Professional Documents
Culture Documents
2002
NEC
CHANGES
Affecting Wiring Devices
$
5.00
TABLE OF CONTENTS PAGE A Message From
Global NEC Changes 2 Leviton Manufacturing Company
2002 NEC Art i cle Renumbering Guide 3
ARTICLE 100 DEFINITIONS 4 Eve ry three years the National Fire Protection
ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS
110.14(C)(1) E l e c t rical Connections 6
Association (NFPA) revises the National
ARTICLE 210 BRANCH CIRCUITS E l e c t ric Code (NEC). Revisions are made to
210.7(C) Branch Circuit Receptacle Requirements 6 improve safety and to set standards for
210.8(A)(8) Ground-Fault Circuit-Interrupter 7
Protection for Personnel handling new electric products and technolo-
210.8(B)(1)(2) &(3) Ground-Fault Circuit-Interrupter 8
Protection for Personnel gies. The new 2002 NEC was released in
210.12(A)(B) Arc-Fault Circuit-Interrupter (AFCI) Protection 9
210.52(C)(5) Dwelling Unit Receptacle Outlets 10 September of 2001 and reflects their
210.52(D) Dwelling Unit Receptacle Outlets 11 latest effort.
210.52(G) Dwelling Unit Receptacle Outlets 13
210.63 Heating, Air-Conditioning, and
Refrigeration Equipment Outlet
13 For 2002, there are hundreds of changes to
210.70(A)(2)(c) Lighting Outlets 14 the NEC. This document identifies the
ARTICLE 250 GROUNDING changes that directly influence the day-to-day
250.146(A) Connecting Receptacle Grounding 15
Te rminal to Box responsibilities of the Electrical Contractor,
ARTICLE 285 TRANSIENT VOLTAGE SURGE
SUPPRESSORS (TVSS)
Building Engineer, Electrical Inspector and
285.1 Scope 16 any individual responsible for electrical instal-
285.5 Listing 16
285.6 S h o rt-circuit Current Rating 16 lations. Tips are given on proper electrical
285.12 Routing of Connections 16
285.21(A)(1)(2)(3) Connection 18
installations, advice or cautions to possible
ARTICLE 404 SWITCHES
conflicts or confusing code rules, and wa rn-
404.8(B) Accessibility and Grouping 20 ings of dangers related to improper electrical
404.9(B)(1)(2) Provisions for Grounding Switch Faceplates 20
404.14(E) Rating and Use of Switches (Including Dimmers) 22 installations. E l e c t rical wo rk is not always an
404.15(B) Switch Marking 22
exact science. Fortunately, the Code allows for
ARTICLE 406 RECEPTACLE, CORD CONNECTORS,
AND ATTACHMENT PLUGS (CAPS) the Au t h o rity Having Ju risdiction (AHJ), the
406.8 Receptacles in Damp or Wet Locations 23, 25, 26
(A)(B)(1)(2)(a)(b) flexibility to waive specific requirements of the
ARTICLE 517 HEALTH CARE FACILITY NEC, or permit alternate methods when
517.13(A)(B) Grounding of Receptacles and Fixed 28
E l e c t ric Equipment in Patient Care Areas assured that equivalent objectives for estab-
517.30(E) Essential Electrical Systems for Hospitals 30 lishing and maintaining effective safety can be
517.41(E) Essential Electrical Systems for Nursing 30
Homes and Limited Care Facilities achieved (80.13 and 90.4). This handbook ref-
ARTICLE 547 AGRICULTURAL BUILDINGS erences related Code rules, we recommend
547.2 Definitions 31
547.5(C)(1)(2)(3) W i ring Methods 31, 32 that you reference the actual 2002 NEC Code
547.5 (G)(1)(2)(3) W i ring Methods 32
547.10(A)(B)(C) Equipotential Planes and Bonding of 33
Book for a thorough understanding of the
Equipotential Planes
entire Code as well as each specific Code
ARTICLE 550 MOBILE HOMES, MANUFACTURED
HOMES, AND MOBILE HOME PARKS change.
550.25(B) Arc-Fault Circuit Interrupter Protection 34
We hope you find this product guide useful.
