representa ninguna aprobación de tipo ni certificación del producto.


This document does not represent type approval or certification of the product.

Toledo, 02 de diciembre de 2020


Toledo, 2nd of december of 2020

Fdo.: David Sáez García


Director Técnico del Laboratorio
de Reacción al Fuego
Technical Director of Fire Reaction Laboratory

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT

El presente Informe de Clasificación no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio. Página 7 de 7
It is not allowed to reproduce partially this Classification Report without the Laboratory’s written approval. Page 7 of 7
730-750 kg/m3 800-830 kg/m3 730-770 kg/m3
D-s2,d0 B-s2,d0 PND EN-13501-1:2018

CLASE E-2 CLASE E-1 UNE-EN 13986:2006+A1:2015

30 N/mm2 22 N/mm2 32 N/mm2 UNE-EN 13986:2006+A1:2015

0,65 N/mm2 0,60 N/mm2 0,80 N/mm2 UNE-EN 13986:2006+A1:2015

0,15 0,15 0,0807 UNE-EN 13986:2006+A1:2015

2500 N/mm2 2500 N/mm2 2800 N/mm2 UNE-EN 13986:2006+A1:2015

T32: αw=0,25(LM) T16: αw=0,30(LM) R32: αw=0,40(LM)


R16: αw =0,55 G5Mi: αw =0,40(M) G4R16: αw=0,50(M)
Mi: αw = 0,50(M) *Microacustic: αw=0,35(LM) **Micro0.5: αw =0,60(L)
EN ISO 11654:1998
Cosmos: αw = 0,4 Cu: αw=0,65 *ID 8: αw=0,80
ID 11: αw=0,85(L) ID 16: αw=0,85 ID 32: αw=0,70
ID 64: αw=0,40(LM)

Thermal insulation PND UNE-EN 13986:2006+A1:2015


Spécification techniques harmonisées
710-740 kg/m3 780-800 kg/m3 700-730 kg/m3
D-s2,d0 B-s2,d0 PND EN-13501-1:2018

CLASE E-2 CLASE E-1 UNE-EN 13986:2006+A1:2015

30 N/mm2 20 N/mm2 30 N/mm2 UNE-EN 13986:2006+A1:2015

0,65 N/mm2 0,60 N/mm2 0,80 N/mm2 UNE-EN 13986:2006+A1:2015

0,15 0,15 0,0807 UNE-EN 13986:2006+A1:2015

2500 N/mm2 2500 N/mm2 2800 N/mm2 UNE-EN 13986:2006+A1:2015

T32: αw=0,25(LM) T16: αw=0,30(LM) R32: αw=0,40(LM)


R16: αw =0,55 G5Mi: αw =0,40(M) G4R16: αw=0,50(M)
Mi: αw = 0,50(M) *Microacustic: αw=0,35(LM) **Micro0.5: αw =0,60(L)
EN ISO 11654:1998
Cosmos: αw = 0,4 Cu: αw=0,65 *ID 8: αw=0,80
ID 11: αw=0,85(L) ID 16: αw=0,85 ID 32: αw=0,70
ID 64: αw=0,40(LM)

Thermal insulation PND UNE-EN 13986:2006+A1:2015


Nº EXAP-4193T20
Página 1 de 8
Page 1 of 8

SOLICITANTE:
APPLICANT:

IDEATEC ADVANCED SOLUTIONS, S.L.U.

INFORME TÉCNICO EXAP [Extended Applications]:


TECHNICAL REPORT EXAP [Extended Applications]:

Determinación del campo de aplicación extendido de resultados de ensayo.


Determination of field of extended application of test results.

• Norma: UNE-CEN/TS 15117:2009


Standard:

• Material: Paneles de MDF ranurados y con orificios traseros.


Material : MDF panels grooved and with rear holes.

 Fabricante: Ideatec Advanced Solutions, S.L.U.


Manufacturer:
Informe Técnico nº EXAP 4193T20
Página 2 de 8
Technical Report Nr EXAP 4193T20
Page 2 of 8

SOLICI TANTE – APPLICANT

IDEATEC ADVANCED SOLUTIONS, S.L.U.


