You are on page 1of 12

Construction and Building Materials 18 (2004) 269–280

Moisture ingress in rammed earth: Part 1—the effect of soil particle-size


distribution on the rate of capillary suction
Matthew Hall*, Youcef Djerbib
Centre for the Built Environment, Sheffield Hallam University, Unit 9 Science Park, Howard Street, Sheffield S1 1WB, UK

Received 19 November 2003; received in revised form 24 November 2003; accepted 24 November 2003

Abstract

The novel initial rate of suction (IRS) ‘wick’ test has been presented, and is suitable for determining the rate of capillary
moisture ingress in unstabilised rammed earth that slakes on contact with water. Experimental testing was performed using the
‘wick’ test to investigate the effect of soil particle-size distribution on moisture ingress in rammed earth. Rammed earth generally
absorbs much less water due to capillary suction, and at a slower rate, than conventional masonry building materials such as
bricks and concrete. Moisture ingress in rammed earth, due to capillary suction, increases linearly per unit inflow surface area
against the square root of elapsed time yt . The particle-size distribution of the soil is critical in determining the rate at which
Ž .
moisture may ingress. In a suitable soil, the ratio between the total specific surface area (SSA) of the aggregate fraction and the
mass of the binder fraction appears to be positively linked with the rate of capillary suction in rammed earth. Experimental data
have been included.
䊚 2003 Elsevier Ltd. All rights reserved.

Keywords: Rammed earth; Moisture ingress; Capillary suction

1. Introduction ness that often plagued the solid walls of older buildings.
As rammed earth walls are monolithic, the capillary
Rammed earth can be defined as ‘«an ancient earth movement of moisture within them is a particular
building technique that involves dynamically compact- problem, especially since there are no chemically dosed
ing moist sub-soil between removable shuttering to layers of mortar to suppress it w2x. A variety of chemical
create an in-situ monolithic compressed earth wall that additives and admixtures that are available commercially
is both strong and durable’ w1x. Figs. 1 and 2 show a could be used to alleviate the problem but current data
rammed earth dwelling constructed by RAMTEC Pty relating to their effectiveness is not forthcoming and so
Ltd in Western Australia, illustrating the current levels poses serious problems for earth building contractors.
of sophistication in design and application of this natu- These problems may be exacerbated depending upon
ral, sustainable material. Some current public percep- the composition of the soil mix used to form the rammed
tions of rammed earth as being a material with low earth walls; the first logical step is to understand the
climatic durability are misguided but not entirely material before investigating how best to treat it.
unfounded. Rammed earth construction is popular and
performs well in warm, dry climates. However, research We have tried many things before regarding admixtures for damp
ingress-all too expensive or unreliable«Does adding clay make it
is essential in determining the application of rammed better or worse? Does removing clay (e.g. by washing) make it
earth in temperate damp climates if it is to succeed in better or worse? Does lessening clay% (e.g. by adding washed
counties such as the UK. Cavity wall masonry construc- sand) make it better or worse? These are real questions w2x.
tion, which is by far the most common form in Britain,
has largely eliminated the problems of penetrating damp- 2. Moisture ingress by capillary suction
*Corresponding author. Tel.: q44-0-114-225-3200; fax: q44-0-
114-225-3206. Excessive moisture content in building elements is
E-mail address: m.hall@shu.ac.uk (M. Hall). referred to as damp w3x. Dampness can enter into and

0950-0618/04/$ - see front matter 䊚 2003 Elsevier Ltd. All rights reserved.
doi:10.1016/j.conbuildmat.2003.11.002
270 M. Hall, Y. Djerbib / Construction and Building Materials 18 (2004) 269–280