ARTICLE 555 MARINAS
555.1 Scope 36
555.2(1)(2) Definitions 36
555.17(B) Boat Receptacle Disconnecting Means 37
555.19(A)(4)(a)(b) Boat Receptacle 37
1
About This Book 2002 NEC ARTICLE RENUMBERING GUIDE
Crossed-out text identifies text that was included in the 1999 To achieve a uniform nu m b e ring system, all wiring method
NEC, but eliminated for the 2002 NEC. Articles had their sections renumbered:
Text that is intended to represent the paraphrased language Article Numbers—
of the 2002 NEC is displayed in the color B l u e.
New Old
Underlined text is intended to represent the intended
change in the 2002 NEC from the 1999 NEC. It is not 312 373 Cabinets and Cutout Boxes
intended to represent an Internet link. 314 370 Outlet Boxes
After each Code article, B rown text identifies appropriate
Leviton product that satisfies the intent of the article. 320 333 Armored Cable–Type AC
324 328 Flat Conductor Cable
GLOBAL NEC CHANGES
330 334 Metal Clad Cable–Type MC
Some changes appear throughout the revised Code for the
purpose of making the NEC easier to use in the United 332 330 Mineral Insulated Cable–Type MI
States, as well as internationally. 334 336 Nonmetallic Sheath Cable–Type NM
Format—The format system for the 2002 NEC wa s 336 340 Tray Cable–Type TC
changed from the “hyphen” system to the “dot” system. For
example, Section 110-26 will now be 110.26. The first letter 338 338 Service Entrance Cable–Type SE
will be capitalized and the following characters will be lower
case. For example: 110.26(A), 110.26(A)(1), 110.26(A)(1)(a) 340 339 U n d e r ground Feeder Cable–Type UF
New Articles—Many new Articles were added, for example: 342 345 Intermediate Metal Conduit
ARTICLE 285—TRANSIENT VOLTAGE SURGE 344 346 Rigid Metal Conduit
SUPPRESSORS (TVSS)
348 350 Flexible Metal Conduit
ARTICLE 406—RECEPTACLES
350 351A Liquidtight Flexible Metal
ARTICLE 647—SENSITIVE ELECTRONIC EQUIPMENT
352 347 Rigid Nonmetallic Conduit
Metric Units—All units of measurement are now listed with
the metric unit first by the foot/pound measurement in 354 343 U n d e r ground PVC with Conductors
parentheses.
356 351B Liquidtight Nonmetallic Conduit
Parts—Article parts in the 1999 NEC were identified by an
upper case letter, such as Part A, Part B, and Part C. The 358 348 Electrical Metallic Tubing
2002 NEC identifies Article parts by a Roman numeral, 362 331 Electrical Nonmetallic Tubing
such as Part I, Part II, and Part III.
366 374 Auxiliary Gutters
368 364 Busways
370 365 Cablebus
372 358 Cellular Concrete Raceway
374 356 Cellular Metal Floor Raceway
376 362A Metal W i r eways
378 362B Nonmetallic Wireways
380 353 Multioutlet Assembly
382 342 Nonmetallic Extensions
384 352C Strut-Type Channel Raceways
386 352A Surface Metal Raceways
388 352B Surface Nonmetallic Raceways
390 354 Underfloor Raceways
392 318 C a ble Trays
394 324 Concealed Knob-and-Tube
396 321 Messenger Supported Wiring
398 320 Open W i ring on Insulators
404 380 Switches
406 410 Receptacles, Cord Connectors
408 384 Switchboards and Panelboards
527 305 Te m p o ra ry Installations
2 3
The Real Thing.
The Leviton Smart Lock™
ARTICLE 100–DEFINITIONS
Article 100 contains the definitions of those terms used
throughout the Code. In general, only those terms used in
two or more Articles are defined in Article 100. A definition
that is listed in a specific Article applies to that Article only,
GFCI with Lock-Out Action.
and a definition given at the beginning of a Part only applies
to that Part.
The definition for “Ground-Fault Circuit Interrupter” was
revised to read:
Ground-Fault Circuit Interrupter. A device intended to
protect persons by functioning to de-energize a circuit within
a short period of time when a current to ground exceeds the
value established for a “Class A” device.