C/ Comuna di Carrara, 10
03660 – NOVELDA (Alicante)
ç

Fecha de solicitud: 24-sep-20 Aceptación de presupuesto: 28-sep-20


Test application date: 24th-Sep-20 Budget acceptance date: 28th-Sep-20

PRODUCTO – PRODUCT

Tipo de muestra: Paneles de MDF ranurados y con orificios traseros.


Type of specimen: MDF panels grooved and with rear holes.

Fabricante: Ideatec Advanced Solutions, S.L.U.


Manufacturer:

Este Informe Técnico EXAP se emite en base a los resultados de ensayo obtenidos según la norma de ensayo:

 UNE-EN 13823:2012+A1:2016 “Ensayos de reacción al fuego de productos de construcción- Productos de


construcción excluyendo revestimientos de suelos expuestos al ataque térmico provocado por un único objeto
ardiendo.”
 EN ISO 11925-2:2020 “Ensayos de Reacción al Fuego de los materiales de construcción. Inflamabilidad de
los productos de construcción cuando se someten a la acción directa de la llama. Parte 2: Ensayo con una
fuente de llama única”.
La determinación del campo de aplicación extendido de resultados de ensayo ha sido realizada conforme a las
reglas y sistemática establecida en las normas:
− UNE-CEN/TS 15117:2009 “Directrices para el establecimiento de las aplicaciones directas”
y de la extensión de las aplicaciones”
− UNE-EN 15725:2011 “Informes de extensión de la aplicación del comportamiento frente al fuego de productos
de construcción y elementos de edificación”.

The present Technical Report EXAP is issued based on the test results obtained according to test standard:

 UNE-EN 13823:2012+A1 :2016 standard “Reaction to fire tests for products. Building products excluding floorings exposed to
the thermal attack by a single burning item”.
 EN ISO 11925-2:2020 standard “Reaction to fire tests for building products. Ignitability of building products
subjected to direct impingement of flame. Part 2: Single flame source test”.
The field of application has been determined according to the rules and procedures defined on the standards:
− UNE-CEN/TS 15117:2009 “Guidance on direct and extended application”
− UNE-EN 15725:2011 “Extended application reports on the fire performance of construction products and building elements”

La información contenida en este Informe Técnico tiene carácter confidencial, por lo que el Laboratorio no facilitará a terceros
información relativa a este Informe Técnico, salvo que lo autorice el Solicitante.
Los resultados de este informe se refieren al comportamiento del producto/familia de productos bajo las condiciones
particulares del ensayo, y no pretende ser el único criterio para determinar el potencial de riesgo de incendio en el uso del
producto/familia de productos.
El presente Informe Técnico no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio.
The information held in this Technical Report is of a confidential nature, meaning the Laboratory shall not provide information in relation to this
report to third parties, except with the authorisation of the applicant. DOCUMENTO FIRMADO
DIGITALMENTE
The test results related to the behaviour of the test specimens of a product/product family under the particular conditions of DIGITALLY
the test; they are not
SIGNED DOCUMENT
intended to be the sole criterion for assessing the potential fire hazard of the product/product family in use.
It is not allowed to reproduce partially this Technical Report without the Laboratory’s written approval.
Informe Técnico nº EXAP 4193T20
Technical Report Nr EXAP 4193T20

Contenido del inform e Técnico - Content of the report

1.- Información del producto.............................................................................................. Página 5

Product information ............................................................................................................. Page 5

2.- Informes y resultados de ensayo en los que se basa el ................................................ Página 6


informe sobre el campo de aplicación extendido

Report and tests results in support of the .................................................................................... Page 6


the extended field of application report.

3.- Campo de aplicación extendido. Procedimiento........................................................... Página 7

Extended field of application. Procedure ..................................................................................... Page 7

4.- Campo de aplicación extendido de los resultados de .................................................. Página 8


Ensayo

Extended field of application of the test results. .......................................................................... Page 8

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe Técnico no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio Página 3 de 8
It is not allowed to reproduce partially this Technical Report without the Laboratory’s written approval Page 3 of 8
Informe Técnico nº EXAP 4193T20
Technical Report Nr EXAP 4193T20

1.- INFORMACIÓN DEL PRODUCTO – PRODUCT INFORMATION

Tipo de muestra: Paneles de MDF ranurados y con orificios traseros.