Fig. 2. Inside a modern rammed earth home (Courtesy RAMTEC Pty


Fig. 1. Modern rammed earth house in Western Australia (Courtesy Ltd 䉷2001).
RAMTEC Pty Ltd 䉷2001).
determined, where mw denotes the mass of water and
move within the fabric of porous construction materials ms the mass of the dry solid:
by a variety of different processes. Porous materials are
often permeable by air and moisture because they mw
contain a network of open channels. According to the ws . (1)
ms
Building Research Establishment w4x, there are two
classifications for these channels dependent upon their In practice, the value of w is determined gravimetrically
diameter. A channel with a nominal diameter of 5 mm as the difference between the total weights of the sample
or above is classed as a pore whereas a channel with a when it is oven dried to a constant weight at 105 8C,
nominal diameter of less than this value is classed as a and when it is wet.
capillary or a micropore. It should be noted that pores The conventional description of the reference moisture
and capillaries are not cylindrical but in fact often content of a porous material allows us to clearly distin-
exhibit a high level of tortuosity w5x. They may also be guish between the hygroscopic moisture content and the
interlinked; the extent of which largely determines the capillary moisture content, as can be seen from Fig. 3.
permeability of a porous material. The theoretical point of total saturation (Wmax) is rarely
Hall w6x observed that if, hypothetically, the solid achieved, and neither is a completely water-free state
material of a porous building material is assumed to be (0). In the nominal dry state a degree of hygroscopic
inert (i.e. no mass transfer occurs), and that specific water remains, defined by the point Wh, whereas above
boundary effects and dissolved atmospheric gases in the the nominal point of saturation (Wsat) techniques such
water are ignored a considerable simplification ensues. as vacuum saturation are required in order to achieve
The role of the solid porous material is then reduced to higher levels of moisture content.
acting as a pore network that ‘partially constrains the Movement of moisture in walls is controlled by the
boundary surfaces of the water phases’ to a particular masonry and by discontinuities (e.g. fracturing) within
geometry. The system then contains a single compo- the material w5x. In terms of the mechanisms of moisture
nent—water—that may exist in any combination of movement we are dealing with ‘«a single fundamental
solid, liquid or gaseous form. The specific moisture process, the movement of water through a permeable
content w of this idealised porous solid can thus be material whose water content is non-uniform and gen-

Fig. 3. Reference moisture contents, adapted from de Freitas et al. (1996).


M. Hall, Y. Djerbib / Construction and Building Materials 18 (2004) 269–280 271

erally less than saturation’ w6x. To illustrate the process because surface tension of the capillary wall material is
of moisture ingress by capillary suction, Hall w6x used a ‘monotonously decreasing function of temperature’.
the classic example of a dry brick that has been placed Conversely, water held within a capillary of uniform
in a shallow tray containing clean water (i.e. the initial temperature but with a gradient in diameter will flow
rate of suction test). From the moment this is done towards the narrower diameter. Consequently, if two
water is absorbed into the brick by capillary action, and capillaries communicate with one another moisture
then attempts to distribute itself throughout the pore transfer will occur between the material with larger pore
network of the brick itself. The imbibed water partially diameters to that with the smaller pore diameters until
displaces the air that previously occupied the pores, the gradient of unequal surface tension has been resolved
whilst at the surfaces that are not actually in contact through equilibrium w12x.
with water evaporation has begun to occur. At this point,
equilibrium can be achieved between evaporative loss 3. Initial rate of suction (IRS) test
and water absorption.
The British Standard BS 3921 w13x test for determin-
However, evaporation entails cooling at the boundary
ing capillary suction of water into masonry materials is
surfaces, which results in a heat flow process being
known as the initial rate of suction (IRS) test. The test
generated inside the brick. The resultant heat gradient
method is essentially a gravimetric determination of
modifies the rate of flow of moisture inside the brick.
sorbed water in a partially immersed porous building
Soluble salts are often dissolved and redeposited at the
material (due to capillary suction) over time, the value
surface where evaporation is occurring, and the resultant
for which is expressed in kilograms per meter square
crystalline deposits referred to as efflorescence. As a
minute. Hall w14x previously observed the cumulative
material approaches saturation, the capillary suction
absorbed mass of water (mw) per unit area of the inflow
approaches zero w7x. Capillary suction in porous mate-
surface, increases linearly against the square root of
rials, therefore, occurs by the progressive displacement
elapsed time Žyt.. The sample is to be kept ‘dry’ prior
of water so that pockets of air entrapped in the pore
to testing. The current IRS test is, however, of little use
and capillary system cannot stop it w8x. The only
for materials that slake (e.g. earth materials) because
exception to this occurs where the capillary pressure is
the determination of imbibed water mass requires the
simply counteracted by the pressure of entrapped air in
mass of the sample to be kept constant. Furthermore,
a duct that is sealed and has no outlet.
the test requires the wetted sample surface to be wiped
Vos and Tammes w9x performed various experiments
with a damp cloth to remove excess water. This presents
on the capillary movement of water and concluded that
a large degree of operator error and a potential drying
water moving through a porous material by capillarity
effect depending upon the type, and moisture content,
could travel twice as far in a horizontal direction than
of the cloth.
in a vertical direction, owing to the effects of gravity.
The testing procedure can be enhanced by maintaining
Kieslinger w10x noted that a good correlation between
a constant water temperature of 20 8C ("18) in order
field data and the equation for determining the height
to ensure constant viscosity. Hall and Kam-Ming Tse
of capillary rise had been observed: w15x recommend that the weighing operation be com-
2s pleted as quickly as possible, ideally within 30 s. Minke
hs (2) w16x has discussed the German standard version of the
Rd IRS test, DIN 52 617, within the context of earth
building materials. The main differences involve encas-
where h: water height achieved (cm); s: (constant)
ing the sample cube sides in fibre-reinforced polyester
0.074 gycm3; d: density of water (approx. 1 gycm3); R:
resin, gluing filter paper to the test face and then placing
radius of capillary (cm).
it on a submerged polyurethane foam base. However,
Capillary rise is therefore dependent on the diameter
this level of sample intervention is perhaps excessive
of the tube and the liquid within the system. Mamillan
w11x gives the following example where, in theory, a 1 and deviates significantly from the ‘natural’ conditions
of the BS 3921 IRS test. The impermeable resin coating
mm pore could enable water to rise by 15 mm; a 0.1-
constricts the natural expansion of the sample and
mm pore enables a capillary rise of 150 mm; and a 0.01
restricts the displacement of air from the pore network
mm pore enables a rise of 1500 mm. The durability of
caused by the imbibed water. Furthermore, equilibrium
many types of natural building stones has been related
between evaporative loss at the sample faces and water
to pore size w5x, such that those with high microporosity
absorption cannot occur.
are often less durable than those with a lower content
of micropores. 4. The IRS ‘wick’ test
According to Vos and Tammes w12x, if a temperature
gradient exists along a capillary then water flow will The IRS ‘wick’ test is a novel adaptation of the
occur in the direction of lower temperature. This is current BS 3921 IRS test apparatus (see Fig. 4) devised
272 M. Hall, Y. Djerbib / Construction and Building Materials 18 (2004) 269–280