Figure 100–2
4 5
ARTICLE 110 – REQUIREMENTS FOR Figure 210–1
ELECTRICAL INSTALLATIONS
110.14 Electrical Connections
New text was added to clarify conductor sizing for term i n a l s
and it reads:
(C) Temperature Limitations.
(1) Equipment Provisions. Unless the equipment is listed
and marked otherwise, conductor ampacities used in deter-
mining equipment termination provisions shall be based on
Table 310.16.
Intent: New text is intended to clarify that Table 310.16 is to
be used when sizing conductors to comply with the terminal
requirements of this subsection. For example, a 50A circuit
would require 6 AWG conductors for 60°C terminals or 8
AWG for 75°C term i n a l s, in accordance with Table 310.16.
Figure 110-2
6 7
Intent: This small change now requires all 15 and 20A, sin- 210.12 Arc - Fault Circuit-Interrupter (AFCI) Protection
gle-phase, 125V receptacles installed in boathouses to be
The word “receptacle” was deleted and the words “listed
GFCI-protected. The GFCI protection requirement for 15 device that protects the entire branch circuit” were added.
and 20A, single-phase, 125V receptacles installed in
dwelling unit boathouses was relocated from Article 555 – This subsection now reads:
M a rinas and Boatyards. Also, the Code does not require a (A) AFCI Definition. An AFCI protection device provides
receptacle to be installed in a boathouse, but if a 15 or 20A, protection from an arcing fault by recognizing the character-
single-phase, 125V receptacle is installed, it must be istics unique to an arcing fault and by functioning to de-
GFCI-protected. e n e r g i ze the circuit when an arc fault is detected.
210.8 Ground-Fault Circuit-Interrupter Protection (B) Dwelling Unit Bedrooms. All branch circuits supplying
for Personnel 15 or 20A, single-phase, 125V receptacle outlets installed in
d welling unit bedrooms must be AFCI protected by a listed
A new subsection was added to include kitchens. device that protects the entire branch circuit.
(B) Other than Dwelling Units. All 15 and 20A, single- Figure 210–4
phase, 125V receptacles installed in the locations specified
below shall have ground-fault circuit-interrupter protection
for personnel.
(1) Bathrooms (2) Rooftops (3) Kitchens
Figure 210–3
8 9
Leviton Note: As of the date that this book was published, Intent: The distance from the bottom of the top cabinets to
there are no commercial AFCI Outlet Branch Circuit Type or a counter surface is typically 18 in. This change permits a
AFCI Outlet Type protection devices (receptacle based multioutlet assembly to be installed in the 2 in. recess
devices described in points 2 & 3 above) available to the beneath the top cabinet, thereby allowing for mounting of
e l e c t rical industry. To this point, these devices are still in the under-cabinet appliances.
development stage and have yet to be perfected. An “appliance garage” is an enclosed area on the counter
Author’s Comment: At the time a dwelling unit is surface where an appliance can be stored and hidden from
view when not in use. If a receptacle is installed inside an
wired, it is hard to tell from looking at the bare walls “appliance garage” it cannot count as a kitchen counter sur-
whether a room will be used as a home office or a
bedroom. Also, if you are looking at an efficiency face outlet required for dwelling units.
apartment, a room may well be furnished with a fold- 210.52 Dwelling Unit Receptacle Outlets
out couch that is used for sleeping on every night,
making it look as much like a bedroom as a living This section was revised to read:
room. If you wire bedroom branch circuits with one (D) Bathrooms. In dwelling units, at least one 15 or 20A,
circuit for lighting and receptacles, this change will
have little effect. However, the practice of separating single-phase, 125V receptacle outlet must be installed in
bathrooms within 3 ft of the outside edge of each basin. The
the lighting from the receptacle circuits in dwelling receptacle outlet must be located on a wall or partition that
unit bedrooms will now require two AFCI circuit
breakers. The 125V limitation to the requirement is adjacent to the basin, or basin counter surface.
means that AFCI protection would not be required for Figure 210–6
a 240V baseboard heater or room air conditioner. For
more information—
www.mikeholt.com/Newsletters/Newsletters.htm,
go to the “Miscellaneous” section and visit my
“AFCI” links.