Type of specimen: MDF panels grooved and with rear holes.

Uso previsto: Revestimiento de paredes y techos para el acondicionamiento acústico.


Foreseen Use: Walls and ceilings covering for acoustic conditioning.

− Aplicación final de uso: Atornillado con rastreles metálicos de sección 25 mm x 17 mm.


Superficie y borde expuesto
End use application: Screwed with steel strips with section 25 mm x 17 mm. Surface and edge
exposure.

Descripción – Description

aspecto liso, con ranuras y orificios traseros recubiertos por su cara expuesta con una melanina de
color roble, con un espesor de 0,1 mm y un gramaje de 0,07 kg/m2 y aspecto liso. Por su cara no
expuesta el tablero de MDF está recubierto por un velo acústico con un espesor de 0,22 mm, un
gramaje de 0,061 kg/m2 y aspecto rugoso.
Los paneles se fijan al sustrato mediante unos rastreles de acero de sección 25 mm x 17 mm,
colocados en sentido horizontal cada 500 mm.

MDF panels with a thickness of 16 mm, with a density of 750 kg/m3 on brown colour and smooth aspect with
grooves and rear holes covered by exposed face with a melamine on oak colour, with a thickness of 0,1 mm
and a weight of 0,07kg/m2and smooth aspect. By the not exposed face the MDF panels are covered with
acoustic veil with a thickness of 0,22 mm and a weight of 0,061 kg/m2.
Panels are fixed to substrate by a steel strips with section 25 mm x 17 mm, fixed on horizontal position each
500 mm.

Los valores de las características de referencia del producto ensayado son:


The values of the characteristics of reference of the tested product are:

Producto
Product
1 2
Ranurado por m2
31 125
Grooved by m2

Las principales características descriptivas de las muestras han sido suministradas por el solicitante.
The main descriptive characteristics of the specimens have been given by the applicant.

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe Técnico no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio Página 4 de 8
It is not allowed to reproduce partially this Technical Report without the Laboratory’s written approval Page 4 of 8
Informe Técnico nº EXAP 4193T20
Technical Report Nr EXAP 4193T20

2.- INFORMES Y RESULTADOS DE ENSAYOS EN LOS QUE SE BASA EL INFORME SOBRE EL CAMPO DE
APLICACIÓN EXTENDIDO.
REPORTS AND RESULTS TEST IN SUPPORT OF EXTENDED FIELD OF APPLICATION REPORT.

Informes - Reports

Referencia informe – Report Reference

4193T20

Solicitante
IDEATEC ADVANCED SOLUTIONS, S.L.U.
Applicant
Laboratorio
AFITI-LICOF
Laboratory
Fecha emisión 2-dic-20
Issuing date 2nd-Dec-20
Fechas de ensayo 20-nov-20 30-nov-20
Tests dates 20th-Nov-20 30th-Nov-20
Método de ensayo
UNE-EN 13823:2012+A1:2016 EN ISO 11925-2:2020
Test method
Referencias muestra
Specimen references “FAMILIA IDEACUSTIC”

Resultados de los ensayos – Test results

A continuación se indican los valores de los parámetros(1) que han servido de base para la
determinación del campo de aplicación:
Hereafter it is shown the values of the test parameters (1) used of base to determine the field of application:

Ensayo según UNE-EN 13823:2012+A1:2016. Informe: 4193T20


Test according to UNE-EN 13823:2012+A1:2016 Report nr: 4193T20
Ranurado por m2
Grooved by m2 Tsp(m2)

31 61,7
Muestras indicativas
Indicative tests
125 84,8

(1) Se consideran parámetros de ensayo que tienen especial relevancia en la determinación del
comportamiento al fuego del producto, en función de la clasificación prevista de dicha gama
de productos.
(1) They are considered to be parameters of test that have special relevancy in the determination of the
behaviour to the fire of the product, depending on the classification foreseen of the above mentioned range
of products.
De acuerdo con los resultados obtenidos, el ranurado por m2 más desfavorable es 125.
According to the obtained results, the grooved by m2 with the worst behaviour is 125.