Fig. 4. BS 3921 IRS test apparatus with IRS ‘wick’ test peripherals.

by the author (Hall). A 30-mm high Oasis娃 ‘wick’, IRS ‘wick’ test data obtained during testing. Note that
which is 80 mm in diameter, acts as the point of contact the mass of sorbed water in the ‘wick’ test samples is
for the sample and represents free water being sorbed around half that of the BS 3921 IRS test samples due
from another saturated porous medium that offers neg- to the inflow-surface area also being approximately half
ligible capillary resistance. However, according to the that of the latter. A good correlation is indicated by a
studies on interface phenomena performed by De Freitas, similar IRS value, calculated as the mass of sorbed
Abrantes and Crausse w17x, theoretically there should be water per unit of surface area over time. It was observed
a small degree of hydric resistance that conditions the that for very porous samples a greater disparity occurred
maximum flow of moisture transmitted from the wick between values obtained using the IRS test and the IRS
to the sample face being tested. The contact area is ‘wick’ test. However, rammed earth is particularly dense
constant and there are no edge effects or meniscus errors with a low porosity and so the IRS ‘wick’ test is
on inflow-surface area calculations, as was previously considered a suitable means with which to test this
the case in the BS 3921 IRS test. Materials that slake material.
in contact with water are stable throughout the test and The variation that occurs between results for individ-
negligible mass loss occurs as the inflow surface is ual test specimens is significant and is an inherent
retained by the self-weight of the sample acting on the problem with both the BS 3921 IRS test and the IRS
solid surface of the wick. The wick itself can simply be ‘wick’ test. The average level of variation between
taken out, washed and reused to maintain accuracy and rammed earth samples was observed to be between
repeatability. approximately 20 and 40%. These parameters are well
Testing was performed on C30 concrete 100=100- within the typical variations observed in our laboratory
mm cubes and 3 types of brick; London Brick ‘Fletton’ for fired clay bricks after several thousand cycles of BS
(high porosity), London Brick ‘Dapple Light’ (medium 3921 IRS testing. This emphasises the myopic nature of
porosity) and Engineering Brick (low porosity). Six testing masonry building materials at this scale when,
representative samples of each material type were select- for example, the behaviour of a construction element
ed. The bricks were cut on a diamond bit saw to give a (e.g. a wall) cannot be defined by the performance of
100=100-mm inflow-surface area the same as the cube an individual brick. However, testing a randomly select-
samples. Firstly, the IRS test was performed in accor- ed batch of samples can be used to give a good
dance with BS 3921 w13x for a period of 5 min for each indication of a porous masonry materials performance
sample with gravimetric moisture determinations taken in terms of moisture ingress due to capillary suction
at 1-min intervals. Secondly, the same samples were through a set of average values.
dried and repeat-tested, as described above, but instead
using the IRS ‘wick’ test apparatus. Hall w14x previously 5. Rammed earth testing
observed that no changes occurred in the pore structure
of fired clay bricks during repeat-tests of this nature. The authors have recently proposed recommendations
The IRS ‘wick’ test values were in close agreement for the production of rammed earth cube samples using
with those obtained using the BS 3921 IRS test. Fig. 5 synthetically blended soils whose particle-size distribu-
illustrates the comparison between BS 3921 IRS and tion can accurately be specified and controlled w1x. The
M. Hall, Y. Djerbib / Construction and Building Materials 18 (2004) 269–280 273