210.52 Dwelling Unit Receptacle Outlets
The maximum distance the required receptacle for the
counter surface can be above the kitchen counter surface of
a dwelling was changed from 18 in. to 20 in. The revised
rule reads:
(C) Counter Surfaces
(5) Receptacle Location. Receptacle outlets required for
the counter surface must be located above, but not more
than 20 in. above the counter surface. Receptacle outlets
that are not accessible by appliances fastened in place,
located in appliance gara g e s, or that supply appliances that
occupy dedicated space cannot be used as the required
counter surface receptacles.
Figure 210–5
Intent: This change clarifies that the bathroom receptacle
outlet can be installed on a partition as well as the wall that
is adjacent to the basin or basin counter surface.
Author’s Comment: GFCI protection is required for all
15 and 20A, single-phase, 125V receptacles in all
bathroom areas of dwelling units (210.8(A)(1)).
10 11
Do your electrical
receptacles meas- 210.52 Dwelling Unit Receptacle Outlets
This section was revised to read:
ure-up to the NFPA (G) Basements and Garages. For a one-family dwelling, at
least one 15 or 20A, single-phase, 125V receptacle outlet,
in addition to any provided for laundry equipment, shall be
installed in each basement. Where a portion of the base-
ment is finished into one or more habitable rooms, each
separate unfinished portion must have a 15 or 20A, single-
phase, 125V receptacle outlet installed.
Figure 210–7
12 13
Exception: A receptacle outlet cannot be required for ARTICLE 250—GROUNDING
rooftop equipment on one and two-family dwellings.
This article covers the requirements for providing a path to
Author’s Comment: This rule does not require a recep- earth for high voltage surges from lightning. In addition, this
tacle within 25 ft of ventilating equipment. article contains the requirements for the low-impedance
Intent: The changes require a 15 or 20A, single-phase, fault current path necessary to remove dangerous voltage
125V receptacle outlet be located within 25 ft of heating, from conductive parts from a system failure.
air-conditioning, and refrigeration equipment (HACR) for all
occupancies, including one and two - family dwellings. This 250.146 Connecting Receptacle Grounding
receptacle must be GFCI-protected if it is located outdoors Terminal to Box
[210.8(A)(3)] or in crawl spaces at or below grade The first sentence of 250.146 in the 1999 NEC was revised
[210.8(A)(4)]. Previously this rule only applied to rooftops. to delete the words “or at”. This section now reads:
Author’s Comment: The outside 15 or 20A, single- (A) Surface Mounted Box. A separate bonding jumper
phase, 125V receptacle outlet required for dwe l l i n g from a receptacle’s grounding terminal is not required if the
units [210.52(E)] could be used to satisfy this require- receptacle is installed in a box that is mounted on or at the
ment, but only if the receptacle outlet is located within surface and direct metal-to-metal contact is made between
25 ft of the equipment. the device yoke and the box.
Figure 250–21
Leviton manufactures GFCI’s in many configurations,
among them:
Cat. No. 6899 20 Amp
GFCI Receptacle
• Back & side wired
• Impact-resistant thermoplastic
construction
• Feed-through protection for
receptacles downstream
14 15
Are You Offering Your
ARTICLE 285 – TRANSIENT VOLTAGE SURGE
SUPPRESSORS (TVSS) Customers The Latest
This Article covers general requirements, installation
requirements, and connection requirements for transient in Surge Protection
Technology?
voltage surge suppressors (TVSS) permanently installed on
premises wiring systems. It does not apply to cord- and-
plug-connected units such as “computer power stri p s.”
This new Article was added to cover the installation require-
ments for Transient Voltage Surge Suppressors (TVSS),
which is a listed protective device that limits transient vo l t-
ages by limiting surge current or diverting it to ground.
Intent: Article 280 in the 1999 NEC contained the installa-
tion requirements for “Surge Arresters”, which are installed
at service equipment (main disconnect). H owever, it did not
have any rules for TVSS devices, which are typically
installed at panelboards.
285.1 Scope
This Article covers the installation and connection require-
ments for TVSS that are permanently installed on premises
wiring systems.
