Professional Documents
Culture Documents
pro
Article 690
● Solar Photovoltaic (PV) Systems 685.14
A person designated as a qualified person shall TABLE 685.3 Application of Other Articles
possess the skills and knowledge related to the con-
struction and operation of the electrical equipment and Conductor/Equipment Section
installation and shall have received documented safety
training on the hazards involved. Documentation of More than one building or 225, Part II
other structure
their qualifications shall be on file with the office of the
Ground-fault protection of 230.95, Exception
establishment in charge of the completed installation. equipment
(3) Effective safeguards acceptable to the authority having Protection of conductors 240.4
jurisdiction are established and maintained. Electrical system coordination 240.12
Ground-fault protection of 240.13(1)
equipment
The integrated electrical systems commonly used in large Grounding ac systems of 50 250.21
and complex industrial processes are designed, installed, volts to less than 1000 volts
and operated under stringent on-site engineering supervi- Equipment protection 427.22
sion. The control equipment, including overcurrent devices, Orderly shutdown 430.44
is located so that it is accessible to qualified personnel, but Disconnection 430.74, Exception Nos. 1 and 2
Disconnecting means in sight 430.102(A), Exception No. 2
that location might not meet and is not required to meet the from controller
conditions described in the Article 100 definition of readily Energy from more than one 430.113, Exception Nos. 1 and
accessible. Locating overcurrent devices and their associ- source 2
ated disconnecting means so that it is not readily accessible Disconnecting means 645.10, Exception
to unqualified personnel is one of the preventative measures Uninterruptible power supplies 645.11(1)
used to help maintain continuity of operation. (UPS)
For some industrial processes, the sudden loss of elec- Point of connection 705.12(A)
tric power to vital equipment is an unacceptable level of
risk, and an orderly shutdown procedure is necessary to pre-
vent severe equipment damage, injury to personnel, or, in ARTICLE 690
some extreme cases, catastrophic failure. Orderly shutdown Solar Photovoltaic (PV) Systems
is commonly employed in nuclear power–generating facili-
ties, paper mills, and other areas with hazardous processes.
Contents
I. General
685.3 Application of Other Articles 690.1 Scope
The articles/sections in Table 685.3 apply to particular cases 690.2 Definitions
of installation of conductors and equipment, where there are 690.3 Other Articles
orderly shutdown requirements that are in addition to those 690.4 Installation
of this article or are modifications of them. (A) Photovoltaic Systems
(B) Identification and Grouping
II. Orderly Shutdown (C) Module Connection Arrangement
(D) Equipment
685.10 Location of Overcurrent Devices in or (E) Wiring and Connections
on Premises (F) Circuit Routing
Location of overcurrent devices that are critical to integrated (G) Bipolar Photovoltaic Systems
electrical systems shall be permitted to be accessible, with (H) Multiple Inverters
mounting heights permitted to ensure security from opera- 690.5 Ground-Fault Protection
tion by unqualified personnel. (A) Ground-Fault Detection and Interruption
(B) Isolating Faulted Circuits
685.12 Direct-Current System Grounding (C) Labels and Markings
690.6 Alternating-Current (ac) Modules
Two-wire dc circuits shall be permitted to be ungrounded.
(A) Photovoltaic Source Circuits
(B) Inverter Output Circuit
685.14 Ungrounded Control Circuits
(C) Disconnecting Means
Where operational continuity is required, control circuits of (D) Ground-Fault Detection
150 volts or less from separately derived systems shall be (E) Overcurrent Protection
permitted to be ungrounded.
The use of photovoltaic (PV) systems as utility-interactive FIGURE 690.1(A) Identification of Solar Photovoltaic
or stand-alone power-supply systems has steadily increased System Components.
as the technology and availability of PV equipment have
evolved. Also, recently passed legislation that provides fi-
nancial incentives to end users has resulted in the burgeon-
ing use of these system in residential, commercial,
institutional, and industrial settings. The requirements of Ar-
ticle 690 cover the use of stand-alone and utility-interactive
PV systems. Utility-interactive photovoltaic systems are
subject to the requirements for interconnected electric power
production sources contained in Article 705.
Exhibit 690.1 shows a custom-designed home with a
PV electrical system. The integrated array of glass panels on
the roof generates electricity directly from the sun using PV
modules.
EXHIBIT 690.1 Roof of a solar house that in the Northern
Hemisphere typically faces south to maximize exposure.
690.2 Definitions (Courtesy of Solar Design Associates, Inc.)
Alternating-Current (ac) Module (Alternating-Current
Photovoltaic Module). A complete, environmentally pro- An ac PV module consists of a single integrated mechanical
tected unit consisting of solar cells, optics, inverter, and unit. Because there is no accessible, field-installed dc wiring
other components, exclusive of tracker, designed to generate in this single unit, the dc PV source-circuit requirements in
ac power when exposed to sunlight.