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe Técnico no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio Página 5 de 8
It is not allowed to reproduce partially this Technical Report without the Laboratory’s written approval Page 5 of 8
Informe Técnico nº EXAP 4193T20
Technical Report Nr EXAP 4193T20

3.- CAMPO DE APLICACIÓN EXTENDIDO. PROCEDIMIENTO.


EXTENDED FIELD OF APPLICATION. PROCEDURE.

Para la determinación del campo de aplicación de los resultados de ensayo se ha utilizado la


siguiente metodología:

1º.- Establecer la influencia de la variación de los parámetros del producto y de la condición final
de uso según lo especificado en:
 UNE-CEN/TS 15117:2009 Anexo A
The following method has been used to determine the field of application of the test results:

1º. Establishing the influence of the variation of the parameters of the product and of the final condition of use
according to the specified in:
 UNE-CEN/TS 15117:2009 Annex A
2º. Realización de ensayos adicionales sobre varios parámetros del producto/condiciones de uso
según lo establecido en el apartado 6.2.2. de la norma UNE-CEN/TS 15117.

2º Adicional test son various product parameters /final use condition according to stablished in chapter 6.2.2 of
UNE-CEN/TS 15117

Influencia de la variación de los parámetros del producto en los resultados


Influence of the product parameters variation in the results

Ensayo según (1) Reglas de variación de resultados Norma


Test about(1) Rules for variation of results Standard
Se realiza una muestra indicativa del menor
ranurado por m2 y una muestra indicativa
del mayor ranuarado por m2. Se finalizan los
Ranurado por UNE-EN
ensayos con el ranurado por m2 más UNE-CEN/TS
m2 13823:2012+A1:
desfavorable. 15117:2009
Grooved by m2 2016
It is tested a single test of less grooved by m2,
and a highest grooved by m2.. With the worst
performing grooved by m2, it is finished the test

(1) Únicamente se hace referencia a la norma de ensayo cuyos resultados presentan variación
como consecuencia de la variación del parámetro considerado.
It only refers to the test Standard whose results present variation as a consequence of the variation of the
considered parameter.

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe Técnico no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio Página 6 de 8
It is not allowed to reproduce partially this Technical Report without the Laboratory’s written approval Page 6 of 8
Informe Técnico nº EXAP 4193T20
Technical Report Nr EXAP 4193T20

4.- CAMPO DE APLICACIÓN EXTENDIDO DE LOS RESULTADOS DE ENSAYO


EXTENDED FIELD OF APPLICATION OF THE TEST RESULTS

Gama de producto – Product family

A continuación se muestra el rango permitido de variabilidad para los distintos parámetros del
producto/condiciones finales de uso. El resto de parámetros deben mantenerse conforme a lo
descrito en el informe de ensayo de referencia.
Hereafter it is shown the range of variation allowed for the different parameters of the product/end use
conditions. Rest of parameters shall be kept as described on the referenced test reports.

Gama de productos
Product family
Tipo de producto Paneles de MDF ranurados y con orificios traseros.
Type of product MDF panels grooved and with rear holes.
Referencia comercial
Commercial trade name “ FAMILIA IDEACUSTIC”

Ranurado por m2 Resultados válidos para ranurados por m2 [31- 125]


Grooved by m2 Results valid for grooved by m2 [31 – 125]
Sustratos de placa de yeso laminado con densidad igual o superior a
525,5 kg/m3.
Sustrato
Substrate
Sustratos con una euroclase A1 ó A2-s1,d0.
Substrates of gypsumplasterboard with density equal or higher to 525,5 kg/m3.
Substrates with a euroclass A1 or A2-s1,d0.