Figure 285–1
16 17
285.21 Connection Leviton Industrial
Where a TVSS is installed, it must be connected as follows:
(A) Location. Power Light (PL) Plugs
(1) Service Supplied Building or Structure. A TVSS can
be connected anywhere on the premises wiring system, but and Connectors
not on the line side of service disconnect overcurrent device.
Figure 285–2 15, 20, and 30 Amp 125 Volt Straight Blade
and Locking Configurations Available
18 19
Our dimmers
turn a hole in
ARTICLE 404 (380)—SWITCHES
The requirements of Article 404 apply to switches of all
types, such as snap (toggle) switches, dimmers, fan
a window of
The text to this section was revised to read:
(B) Voltage Between Adjacent Devices. Snap switches
shall not be grouped or ganged in enclosures with other
snap switches, receptacles, or similar dev i c e s, if the voltage
between adjacent devices exceeds 300V, unless they are
installed in enclosures equipped with permanently installed
b a r riers between adjacent devices.
Figure 404-1
Intent: This rule in the 1999 NEC only prohibited the gang-
ing of switches if the voltage exceeded 300V. The text in the
2002 NEC, has extended this requirement if the voltage
exceeds 300V between switches and other devices such as
receptacles.
404.9 Provisions for Grounding Switch Faceplates
The text to this subsection was revised to read:
(B) Grounding. Snap switches, including dimmer and simi-
lar control switches, must be effectively grounded and must
provide a means to ground metal faceplates, whether or not
a metal faceplate is installed. Snap switches must be con- MonetTM MuralTM Toggle TouchTM
sidered effectively grounded in accordance with (1) or (2). architectural Decora®-style digital preset
Figure 404-2 specification- digital dimmer touch dimmer
grade dimmer
Certification and
Training Program
Powerful support
from Leviton
24 25
Let Leviton Sell-Up
(2) Other Receptacles. All other receptacles installed in a
wet location must comply with (a) or (b):
Your Next Job!
(a) A receptacle installed in a wet location must have a
“raintight while-in-use” cover (enclosure that is weatherproof
Direct Your
with the attachment plug cap inserted), if stationary or fixed
equipment is plugged into it. Customers
(b) A receptacle installed in a wet location having a “weather
resistant” cover (cover that is weatherproof when the cover
is closed and an attachment plug is not inserted) is perm i t-
To Leviton’s
ted, if portable equipment is plugged.
Figure 406-3
26 27
Figure 517-2
ARTICLE 517 – HEALTH CARE FACILITY
Article 517 applies to electrical wiring in health care facilities
such as hospitals; nursing homes; limited care; supervisory
care; clinics; medical and dental offices, and ambulatory
care, whether permanent or movable. This Article is not
intended to apply to animal veterinary facilities.
517.13 Grounding of Receptacles and Fixed Electric
Equipment in Patient Care Areas
The section was completely revised to read as follows:
W i ring in patient care areas must comply with (A) and (B) below:
(A) Wiring Methods. All branch circuits serving patient care
areas must be installed in a metal raceway or cable that is
listed in 250.118 as an acceptable grounding return path,
such as EMT and/or Type AC cable.
Figure 517-1
28 29
517.30 Essential Electrical Systems for Hospitals 547.2 Definitions
A new subsection was added and it reads: The definition for an Equipotential Plane was revised to read:
(E) Receptacle Identification. The cover plates for recep- Equipotential Plane. An area where wire mesh or other
tacles, or receptacles supplied from the emergency system, conductive elements are embedded in or placed under c o n-
must have a distinctive color or marking so as to be readily crete, bonded to all metal structures and fixed nonelectri c a l
identifiable. equipment that may become energized to the grounding
Figure 517-4 system. The purpose of the equipotential plane is to prevent
a difference in voltage within the plane area.
Figure 547-1
32 33
Discovering the
FPN No. 1: Methods to establish equipotential planes are
d e s c ribed in Equipotential Planes in Animal Containment
Areas, American Society of Agricultural Engineers
benefits of occu-
(ASAE) EP473-1997. For more information, call the soci-
ety at 1-616-429-0300.