Wind, engine-generator,
micro-hydro-electric, and Energy storage, charge controller,
other power sources and system control
Inverter input circuit
Inverter output circuit
Photovoltaic
output circuit
dc loads Inverter
Hybrid system
Charge controller
Photovoltaic output Inverter input circuit EXHIBIT 690.2 An array composed of multiple modules or pan-
circuit Inverter output circuit els installed on a support structure and foundation. (Courtesy of
Main supply NECA)
equipment for
Inverter ac loads
Array. A mechanically integrated assembly of modules or Electrical Production and Distribution Network. A
panels with a support structure and foundation, tracker, and power production, distribution, and utilization system, such
other components, as required, to form a direct-current as a utility system and connected loads, that is external to
power-producing unit. and not controlled by the photovoltaic power system.
production and distribution network. For the purpose of this into electric energy suitable for connection to a utilization
definition, an energy storage subsystem of a solar photovol- load.
taic system, such as a battery, is not another electrical pro-
duction source. Stand-Alone System. A solar photovoltaic system that
supplies power independently of an electrical production
Inverter. Equipment that is used to change voltage level or and distribution network.
waveform, or both, of electrical energy. Commonly, an in-
verter [also known as a power conditioning unit (PCU) or
power conversion system (PCS)] is a device that changes dc The simplified circuit schematics in Exhibits 690.3 through
input to an ac output. Inverters may also function as battery 690.6 demonstrate the use of various components in a PV sys-
chargers that use alternating current from another source tem. Specific requirements for overcurrent protection, discon-
and convert it into direct current for charging batteries. necting means, and grounding are covered in other sections of
Article 690 and should not be assumed based on these draw-
Inverter Input Circuit. Conductors between the inverter
ings. Instructions for, or labels on the PV module might re-
and the battery in stand-alone systems or the conductors be-
quire additional overcurrent devices that may not be shown.
tween the inverter and the photovoltaic output circuits for
electrical production and distribution network.
Inverter Output Circuit. Conductors between the inverter Subarray. An electrical subset of a PV array.
and an ac panelboard for stand-alone systems or the conduc-
tors between the inverter and the service equipment or an- 690.3 Other Articles
other electric power production source, such as a utility, for
electrical production and distribution network. Wherever the requirements of other articles of this Code and
Article 690 differ, the requirements of Article 690 shall
Module. A complete, environmentally protected unit con- apply and, if the system is operated in parallel with a pri-
sisting of solar cells, optics, and other components, exclu- mary source(s) of electricity, the requirements in 705.14,
sive of tracker, designed to generate dc power when exposed 705.16, 705.32, and 705.143 shall apply.
to sunlight.
Exception: Solar photovoltaic systems, equipment, or wir-
Monopole Subarray. A PV subarray that has two conduc-
ing installed in a hazardous (classified) location shall also
tors in the output circuit, one positive (1) and one nega-
comply with the applicable portions of Articles 500 through
tive(2). Two monopole PV subarrays are used to form a
516.
bipolar PV array.
Panel. A collection of modules mechanically fastened to- 690.4 Installation
gether, wired, and designed to provide a field-installable (A) Photovoltaic Systems. Photovoltaic systems shall be
unit. permitted to supply a building or other structure in addition
to any other electricity supply system(s).
Photovoltaic Output Circuit. Circuit conductors between
the photovoltaic source circuit(s) and the inverter or dc utili-
(B) Identification and Grouping. Photovoltaic source cir-
zation equipment.
cuits and PV output circuits shall not be contained in the
Photovoltaic Power Source. An array or aggregate of ar- same raceway, cable tray, cable, outlet box, junction box, or
rays that generates dc power at system voltage and current. similar fitting as conductors, feeders, or branch circuits of
other non-PV systems, unless the conductors of the different
Photovoltaic Source Circuit. Circuits between modules systems are separated by a partition. Photovoltaic system
and from modules to the common connection point(s) of the conductors shall be identified and grouped as required by
dc system. 690.4(B)(1) through (4). The means of identification shall
Photovoltaic System Voltage. The direct current (dc) volt- be permitted by separate color coding, marking tape, tag-
age of any photovoltaic source or photovoltaic output circuit. ging, or other approved means.
For multiwire installations, the photovoltaic system voltage is
the highest voltage between any two dc conductors.
Section 690.4(B) does not permit the alternating-current
Solar Cell. The basic photovoltaic device that generates branch-circuit conductors that supply an exterior luminaire
electricity when exposed to light. installed near a roof-mounted PV array to share the same
raceway or cable with the conductors of PV source circuits
Solar Photovoltaic System. The total components and or PV output circuits.
subsystems that, in combination, convert solar energy
+
+ –
**
+ – Batteries
PV
** modules
+ –
** –
+ –
**
+ – ** Overcurrent device may be required by UL 1703
**
Equipment grounding
Current-limiting fuse
+
box
– – – –
*
*
Ground-fault +
+
system
– – – –
–
Battery
Typical subarray 1 of 5 bank
Inverter with
battery
H charger
Fuel cell
N
120 Vac out
240/120 H
Wall
N
ac panelboard
(D) Equipment. Inverters, motor generators, photovoltaic such as beams, rafters, trusses, and columns where the loca-
modules, photovoltaic panels, ac photovoltaic modules, tion of those structural members can be determined by ob-
source-circuit combiners, and charge controllers intended servation. Where circuits are imbedded in built-up, laminate,
for use in photovoltaic power systems shall be identified and or membrane roofing materials in roof areas not covered by
listed for the application. PV modules and associated equipment, the location of cir-
cuits shall be clearly marked.