Fig. 5. Comparison between BS 3921 IRS test and IRS ‘wick’ test results.

same ten soil recipes, specified previously, have been was found highly repeatable and consistent in terms of
used for the experimental work detailed in this article, density, dimensional stability and compressive strength.
as can be seen from the particle-size distribution chart The rammed earth samples were tested in accordance
illustrated in Fig. 6. Further details on the physical and with the previously defined IRS ‘wick’ test, which is a
mechanical properties of the rammed earth cube samples peripheral to the BS 3921 IRS test. Six samples from
have been previously illustrated, by the authors, in depth each of the ten soil types identified above were used as
w1x. This method of rammed earth sample production the test specimens. Each sample was tested for a period

Fig. 6. BS 1377 Particle-size distribution chart with rammed earth soil data.
274 M. Hall, Y. Djerbib / Construction and Building Materials 18 (2004) 269–280

Table 1
The average amount of sorbed water during a 5-min IRS ‘wick’ test

Masonry type Dry massavg (g) Average wm (g) Average wm (%)


London brick – Fletton 851.0 10.95 1.29
London brick – Dapple light 923.2 7.12 0.77
Engineering brick 1316.6 12.47 0.95
C30 concrete 2165.8 6.72 0.31
Rammed earth – 532 2136.9 3.17 0.15
Rammed earth – 622 2132.0 3.37 0.16
Rammed earth – 712 2068.8 8.45 0.41
Rammed earth – 802 2030.6 15.15 0.74
Rammed earth – 433 2180.5 3.42 0.16
Rammed earth – 523 2101.3 4.22 0.20
Rammed earth – 613 2120.0 4.15 0.20
Rammed earth – 703 2058.4 5.95 0.29
Rammed earth – 424 2067.3 5.92 0.28
Rammed earth – 514 2089.0 3.12 0.15