Parámetros de comportamiento al fuego de la gama de producto


Fire behaviour parameters for the product family

Método de ensayo según UNE-EN 13823:2012+A1:2016 Resultados


Test according to UNE-EN 13823:2012+A1:2016 Results
THR600s (MJ) [Cantidad total de calor desprendido de la muestra]
5,6
[Total heat release]

FIGRA 0,2(W/s) [Valor máximo del cociente de la velocidad de


desprendimiento de calor] 53,10
[Maximum of the quotient of heat release rate from the specimen]

TSP600s (m2) [Producción total de humo]


116,7
[Total smoke production]
SMOGRA (m2/s2) [Tasa de producción de humo]
14,45
[Smoke growth rate]
LFS [Propagación lateral de la llama a lo largo del ala]  Sí  No
[Lateral flame spread on the long specimen wing]  Yes  No

Caída de gotas inflamadas  Sí  No


Falling of flaming drops  Yes  No
Tiempo de persistencia de gotas inflamadas (s)
Time of flaming drops persistence (s) -------
DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe Técnico no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio Página 7 de 8
It is not allowed to reproduce partially this Technical Report without the Laboratory’s written approval Page 7 of 8
Informe Técnico nº EXAP 4193T20
Technical Report Nr EXAP 4193T20

Método de ensayo Parámetro Resultados


Test method Parameter Results
Cumple
Fulfill
EN ISO 11925-2:2020, 1 2 3 4 5 6

Exposición = 30 s sí sí sí sí sí sí sí
Fs ≤ 150 mm
Exposure time = 30 s yes yes yes yes yes yes yes

Inflamación del
Gotas/partículas en llamas sí
papel de filtro no no no no no no
Drops / Particles flamed yes
Ignicion of filter paper

Toledo, 02 de diciembre de 2020


Toledo, 2nd of december of 2020

Fdo.: David Sáez García


Director Técnico del Laboratorio
de Reacción al Fuego
Technical Director of Fire Reaction Laboratory

DOCUMENTO FIRMADO
DIGITALMENTE
DIGITALLY SIGNED DOCUMENT
El presente Informe Técnico no debe reproducirse parcialmente sin la aprobación por escrito del Laboratorio Página 8 de 8
It is not allowed to reproduce partially this Technical Report without the Laboratory’s written approval Page 8 of 8
NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural Specification

Material Submittal for Ideacustic High 16-wall Cladding

COUNTRY OF ORIGIN
NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural Specification

Material Submittal for Ideacustic High 16 wall Cladding

APPROVED SAMPLE
NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural Specification

Material Submittal for Ideacustic High 16 wall Cladding

EMAIL CONFIRMATION
Chris Enyinnaya Uwanuakwa

From: Girish G. Pillai


Sent: Saturday, July 2, 2022 9:31 AM
To: Chris Enyinnaya Uwanuakwa
Subject: FW: GROUND FLOOR AUDITORIUM PLAN

From: Luis Andres Camargo Bojaca <luis@amaqatar.com>


Sent: Monday, June 6, 2022 2:19 PM
To: Girish G. Pillai <girishg@galfarqatar.com.qa>; Alexander Rafael Garcia Luque <Alexander@amaqatar.com>
Cc: Sreejith S. <Sreejith@galfarqatar.com.qa>; Sheeju David <Sheeju@galfarqatar.com.qa>
Subject: RE: GROUND FLOOR AUDITORIUM PLAN

Dear Girish

Please check the following to reply to your comments and queries regarding the placement of perforated panels for acoustic control purposes.

 We set two options for acoustic control materials that give the best results according to the installation conditions. Please use this particular material, or the ones that
provide similar acoustic absorption coefficients, as well as the installation setup must be accordingly to the presented (air gaps, and insulation material, must be
followed as mentioned)

1
AA1: Reference Image Acoustic Absorption coefficients

Perforated PANEL:

MappyMicro Absorption
Frequency (Hz)
Perforated MDF panel with microperforated Coefficient(α)
veneer cover Material 63 125 250 500 1000 2000 4000 4000
 A mixed panel with:
Mappy Micro 0.65 0.85 0.8 0.75 0.65 0.65 0.55 0.5
-Perforated pattern of 8mm round
perforations spaced at 16mm centers
-Microperforated pattern of 0.5mm round
perforations spaced at 2mm centers
 Open area 39.25%
INSTALLATION SETUP
 Thickness: 16mm
 Back Air cavity: Minimum 200 - 300 mm
with 50mm glass wool 10 – 22kg/m3)
 Installed over Rigid backing.