Control panel
PV modules
Charge
Grounding controller
electrode
dc loads
Fused
disconnect with
current-limiting
fuses
+ +
– – Batteries
+ +
– –
*
+ 240 V output
dc Utility
– ac required Residential ac
grounding disconnect disconnect
electrode panelboard
(located
+ conductor near meter)
(GEC)
ac
– 4– 28 PV dc Electrodes bonded grounding
modules grounding together or dc GEC electrode
+ connected electrode connected to ac conductor
in series grounding electrode (GEC)
– ac
grounding
electrode
+
Optional auxiliary
grounding electrode
cuits and with all dc source and dc output circuits isolated be permitted. If a grounded conductor is opened to interrupt
from buildings shall be permitted without ground-fault pro- the ground-fault current path, all conductors of the faulted
tection. circuit shall be automatically and simultaneously opened.
Manual operation of the main PV dc disconnect shall
Exception No. 2: Photovoltaic arrays installed at other
not activate the ground-fault protection device or result in
than dwelling units shall be permitted without ground-fault
grounded conductors becoming ungrounded.
protection if each equipment grounding conductor is sized
in accordance with 690.45.
Typical ground-fault protection devices meeting the require-
ments of 690.5(A) operate by opening the main dc bonding
Ground-fault detection and interruption for the direct- jumper. They sense dc ground faults anywhere on the dc sys-
current portions of PV systems should not be confused with tem and may be mounted anywhere in that system. They are
the requirements for alternating-current circuit GFCI protec- usually installed inside the utility-interactive inverters or in
tion, as defined in Article 100. A GFCI is intended for the the dc power center in stand-alone PV systems. Ground-fault
protection of personnel in single-phase ac systems. The ac protection accomplished through the opening of the grounded
GFCI functions to open the ungrounded conductor when a conductor also has to incorporate disconnecting means to au-
5-mA fault current is detected. In contrast, devices meeting tomatically open all conductors of the faulted circuit.
the requirements of 690.5 are intended to prevent fires in dc
PV circuits due to ground faults.
(B) Isolating Faulted Circuits. The faulted circuits shall
be isolated by one of the two following methods:
(A) Ground-Fault Detection and Interruption. The
ground-fault protection device or system shall be capable of (1) The ungrounded conductors of the faulted circuit shall
detecting a ground-fault current, interrupting the flow of be automatically disconnected.
fault current, and providing an indication of the fault. (2) The inverter or charge controller fed by the faulted cir-
Automatically opening the grounded conductor of the cuit shall automatically cease to supply power to output
faulted circuit to interrupt the ground-fault current path shall circuits.
Typical ground-fault protection devices operating in PV sys- moves the external source and turns off all ac PV modules
tems (48-volt nominal and below) automatically disconnect connected to that disconnecting device.
the ungrounded conductor with a circuit breaker mechani-
cally linked to a ground-fault-sensing circuit breaker. Equip-
ment operating above 48 volts nominal usually automatically (D) Ground-Fault Detection. Alternating-current module
shuts off the connected equipment to meet this requirement systems shall be permitted to use a single detection device to
when a ground fault is sensed. detect only ac ground faults and to disable the array by re-
moving ac power to the ac module(s).
under controlled laboratory conditions and the open-circuit TABLE 690.7 Voltage Correction Factors for Crystalline
and Multicrystalline Silicon Modules
voltage under field-installed conditions can be significant.
Consequently, the higher-rated open-circuit voltage must Correction Factors for Ambient Temperatures Below 25°C
be used to select circuit components with proper voltage (77°F). (Multiply the rated open circuit voltage by the
ratings. appropriate correction factor shown below.)
The voltage potential (both open circuit and operating)
of a PV power source increases with decreasing tempera- Ambient Ambient
Temperature (°C) Factor Temperature (°F)
ture. The installer should note the temperature conditions
under which the PV device was rated. If the anticipated low- 24 to 20 1.02 76 to 68
est temperature at the installation site is lower than the rating 19 to 15 1.04 67 to 59
condition (25°C), Table 690.7 should be used to adjust the 14 to 10 1.06 58 to 50
maximum open-circuit voltage of the crystalline system be- 9 to 5 1.08 49 to 41
fore conductors, overcurrent devices, and switchgear are se- 4 to 0 1.10 40 to 32
lected. 21 to 25 1.12 31 to 23
The temperature adjustment requirement is also in- 26 to 210 1.14 22 to 14
cluded in the instructions provided with listed PV modules 211 to 215 1.16 13 to 5
and is established at a fixed 125 percent, regardless of tem- 216 to 220 1.18 4 to 24
221 to 225 1.20 25 to 213
perature. Table 690.7 supersedes the fixed 125 percent
226 to 230 1.21 214 to 222
where the lowest temperature is above 240°C.