of 5-min and the mass of sorbed water (mw) recorded within the cube and, more importantly, at the inflow test
at 1-min intervals. After testing the samples were then face.
allowed to dry before the IRS ‘wick’ test regime The surface finish of the inflow test face appears to
(described above) was repeated using the same samples be critical in determining the level of moisture ingress
and the same inflow-surfaces. This time, however, only in rammed earth. It is controlled by the particle-size
three from each of the six samples (in each set) were distribution of the soil and by the random location of
selected for the re-testing. The samples selected from a different sized particles towards the facade.¸ Larger
particular soil type all had a similar IRS value, thereby particles in this region appear to cause micro-cracking
eliminating the upper and lower values from the repeat- and internal fissures that allow large volumes of water
test results. Weight determinations were made at 1-min to be imbibed. In addition, moisture ‘tracking’ may
intervals but the total test duration was extended to give occur where the migrating moisture follows the contour
values for 1, 2, 3, 4, 5, 10, 20, 30, 40, 50 and 60-min of larger (e.g. gravel) particles, within the matrix, due
elapsed time intervals. to their surface tension. This factor may be magnified
on small-scale laboratory tests such as this where, for
6. Results and discussion example, a piece of 14 mm gravel represents over 1y
8th the width of an 80 mm inflow surface test area. In
Rammed earth generally has a very low initial rate of addition, moisture ingress in rammed earth facades
¸ was
suction compared to conventional masonry materials observed to be much greater at the compaction planes
such as concrete and fired clay bricks, and absorbs much (i.e. the zones between layers of compacted soil) where
smaller amounts of water over a given time span. This the inherent degree of compaction is slightly less.
is perhaps due to its relatively high density and resultant Discretionary operator control during small-scale lab-
lower bulk porosity, as defined earlier. This has been oratory testing introduces factors that would not nor-
clearly illustrated in Table 1 where the average mass of mally be present in the testing of a full-sized wall.
sorbed water, during a 5-min IRS ‘wick’ test, for each Sample faces that were free from defects, for example,
material tested has been expressed as a percentage of were selected for testing to reduce the variability of
the sample’s dry mass. The initial rate of suction over results and random effects. This level of control is
a period of 5 min has been illustrated in Fig. 7 to show acceptable for small-scale laboratory testing, as the
the comparison between rammed earth and conventional number of variables should be minimised wherever
masonry materials. Fletton bricks and Engineering possible. The use of full-sized test walls would lessen
bricks, for example, have a higher suction rate than these considerations and, in one sense, provide a more
every rammed earth sample apart from 802. C30 con- realistic representation of the materials performance in-
crete is just above 703, which is the third poorest situ. However, accuracy and quality control tend to
rammed earth sample. The fired clay brick IRS curves diminish as the scale of the test increases.
are a different gradient to rammed earth, but concrete is Fig. 8 shows the comparison between the ten rammed
almost the same indicating similarities between their earth soil types tested over a 60-min duration. The IRS
internal pore structure. The large degree of variation curves exist in three distinct bands: high (802), medium
that occurred between individual test specimens was (712, 703, 424) and low (523, 613, 433, 622, 532,
attributed to natural variations in pore structure both 514). Beyond the 10-min point, the IRS of all samples
M. Hall, Y. Djerbib / Construction and Building Materials 18 (2004) 269–280 275

Fig. 7. IRS ‘wick’ test results (5-min regime) for rammed earth vs. conventional masonry.

begins to decrease significantly and by 50–60 min, all being re-tested in the 60-min regime. Re-testing rammed
samples are at a very similar IRS value. Notably, it has earth appears to result in lowering its IRS value. The
been observed previously that after approximately 3 h average variation between results, due to repeat testing,
of testing mw is proportional to t giving experimental indicates an approximate decrease in IRS value from as
confirmation of a steady state in three-dimensional water little as 5% up to as much as 44%. The quantity of
absorption scenarios such as this. The ‘wick’ test is reduction in IRS appears to coincide with samples that
three-dimensional because Hall w14x previously observed absorb more water due to capillary suction, as can be
that, in a modified IRS test, a spherical inflow source clearly seen from Fig. 9. This indicates that the ingress
in the centre of sample face allows for lateral spreading of water may have changed the properties of the mate-
of the sorbed water within the material. It is possibly rial, such as its internal pore structure, especially since
more realistic than the one-dimensional BS 3921 IRS the surface finish had visibly become altered following
test for experimentally determining the ingress of mois- the first regime of testing.
ture, due to capillary suction, and comparing the results Theoretically the yt law (detailed above) is only
obtained to those for full-sized test walls. Furthermore, applicable for the one-dimensional case of the BS 3921
the geometry and dimensions of inflow-surface area on IRS test where the inflow of sorbed water is normal to
the IRS ‘wick’ test can be transposed to other three- the inflow surface w14x. Hall states that for the circular
dimensional moisture ingress test methodologies, such source, with three-dimensional lateral internal spreading
as the Initial Surface Absorption (ISA) test, to allow (i.e. IRS ‘wick’ test), cumulative absorption should
for comparison between the obtained data. increase more rapidly than yt for common clay bricks
Differences were observed, in the IRS of a given w14x. However, the results obtained for rammed earth
sample, between being tested in the 5-min regime, and show that when the mass of sorbed water wmw(g)x is
276 M. Hall, Y. Djerbib / Construction and Building Materials 18 (2004) 269–280

Fig. 8. IRS ‘wick’ repeat-test results (60-min regime) for rammed earth.