2
AA2: Reference Image Acoustic Absorption coefficients

Perforated PANEL: Absorption


Frequency (Hz)
Coefficient(α)
Ideacoustic High 16
Slotted panels with groove front face and Material 63 125 250 500 1000 2000 4000 4000
perforated rear. Diacaustic High 16 0.33 0.33 0.6 0.89 0.90 0.75 0.64 0.6
 A composite panel with:
-Rear holes of 10mm round perforations
spaced at 16mm centers
- Frontal Longitudinal ribbing, 16mm
grooves, 3mm slotting
 Open area 11,57%
INSTALLATION SETUP
 Thickness: 16mm
 Back Air cavity: Minimum 200 - 300 mm
with 50mm glass wool 10 – 22kg/m3)
 Installed over Rigid backing.

 The perforated material coverage area must include a minimum of:


- The whole back wall area: around 195 m2
- The back side area of the parapet: Around 104 m2 (52 m2 on each side). The air gap thickness and a rigid backing its necessary, so the thickness of the element
only allows one side to be perforated
- The side walls area: Around 40 m2 (20m2 on each side). Duplicate the current proposed area ( 10.34 m2) by doubling the height of each perforated portion in
each side wall panel.
- Total (minimum) area coverage: Around 339 m2

 The entry-exit ramp proposed area is not functional for absorption purposes due to its location. It is more effective to increase the area coverage on the Side walls.
 We kindly remind you that this area coverage only works if the perforated panels are installed in the proposed setup and comply with the acoustic absorption
coefficients. Other materials with different perforation patterns, installation setups, or coverage areas will change the results and must be reviewed.

If you have any further comments or questions, please let me know.

Best Regards,

3
Luis Andres Camargo
Senior Acoustic Engineer
MOB: (+974) 55092402

Acoustic Design, Consultancy and Measurements services.


ISO 9001 Certification No. BQSR12155.
AL MANA & ASSOCIATES PO Box 31260, Doha - Qatar TEL: (+974) 44684482 FAX: (+974) 44689393 WEBSITE: www.amaqatar.com

Please consider the environment before printing this email.


The information in this e-mail, together with any attachments, is intended only for the person or entity to which it is addressed and may contain confidential and/or privileged material. You
should only read,disclose, re-transmit, copy, distribute or act in reliance upon the information if it is addressed to you. If you are not the intended recipient of this e-mail communication,
please notify us immediately by e-mail to admin@amaqatar.com and then destroy any electronic or paper copy of this message. Any views expressed in this e-mail communication are those
of the individual sender, unless otherwise specifically stated. Al Mana & Associates does not represent, warrant or guarantee that the integrity of this communication has been maintained
or that the communication is free of errors, virus or interference.

Copyright Al Mana & Associates. All rights reserved.

suits

From: Girish G. Pillai <girishg@galfarqatar.com.qa>


Sent: Saturday, June 4, 2022 12:10 PM
To: Alexander Rafael Garcia Luque <Alexander@amaqatar.com>
Cc: Luis Andres Camargo Bojaca <luis@amaqatar.com>; Sreejith S. <Sreejith@galfarqatar.com.qa>; Sheeju David <Sheeju@galfarqatar.com.qa>
Subject: FW: GROUND FLOOR AUDITORIUM PLAN

Dear Alex

Further to our discussion regarding option no -3, please find attached ground floor layout drawings where in we have entry /Exit ramp on both ends which
has an are coverage of 104 m2.

So to summarize-

Area covered under the initial report – 600 m2

4
NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural Specification

Material Submittal for Ideacustic High 16-wall Cladding

INSTALLATION MANUAL
NEW SECONDARY SCHOOL DUKHAN TOWNSHIP
Project Specification :4088-DESS-9-A14-0001 Architectural Specification

Material Submittal for Ideacustic High 16 wall Cladding

AREA OF APPLICATION
℄℄

℄℄

GALFAR AL MISNAD ENGG. & CONTG. W.L.L, -2


19 7 7 0 17

h
P.O.Box # 22170 QATAR DESIGN CONSORTIUM W.L.L
ARCHITECTS, ENGINEERS, PROJECT MANAGERS & CONSULTANTS Yea
Doha - Qatar r s