231 to 235 1.23 223 to 231
Where a listed PV module includes open-circuit voltage 236 to 240 1.25 232 to 240
temperature coefficients in the installation instructions,
these temperature coefficients provide a more accurate max-
imum system voltage and are required to be used instead of
applying Table 690.7. The NEC does not require tempera- maximum photovoltaic system voltage up to 600 volts.
ture coefficient information to be included in the installation Other installations with a maximum photovoltaic system
instructions. voltage over 600 volts shall comply with Article 690, Part
Bipolar PV systems (with positive and negative volt- IX.
ages) must use the sum of the absolute values of the open-
circuit voltages to determine the rated open-circuit system
A significant difference exists between the rated open-circuit
voltage. For example, a system with open-circuit voltages of
voltage and the operating voltage in PV dc circuits. For the
1480 volts and 2480 volts with respect to ground would
PV system to perform its intended function, rated dc open-
have a system open-circuit voltage of 960 volts. This voltage
circuit voltages of up to 600 volts may be present.
should be multiplied by a temperature-dependent factor
from Table 690.7, yielding a system design voltage of up to
1200 volts. The system design voltage should be used in the (D) Circuits over 150 Volts to Ground. In one- and two-
selection of cables and other equipment. Also, see the defini- family dwellings, live parts in photovoltaic source circuits
tion of photovoltaic system voltage in 690.2. Certain meth- and photovoltaic output circuits over 150 volts to ground
ods of connecting bipolar PV arrays meeting the shall not be accessible to other than qualified persons while
requirements of 690.7(E) may have different requirements energized.
for calculating the maximum system voltage.
Informational Note: See 110.27 for guarding of live parts,
and 210.6 for voltage to ground and between conductors.
(B) Direct-Current Utilization Circuits. The voltage of
dc utilization circuits shall conform to 210.6. Where dc circuitry over 150 volts to ground is present in
one- and two-family dwellings, additional protection for un-
qualified persons may be needed. Protection may be in the
The requirements of 690.7(B) cover installations where the form of conduit, a closed cabinet, or an enclosure that re-
PV output is connected to dc utilization circuits. quires the use of tools to open it and that permits entry only
by qualified persons.
(C) Photovoltaic Source and Output Circuits. In one-
and two-family dwellings, photovoltaic source circuits and (E) Bipolar Source and Output Circuits. For 2-wire cir-
photovoltaic output circuits that do not include lamphold- cuits connected to bipolar systems, the maximum system
ers, fixtures, or receptacles shall be permitted to have a voltage shall be the highest voltage between the conductors
of the 2-wire circuit if all of the following conditions (3) Inverter Output Circuit Current. The maximum cur-
apply: rent shall be the inverter continuous output current rating.
(1) One conductor of each circuit of a bipolar subarray is
solidly grounded. Both stand-alone and utility-interactive inverters are power-
limited devices. Output circuits connected to these devices are
Exception: The operation of ground-fault or arc-fault de- sized on the continuous rated outputs of these devices and are
vices (abnormal operation) shall be permitted to interrupt not based on load calculations or reduced-size PV arrays or
this connection to ground when the entire bipolar array be- battery banks, if any. Some inverters may have specifications
comes two distinct arrays isolated from each other and the listing sustained maximum output currents, and the higher of
utilization equipment. this number or the rated output should be used.
The exception to 690.8(B)(1)(a) permits use at the full rating 690.9 Overcurrent Protection
of assemblies, such as panelboards, incorporating overcur- (A) Circuits and Equipment. Photovoltaic source circuit,
rent devices listed for continuous operation at 100 percent of photovoltaic output circuit, inverter output circuit, and stor-
the rating. age battery circuit conductors and equipment shall be pro-
tected in accordance with the requirements of Article 240.
Circuits connected to more than one electrical source shall
(b) Terminal temperature limits shall be in accordance have overcurrent devices located so as to provide overcur-
with 110.3(B) and 110.14(C). rent protection from all sources.
(c) Where operated at temperatures greater than 40°C
(104°F), the manufacturer’s temperature correction factors Exception: An overcurrent device shall not be required for
shall apply. PV modules or PV source circuit conductors sized in accor-
(d) The rating or setting of overcurrent devices shall be dance with 690.8(B) where one of the following applies:
permitted in accordance with 240.4(B), (C), and (D). (a) There are no external sources such as parallel-con-
nected source circuits, batteries, or backfeed from in-
verters.
(2) Conductor Ampacity. Circuit conductors shall be sized
(b) The short-circuit currents from all sources do not ex-
to carry not less than the larger of 690.8(B)(2)(a) or (2)(b).
ceed the ampacity of the conductors or the maximum
overcurrent protective device size specified on the PV
(a) One hundred and twenty-five percent of the maxi-
module nameplate.
mum currents calculated in 690.8(A) without any additional
correction factors for conditions of use. Informational Note: Possible backfeed of current from any
(b) The maximum currents calculated in 690.8(A) after source of supply, including a supply through an inverter into
conditions of use have been applied. the photovoltaic output circuit and photovoltaic source cir-
cuits, is a consideration in determining whether adequate
(c) The conductor selected, after application of condi- overcurrent protection from all sources is provided for con-
tions of use, shall be protected by the overcurrent protective ductors and modules.
device, where required.
(C) Systems with Multiple Direct-Current Voltages. For In the circuits illustrated in Exhibits 690.3, 690.4, 690.5, and
a photovoltaic power source that has multiple output circuit 690.6, the PV source-circuit overcurrent devices are required
voltages and employs a common-return conductor, the am- to be rated so that the source-circuit conductors are pro-
pacity of the common-return conductor shall not be less than tected in accordance with Article 240 and so that the over-
the sum of the ampere ratings of the overcurrent devices of current device ratings do not exceed the maximum
the individual output circuits. overcurrent device rating marked on the modules. Possible
backfeed currents from the other PV source circuits, other
(D) Sizing of Module Interconnection Conductors. supply sources through the inverter, and storage-battery cir-
Where a single overcurrent device is used to protect a set of cuits, if any, have to be considered.
two or more parallel-connected module circuits, the ampac- Blocking diodes (possibly required by the module man-
ity of each of the module interconnection conductors shall ufacturer for specific applications) can lose their blocking
not be less than the sum of the rating of the single fuse plus ability because of overtemperature conditions or internal
125 percent of the short-circuit current from the other breakdown. Therefore, overcurrent protection has to be con-
parallel-connected modules. sidered with a condition of shorted blocking diodes if they
are used in the circuit.