w z were found to give no obvious pattern or relationship


plotted against the root of time xyytŽmin.|~ the relationship with the IRS value.
is clearly linear as can be seen from Fig. 10. This may The total specific surface area (SSA) value for each
be because the total mass of sorbed water is considerably soil type was calculated using the retained mass values
less in rammed earth, and the internal pore structure is obtained during sieve analysis. Assuming each individ-
quite different. The linear value allows for interpolation ual soil particle to be spherical, its surface area can be
and future forecast of the amount of water taken up by simply calculated using 4pr2. The mass retained for
a given mass of rammed earth after a given elapsed each particle diameter is known; therefore the SSA can
time. It also shows the performance of each soil type be calculated and expressed in millimetre square per
more clearly allowing direct comparisons to be made gram. The total SSA for a given soil type is simply the
more easily. Notably, the same three bands appear: high, summation of the SSA values obtained for each sieve
medium and low, as described earlier. size. The author hypothesised that the binder is not as
The bulk porosity of the samples was calculated by effectively distributed amongst the aggregate particles
first determining the particle density of each soil type when the specific surface area of the latter is increased
in accordance with BS 1377 w18x. The calculation of beyond a certain value. This may result in the enhanced
void space (bulk porosity) within a rammed earth ability of the aggregate to adsorb moisture, due to
sample can thus be calculated when its dry mass and surface tension, resulting in increased capillary potential
volumetric proportions are known. Fig. 11 illustrates the within the matrix. It may also lead to areas of pore
positive relationship that exists between bulk porosity space that are devoid of binder leaving few obstructions
and the IRS value taken after 1 min of testing. The bulk to impede the flow of imbibed water. This decrease in
porosity (total void space) of rammed earth is therefore effective binder distribution within the matrix of the
likely to be a similar value to the apparent porosity, i.e. material may lead to a more open-structured pore net-
the amount of void space that is permeable and not work capable of allowing a greater rate of moisture
enclosed. This indicates that much of the pore space ingress and subsequent migration. In support of this
within rammed earth is possibly interlinked and poten- theory, Figs. 12 and 13 show an increase in average IRS
tially permeable to moisture. Linear increasesydecreases value coinciding with a relative increase in the mass of
in the compressive strength of rammed earth, however, particles with diameters between 63 um and 3.35 mm,
M. Hall, Y. Djerbib / Construction and Building Materials 18 (2004) 269–280 277

Fig. 9. Variation of IRS in rammed earth samples due to single repeat-testing.

but with a sharp decrease in the mass of particles above suitable for use with unstabilised earth materials that
3.35 mm. This may indicate that a rise in the number slake on contact with water. It produces consistent results
of particles )3.35 mm can give a sufficient decrease in that, for dense samples such as rammed earth, are in
total SSA such that the effectiveness of binder distri- good agreement with the original BS 3921 IRS test.
bution returns to a level where capillary potential is Rammed earth generally outperforms conventional
significantly reduced. It can be observed that when the modern masonry materials significantly in terms of the
ratio of )3.35 to -3.35 mm particles (defined here as rate and quantity of moisture ingress due to capillary
the ‘3.35 ratio’) is greater than 5, the amount of water suction. However, the particle-size distribution of the
imbibed due to capillary suction increases to measurably soil is critical in determining the rate at which moisture
significant levels. This observation has been clearly may ingress due to capillary suction. The ingress of
illustrated in Fig. 14. moisture into rammed earth appears to alter its properties
such that in a repeat test the IRS is reduced. The amount
7. Conclusions
by which the IRS value is reduced in a repeat test
The novel IRS ‘wick’ test has been devised as a appears to be proportionally indexed to the original IRS
peripheral to the established BS 3921 IRS test, and is value prior to repeat testing.

Fig. 10. Relationship between mass of sorbed water and square root of elapsed time.
278 M. Hall, Y. Djerbib / Construction and Building Materials 18 (2004) 269–280

Fig. 11. Relationship between the bulk porosity of rammed earth and its IRS value.

Moisture ingress in rammed earth, due to capillary linked with the rate of capillary suction in rammed
suction, increases linearly per unit inflow surface area earth. When the mass of the binder fraction in a suitable
against the square root of elapsed time Žyt. . This allows soil is less than 10% of the total soil mass, it would
predictions to be made on the rate and amount of appear that the rate of moisture ingress, due to capillary
moisture ingress at a given future point in time. The suction, in rammed earth is significantly increased. It is
results obtained are in good agreement with current non- hypothesised, therefore, that through granular stabilisa-
saturated flow theory further supporting the validity of tion (i.e. artificially modifying the particle-size distri-
the proposed IRS ‘wick’ test. bution through additionysubtraction of material) the rate
In a suitable soil, the ratio between the total specific of capillary moisture ingress in rammed earth can be
surface area (SSA) of the aggregate fraction and the controlled. A simple initial suggestion may be to ensure
mass of the binder fraction appears to be positively a minimum binder quantity of approximately 10% by

Fig. 12. Particle-size distribution and IRS values for rammed earth soils with two parts binder.
M. Hall, Y. Djerbib / Construction and Building Materials 18 (2004) 269–280 279

Fig. 13. Particle-size distribution and IRS values for rammed earth soils with three parts binder.