Author’s Comment: To see the report on Stray Voltage
pancy sensors
Problems with Dairy Cows available from the
University of Minnesota; call 1-612-625-8173.
FPN No. 2: Low grounding electrode system resistances
may reduce potential differences in livestock facilities.
Intent: The intent of the revisions is to clarify that an equipo-
tential plane is not required for indoor or outdoor dirt confine-
ment areas, if GFCI protection is provided for electrical
equipment accessible to animals in the confinement areas.
34 35
ARTICLE 555 – MARINAS 555.17 Boat Receptacle Disconnecting Means
555.1 Scope The requirement for the boat disconnecting means was
completely revised to read:
A new sentence was added, which reads:
(B) Location. The disconnecting means for a boat recepta-
This Article covers the installation of wiring and equipment cle must be readily accessible and not more than 30 in. from
in the areas comprising fixed or floating piers, wharfs, the receptacle. Circuit breakers or switches located in
docks, and other areas in marinas, boatyards, boat basins, m a rine power outlets can be used for the boat receptacle
boathouses, and similar occupancies that are used, or disconnecting means.
intended for use, for the purpose of repair, berthing, launch-
ing, storage, or fueling of small craft and the moorage of Figure 555-2
floating buildings. Private, noncommercial docking facilities
constructed or occupied for the use of the owner or resi-
dents of the associated single-family dwelling are not cov-
ered by this Article.
Intent: This clarifies that the requirements of Article 555 do
not apply to boat docks at a single-family dwe l l i n g . For sin-
gle-family dwellings, GFCI personnel protection is required
for all 15 and 20A, single-phase, 125V receptacles located
outdoors or in boathouses [210.8(A)(3) and 210.8(A)(8)].
Author’s comment: There is no definition for single-
family dwelling unit, but I think it is a single dwe l l i n g
unit [Article 100]. Docking facilities at buildings con-
taining more than one dwelling unit such as duplexes,
condominiums, apartments fall under the requirements
of Article 555.
Leviton manufactures GFCI’s in many configurations.
See illustrations throughout this publication or contact
Leviton for more information.
555.2 Definitions
A definition for Electrical Datum Plane was added and
it reads: Intent: This requirement was extracted from NFPA 303—
Fire Protection Standard for Marinas and Boatyards.
Electrical Datum Plane. The electrical datum plane is
defined as follows: 555.19 Boat Receptacle
(1) Land areas subject to tidal fluctuation. The electrical N ew text was added and it reads:
datum plane is a hori zontal plane 2 ft above the highest (A) Boat Receptacles
high tide level for the area occurring under normal circum- (4) Ratings. Receptacles that provide shore power for boats must
stances. be rated not less than 30A and must be a single-outlet type.
(2) Land areas not subject to tidal fluctuation. The electrical (a) Receptacles rated 50A and less must be of the locking and
datum plane is a hori zontal plane 2 ft above the highest grounding-type.
water level for the area occurring under normal circum- Figure 555-3
stances.
Figure 555-1
A p p l i c a ble Leviton
Cat. Nos. 4100P12W and
4100C12W Pin & Sleeve Type
L o cking Plug & Connector
• Engineered to IP67 Watertight
Standards
• Listed to meet UL, CE, CSA, IP
and IEC standards
• 2-Year limited warranty
38 39
One or more means to disconnect all ungrounded (hot) conduc- Figure 680-4
tors must be provided for all utilization equipment other than
lighting. Each means must be accessible and within sight (within
50 ft) from its equipment.
Figure 680-3
40 41
“With my heavy work
load, For areas where a higher level
how can I keep up with of protection is desired, Leviton
Smart Lock™ GFCI.
Assistance Pro g r a m s
n Contractor Marketing n F requently Asked
P ro g r a m s Questions
The Contractor Connection was designed to convey
information that you can use to sell-up your services
and better your business.
Please visit the Contractor Connection and see how
Leviton can help you become a better contractor.
42 43
Learn The ABC’s of
Sales and Marketing NOTES
with Leviton’s
“Contractor
44 45
Leviton wants to help electrical contractors and tra d e
professionals keep up with the most current changes
that will affect the way they do business.
Visit Leviton’s Code Connection Web site at
www.leviton.com