In typical one- and two-family dwelling unit utility-
Normally, labeling or module instructions require reverse interactive PV systems, overcurrent devices may only be re-
overcurrent protection for each module or string of modules. quired in the dc PV source or output circuits where there are
In some cases, modules with low-rated short-circuit currents more than two strings of PC modules connected in parallel.
and high values of the required series protective fuse may At the inverter or battery/charge controller end of the
allow the use of one overcurrent device to provide reverse- PV output circuit, the need for overcurrent protection has to
be considered with respect to the maximum backfeed fault Direct-current fault currents are considerably harder to inter-
current available from other sources. rupt than ac faults. Overcurrent devices marked or listed
only for ac use should not be used in dc circuits. Automo-
tive- and marine-type fuses, although used in these dc sys-
(B) Power Transformers. Overcurrent protection for a
tems, are not suitable for use in permanently wired
transformer with a source(s) on each side shall be provided
residential or commercial electrical power systems meeting
in accordance with 450.3 by considering first one side of the
the requirements of the Code.
transformer, then the other side of the transformer, as the
primary.
(E) Series Overcurrent Protection. In PV source circuits,
Exception: A power transformer with a current rating on a single overcurrent protection device shall be permitted to
the side connected toward the utility-interactive inverter protect the PV modules and the interconnecting conductors.
output, not less than the rated continuous output current of
the inverter, shall be permitted without overcurrent protec-
tion from the inverter. The single overcurrent device (when required) may provide
both the reverse-current protection required for the series-
(C) Photovoltaic Source Circuits. Branch-circuit or connected PV modules and the overcurrent protection re-
supplementary-type overcurrent devices shall be permitted quired for the interconnecting conductors.
to provide overcurrent protection in photovoltaic source cir-
cuits. The overcurrent devices shall be accessible but shall
not be required to be readily accessible.
690.10 Stand-Alone Systems
Standard values of supplementary overcurrent devices The premises wiring system shall be adequate to meet the
allowed by this section shall be in one ampere size incre- requirements of this Code for a similar installation con-
ments, starting at one ampere up to and including 15 am- nected to a service. The wiring on the supply side of the
peres. Higher standard values above 15 amperes for building or structure disconnecting means shall comply with
supplementary overcurrent devices shall be based on the this Code except as modified by 690.10(A) through (E).
standard sizes provided in 240.6(A).
(A) Inverter Output. The ac output from a stand-alone
inverter(s) shall be permitted to supply ac power to the
If the overcurrent protection of PV source circuits is con- building or structure disconnecting means at current levels
sidered supplementary overcurrent protection, use of over- less than the calculated load connected to that disconnect.
current devices with ratings other than those suitable for The inverter output rating or the rating of an alternate energy
branch-circuit protection is permitted. The use of such de- source shall be equal to or greater than the load posed by the
vices permits module protection closer to the specified rat- largest single utilization equipment connected to the system.
ings required on the labels attached to listed modules. It is Calculated general lighting loads shall not be considered as
anticipated that only qualified service personnel will re- a single load.
place or reset overcurrent devices in PV source circuits.
Consequently, ready access to the user need not be pro-
vided. These supplementary overcurrent devices must be A stand-alone residential or commercial PV installation may
listed for dc operation and have appropriate voltage and have an ac output and be connected to a building wired in
current ratings. full compliance with all articles of this Code. Even though
Overcurrent devices used to protect modules or module such an installation may have service-entrance equipment
interconnections may be installed in enclosures mounted rated at 100 or 200 amperes at 120/240 volts, the PV source
outdoors in locations exposed to direct sunlight that may is not required to provide either the full current rating or the
subject the overcurrent devices to operating temperatures dual voltages of the service equipment. While safety re-
higher than 40°C. Appropriate derating instructions are quirements dictate full compliance with the ac wiring sec-
available from the overcurrent device manufacturer. tions of the Code, a PV installation is usually designed so
that the actual ac demands on the system are sized to the
output rating of the PV system. The inverter output is re-
(D) Direct-Current Rating. Overcurrent devices, either quired by 690.10(A) to have sufficient capacity to power the
fuses or circuit breakers, used in any dc portion of a photo- largest single piece of utilization equipment to be supplied
voltaic power system shall be listed for use in dc circuits and by the PV system, but the inverter output does not have to be
shall have the appropriate voltage, current, and interrupt rat- sized for the potential multiple loads to be simultaneously
ings.
switches or six circuit breakers mounted in a single enclosure, ungrounded conductors of all sources. If the equipment is
in a group of separate enclosures, or in or on a switchboard. energized from more than one source, the disconnecting
means shall be grouped and identified.