Fig. 14. Relationship between IRS value and ‘3.35 ratio’ for rammed earth soils containing two and three parts binder.

mass. A ‘3.35 ratio’ of 5 has been proposed as a for pictures, helpful advice and discussion Stephen
potential target value by which to attenuate the required Hetherington (Sheffield Hallam University) for techni-
approach to granular stabilisation. The 802 soil (worst), cal support Paul Scholey (Rotherham Sand & Gravel
for example, can have its ‘3.35 ratio’ lowered from Co Ltd.) for generous donation of earth materials.
above 20.0 to below 5.0 by adding 12% by mass of 10
mm pea gravel. This should have the effect of lowering References
the rate of moisture ingress due to capillary suction, or w1x Hall M, Djerbib Y. Rammed earth sample production: context,
even achieving an optimum value. This observation has recommendations and consistency. Constr Build Mater
significant practical applications but requires testing in 2004;118(4):281 –286.
the field in order to prove or disprove the hypothesis. w2x Dobson S. (RAMTEC Pty Ltd.) Pers. comm.
w3x Oliver A. Dampness in buildings. Second ed. Oxford: Black-
Acknowledgments wells, 1997.
w4x Building research establishment (BRE). The selection of nat-
The author wishes to acknowledge the help of the ural building stone. London: HMSO, 1983. p. 1 –8 (Digest
following parties: Stephen Dobson (RAMTEC Pty Ltd) 269).
280 M. Hall, Y. Djerbib / Construction and Building Materials 18 (2004) 269–280

w5x Laycock EA. Frost degradation and weathering of the magne- 27–30 October 1981: part A deterioration, Rossi-manaresi R.
sian limestone building stone of the Yorkshire province. Ph.D. (ed.), Bologna, pp. 59–72.
Thesis, University of Sheffield, 1997. w12x Vos BH, Tammes E. Moisture and moisture transfer in porous
w6x Hall C. Water movement in porous building materials – I: materials. Report no. BI-69-96, Nov 1969. Organisation for
unsaturated flow theory and its applications. Build Environ industrial research TNO, Institute TNO for building materials
1977;12:117 –25. and building structures, Delft, Holland.
w7x Killip IR, Cheetham DW. The prevention of rain penetration w13x British Standards Institute (BSI). BS 3921: 1985 (partially
through external walls and joints by means of pressure equal- withdrawn) specification for clay bricks. BSI: London, 1985.
isation. Build Environ 1984;19(2):81 –91. w14x Hall C. Water movement in porous building materials – IV:
w8x Camuffo D. Physical weathering of stones. Elsevier Science, the initial surface absorption and the sorptivity. Build Environ
1995. p. 1 –14. 1981;16(3):117 –25.
w15x Hall C, Kam-Ming Tse T. Water movement in porous building
w9x Vos BH, Tammes E. Flow of water in the liquid phase. Report
materials – VII: the sorptivity of mortars. Build Environ
no. B 1-68-38, Inst. TNO for building materials and building
1986;21(2):113 –8.
structures, Delft, Holland, 1968. w16x Minke G. Earth construction handbook: the building material
w10x Kieslinger A. Feuchtigkeitsschaden ¨ an bauwerken. Zemet earth in modern architecture. UK: WIT Press, 2000.
Beton 1957;9:1 –7. w17x De Freitas VP, Abrantes V, Crausse P. Moisture migration in
w11x Mamillan. Connaissances actuelles des problemes de remontees ´ building walls – analysis of the interface phenomena. Build
d’eau par capillarite´ dans les mures. Rapporti della soprinten- Environ 1996;31(2):99 –108.
denza per I beni artistici e storica per le province di bologna, w18x British Standards Institute (BSI). BS 1377-2: 1990 soils for
Ferrara, forli e ravenna. The conservation of stone II pre-prints civil engineering purposes – part 2: classification. BSI: Lon-
of the contributions to the international symposium, Bologna, don, 1990.

You might also like