(5) Grouping. The photovoltaic system disconnecting A single disconnecting means in accordance with
means shall be grouped with other disconnecting means for 690.17 shall be permitted for the combined ac output of
the system to comply with 690.14(C)(4). A photovoltaic dis- one or more inverters or ac modules in an interactive sys-
connecting means shall not be required at the photovoltaic tem.
module or array location.
690.16 Fuses
Where a building has multiples sources of power, such as the
Switches, pullouts, or similar devices that have suitable rat-
utility, the PV array, backup generator, and wind system, no
ings may serve as means to disconnect fuses from all sources
more than six disconnects for each source of power to the
of supply.
building, are allowed, and the disconnects for each source
are required to be grouped together. However, a PV system
may be considered a source of supply separate from a utility
(A) Disconnecting Means. Disconnecting means shall be
source under certain conditions (see 230.2), and each source
provided to disconnect a fuse from all sources of supply if
may have up to six grouped disconnecting means as permit- the fuse is energized from both directions. Such a fuse in a
ted by 230.72. photovoltaic source circuit shall be capable of being discon-
nected independently of fuses in other photovoltaic source
(D) Utility-Interactive Inverters Mounted in Not-Readily- circuits.
Accessible Locations. Utility-interactive inverters shall be
permitted to be mounted on roofs or other exterior areas that (B) Fuse Servicing. Disconnecting means shall be in-
are not readily accessible. These installations shall comply stalled on PV output circuits where overcurrent devices
with (1) through (4): (fuses) must be serviced that cannot be isolated from ener-
gized circuits. The disconnecting means shall be within sight
(1) A direct-current photovoltaic disconnecting means shall of, and accessible to, the location of the fuse or integral with
be mounted within sight of or in the inverter. fuse holder and shall comply with 690.17. Where the dis-
(2) An alternating-current disconnecting means shall be connecting means are located more than 1.8 m (6 ft) from
mounted within sight of or in the inverter. the overcurrent device, a directory showing the location of
each disconnect shall be installed at the overcurrent device
This section permits the utility-interactive inverter to be in- location.
stalled in a location that is not readily accessible, so the re- Non-load-break-rated disconnecting means shall be
quirements in 690.14(D)(1) and (D)(2) provide for dc and ac marked “Do not open under load.”
disconnecting means at the inverter location to facilitate ser-
vicing of the inverter. 690.17 Switch or Circuit Breaker
The disconnecting means for ungrounded conductors shall
consist of a manually operable switch(es) or circuit
(3) The alternating-current output conductors from the in-
breaker(s) complying with all of the following requirements:
verter and an additional alternating-current disconnecting
means for the inverter shall comply with 690.14(C)(1). (1) Located where readily accessible
(2) Externally operable without exposing the operator to
contact with live parts
The disconnect required by 690.14(C)(1) allows the
(3) Plainly indicating whether in the open or closed posi-
inverter(s) and the circuit to it (them) to be de-energized tion
from a readily accessible location.
(4) Having an interrupting rating sufficient for the nominal
circuit voltage and the current that is available at the
(4) A plaque shall be installed in accordance with 705.10. line terminals of the equipment
The use of metallic raceways, Type MC metal-clad cable, or (1) Exposed raceways, cable trays, and other wiring methods
metal enclosures inside a building provides additional physi- (2) Covers or enclosures of pull boxes and junction boxes
cal protection for these circuits. Metallic raceways also pro- (3) Conduit bodies in which any of the available conduit
openings are unused
(4) Marking and Labeling Methods and Locations. The (B) Guarding. The connectors shall be constructed and in-
labels or markings shall be visible after installation. Photo- stalled so as to guard against inadvertent contact with live
voltaic power circuit labels shall appear on every section of parts by persons.
the wiring system that is separated by enclosures, walls, par-
titions, ceilings, or floors. Spacing between labels or mark- (C) Type. The connectors shall be of the latching or lock-
ings, or between a label and a marking, shall not be more ing type. Connectors that are readily accessible and that are
than 3 m (10 ft). Labels required by this section shall be suit- used in circuits operating at over 30 volts, nominal, maxi-
able for the environment where they are installed. mum system voltage for dc circuits, or 30 volts for ac cir-
cuits, shall require a tool for opening.
The objective of the requirements contained in 690.31(E)(1) (D) Grounding Member. The grounding member shall be
through (4) is to protect persons from inadvertently damag- the first to make and the last to break contact with the mat-
ing PV source and output circuit conductors. Where the lo- ing connector.
cation of the PV circuit conductors is not obvious, fire
fighters, other first responders, and maintenance personnel (E) Interruption of Circuit. Connectors shall be either (1)
could be exposed to shock hazards. Ventilating roofs con- or (2):
taining PV source or output circuits by cutting the mem-
(1) Be rated for interrupting current without hazard to the
brane with saws exposes personnel to shock hazards and the
operator.
building to further damage resulting from the ignition of
(2) Be a type that requires the use of a tool to open and
combustible members due to arcing from damaged conduc-
marked “Do Not Disconnect Under Load” or “Not for
tors.
Current Interrupting.”
(F) Flexible, Fine-Stranded Cables. Flexible, fine- The two options provided for connectors in this requirement
stranded cables shall be terminated only with terminals, provide for safe disconnection of circuit connectors either
lugs, devices, or connectors in accordance with 110.14(A). by being able to be opened under load or by having a warn-
ing indicating that disconnection prior to opening the con-
nector is necessary. Connectors that can be opened or
Flexible, fine-stranded cables recognized in Table disconnected using only the hands are not acceptable.
310.104(A) have numerous, very fine strands and can be
used only with specially tested, listed, and identified termi-
nations. The terminals, connectors, and crimp-on lugs found 690.34 Access to Boxes
on most electrical equipment used in PV systems are not Junction, pull, and outlet boxes located behind modules or
suitable for use with these types of cables. The requirements panels shall be so installed that the wiring contained in them
for these fine-stranded conductors are covered in 110.14. can be rendered accessible directly or by displacement of a
module(s) or panel(s) secured by removable fasteners and
connected by a flexible wiring system.
690.32 Component Interconnections
Fittings and connectors that are intended to be concealed at 690.35 Ungrounded Photovoltaic Power
the time of on-site assembly, where listed for such use, shall Systems
be permitted for on-site interconnection of modules or other Photovoltaic power systems shall be permitted to operate
array components. Such fittings and connectors shall be with ungrounded photovoltaic source and output circuits
equal to the wiring method employed in insulation, tempera- where the system complies with 690.35(A) through (G).
ture rise, and fault-current withstand, and shall be capable of
resisting the effects of the environment in which they are (A) Disconnects. All photovoltaic source and output cir-
used. cuit conductors shall have disconnects complying with 690,
Part III.
690.33 Connectors
The connectors permitted by Article 690 shall comply with (B) Overcurrent Protection. All photovoltaic source and
690.33(A) through (E). output circuit conductors shall have overcurrent protection
complying with 690.9.
(A) Configuration. The connectors shall be polarized and
shall have a configuration that is noninterchangeable with (C) Ground-Fault Protection. All photovoltaic source
receptacles in other electrical systems on the premises. and output circuits shall be provided with a ground-
tion for equipment grounding conductors in photovoltaic Informational Note No. 2: For utility-interactive systems,
systems that are not provided with ground-fault protection is the existing premises grounding system serves as the ac
related to size and withstand capability of the equipment grounding system.
grounding conductor, rather than overcurrent device opera-
tion. (1) Separate Direct-Current Grounding Electrode Sys-
tem Bonded to the Alternating-Current Grounding Elec-
690.46 Array Equipment Grounding trode System. A separate dc grounding electrode or system
Conductors shall be installed, and it shall be bonded directly to the ac
Equipment grounding conductors for photovoltaic modules grounding electrode system. The size of any bonding
smaller than 6 AWG shall comply with 250.120(C). jumper(s) between the ac and dc systems shall be based on
the larger size of the existing ac grounding electrode con-
690.47 Grounding Electrode System ductor or the size of the dc grounding electrode conductor
specified by 250.166. The dc grounding electrode system
(A) Alternating-Current Systems. If installing an ac sys- conductor(s) or the bonding jumpers to the ac grounding
tem, a grounding electrode system shall be provided in ac- electrode system shall not be used as a substitute for any re-
cordance with 250.50 through 250.60. The grounding quired ac equipment grounding conductors.
electrode conductor shall be installed in accordance with
250.64. (2) Common Direct-Current and Alternating-Current
Grounding Electrode. A dc grounding electrode conductor
(B) Direct-Current Systems. If installing a dc system, a of the size specified by 250.166 shall be run from the marked
grounding electrode system shall be provided in accordance dc grounding electrode connection point to the ac grounding
with 250.166 for grounded systems or 250.169 for un- electrode. Where an ac grounding electrode is not accessi-
grounded systems. The grounding electrode conductor shall ble, the dc grounding electrode conductor shall be connected
be installed in accordance with 250.64. to the ac grounding electrode conductor in accordance with
A common dc grounding-electrode conductor shall be 250.64(C)(1). This dc grounding electrode conductor shall
permitted to serve multiple inverters. The size of the com- not be used as a substitute for any required ac equipment
mon grounding electrode and the tap conductors shall be in grounding conductors.
accordance with 250.166. The tap conductors shall be con-
nected to the common grounding-electrode conductor by (3) Combined Direct-Current Grounding Electrode
exothermic welding or with connectors listed as grounding Conductor and Alternating-Current Equipment
and bonding equipment in such a manner that the common Grounding Conductor. An unspliced, or irreversibly
grounding electrode conductor remains without a splice or spliced, combined grounding conductor shall be run from
joint. the marked dc grounding electrode conductor connection
point along with the ac circuit conductors to the grounding
(C) Systems with Alternating-Current and Direct-Cur- busbar in the associated ac equipment. This combined
rent Grounding Requirements. Photovoltaic systems hav- grounding conductor shall be the larger of the sizes specified
ing dc circuits and ac circuits with no direct connection by 250.122 or 250.166 and shall be installed in accordance
between the dc grounded conductor and ac grounded con- with 250.64(E).
ductor shall have a dc grounding system. The dc grounding
system shall be bonded to the ac grounding system by one of
the methods in (1), (2), or (3). Inverters used in PV power systems usually contain a trans-
This section shall not apply to ac PV modules. former that isolates the dc grounded circuit conductor from
When using the methods of (C)(2) or (C)(3), the exist- the ac grounded circuit conductor. Isolation necessitates that
ing ac grounding electrode system shall meet the applicable both a dc and an ac grounding system be installed. The two
requirements of Article 250, Part III. grounding systems are to be bonded together or have a com-
Informational Note No. 1: ANSI/UL 1741, Standard for In-
mon grounding electrode so that all ac and dc grounded cir-
verters, Converters, and Controllers for Use in Independent cuit conductors and equipment grounding conductors have
Power Systems, requires that any inverter or charge control- the same near-zero potential to earth.
ler that has a bonding jumper between the grounded dc con- The combined dc equipment grounding, dc system
ductor and the grounding system connection point have that grounding, and ac equipment grounding required by this
point marked as a grounding electrode conductor (GEC)
connection point. In PV inverters, the terminals for the dc section establishes only one grounding circuit and connec-
equipment grounding conductors and the terminals for ac tion for the entire PV system from the PV array to the ac
equipment grounding conductors are generally connected point of connection. Under PV dc ground-fault conditions,
to, or electrically in common with, a grounding busbar that an interruption of this single circuit may allow exposed
has a marked dc GEC terminal.
contact by persons or objects, regardless of voltage or bat- tery electrical system for maintenance. This disconnecting
tery type. means shall not disconnect the grounded circuit conductor(s)
for the remainder of the photovoltaic electrical system. A
Informational Note: Batteries in solar photovoltaic systems
are subject to extensive charge–discharge cycles and typi- non–load-break-rated switch shall be permitted to be used as
cally require frequent maintenance, such as checking elec- the disconnecting means.
trolyte and cleaning connections.
(G) Battery Systems of More Than 48 Volts. On photo-
voltaic systems where the battery system consists of more
At any voltage, a primary safety concern in battery systems than twenty-four 2-volt cells connected in series (more than
is that a fault (e.g., a metal tool dropped onto a terminal) 48 volts, nominal), the battery system shall be permitted to
might cause a fire or an explosion. Guarded, as defined in operate with ungrounded conductors, provided the following
Article 100, describes the best method to reduce this hazard. conditions are met:
(1) The photovoltaic array source and output circuits shall
(C) Current Limiting. A listed, current-limiting, overcur- comply with 690.41.
rent device shall be installed in each circuit adjacent to the (2) The dc and ac load circuits shall be solidly grounded.
batteries where the available short-circuit current from a bat- (3) All main ungrounded battery input/output circuit con-
tery or battery bank exceeds the interrupting or withstand ductors shall be provided with switched disconnects
ratings of other equipment in that circuit. The installation of and overcurrent protection.
current-limiting fuses shall comply with 690.16. (4) A ground-fault detector and indicator shall be installed
to monitor for ground faults in the battery bank.
(D) Battery Nonconductive Cases and Conductive
Racks. Flooded, vented, lead-acid batteries with more than 690.72 Charge Control
twenty-four 2-volt cells connected in series (48 volts, nomi- (A) General. Equipment shall be provided to control the
nal) shall not use conductive cases or shall not be installed in charging process of the battery. Charge control shall not be
conductive cases. Conductive racks used to support the non- required where the design of the photovoltaic source circuit
conductive cases shall be permitted where no rack material is matched to the voltage rating and charge current require-
is located within 150 mm (6 in.) of the tops of the noncon- ments of the interconnected battery cells and the maximum
ductive cases. charging current multiplied by 1 hour is less than 3 percent
This requirement shall not apply to any type of valve- of the rated battery capacity expressed in ampere-hours or as
regulated lead-acid (VRLA) battery or any other types of recommended by the battery manufacturer.
sealed batteries that may require steel cases for proper op- All adjusting means for control of the charging process
eration. shall be accessible only to qualified persons.
Informational Note: Certain battery types such as valve-
regulated lead acid or nickel cadmium can experience ther-
Grounded metal trays and cases or containers (as normally mal failure when overcharged.
required by 250.110) in flooded, lead-acid battery systems
operating over 48 volts, nominal, have been shown to be a (B) Diversion Charge Controller.
contributing factor in ground faults. Nonconductive racks,
(1) Sole Means of Regulating Charging. A photovoltaic
trays, and cases minimize this problem.
power system employing a diversion charge controller as the
sole means of regulating the charging of a battery shall be
equipped with a second independent means to prevent over-
(E) Disconnection of Series Battery Circuits. Battery cir-
charging of the battery.
cuits subject to field servicing, where more than twenty-four
2-volt cells are connected in series (48 volts, nominal), shall
(2) Circuits with Direct-Current Diversion Charge Con-
have provisions to disconnect the series-connected strings
troller and Diversion Load. Circuits containing a dc diver-
into segments of 24 cells or less for maintenance by quali-
sion charge controller and a dc diversion load shall comply
fied persons. Non–load-break bolted or plug-in disconnects
with the following:
shall be permitted.
(1) The current rating of the diversion load shall be less than
(F) Battery Maintenance Disconnecting Means. Battery or equal to the current rating of the diversion load charge
installations, where there are more than twenty-four 2-volt controller. The voltage rating of the diversion load shall
cells connected in series (48 volts, nominal), shall have a be greater than the maximum battery voltage. The power
disconnecting means, accessible only to qualified persons, rating of the diversion load shall be at least 150 percent of
that disconnects the grounded circuit conductor(s) in the bat- the power rating of the photovoltaic array.