You are on page 1of 11

General information

Station CB2 Voltage U0 20,00 kV

Number Location HVS00

Switchgeartype Customer

Manufacturer SCHNEIDER Installationyear

Inspector ANDIKA DWI MAIYUDHA Measuredate 21/02/2023

Deviceinformation

Megger PD scan 14382980014 Version 1.2.19 Calibrationdate 25/03/2022

Recommendation

Ambient information

Temperature 28,00 °C Humidity 79,00 %

Ground noise
Level Pulse per cycle

Internal 0 dBµV 0 ppc

Date Signature

1/11
Plugin Version 1.0
Measurement data

Testobject Description DEPAN BAWAH

Termination Cable

Measurements Results Ground noise


Level Pulse per cycle Level Pulse per cycle

MAX 4 dB 0 ppc - dB - ppc


TEV AVG 4 dB 0 ppc - dB - ppc

Evaluation Criticality Criteria


Good Moderate Bad

TEV 0 <=5 6-19 >=20

Recommendation

2/11
Plugin Version 1.0
Graphs and pictures

TEV Histogram

TEV PRPD

3/11
Plugin Version 1.0
Measurement data

Testobject Description DEPAN TENGAH

Termination Cable

Measurements Results Ground noise


Level Pulse per cycle Level Pulse per cycle

MAX 5 dB 0 ppc - dB - ppc


TEV AVG 5 dB 0 ppc - dB - ppc

Evaluation Criticality Criteria


Good Moderate Bad

TEV 0 <=5 6-19 >=20

Recommendation

4/11
Plugin Version 1.0
Graphs and pictures

TEV Histogram

TEV PRPD

5/11
Plugin Version 1.0
Measurement data

Testobject Description BELAKANG BAWAH

Termination Cable

Measurements Results Ground noise


Level Pulse per cycle Level Pulse per cycle

MAX 5 dB 0 ppc - dB - ppc


TEV AVG 5 dB 0 ppc - dB - ppc

Evaluation Criticality Criteria


Good Moderate Bad

TEV 0 <=5 6-19 >=20

Recommendation

6/11
Plugin Version 1.0
Graphs and pictures

TEV Histogram

TEV PRPD

7/11
Plugin Version 1.0
Measurement data

Testobject Description BELAKANG TENGAH

Termination Cable

Measurements Results Ground noise


Level Pulse per cycle Level Pulse per cycle

MAX 5 dB 0 ppc - dB - ppc


TEV AVG 5 dB 0 ppc - dB - ppc

Evaluation Criticality Criteria


Good Moderate Bad

TEV 0 <=5 6-19 >=20

Recommendation

8/11
Plugin Version 1.0
Graphs and pictures

TEV Histogram

TEV PRPD

9/11
Plugin Version 1.0
Measurement data

Testobject Description BELAKANG ATAS

Termination Cable

Measurements Results Ground noise


Level Pulse per cycle Level Pulse per cycle

MAX 5 dB 0 ppc - dB - ppc


TEV AVG 4 dB 0 ppc - dB - ppc

Evaluation Criticality Criteria


Good Moderate Bad

TEV 0 <=5 6-19 >=20

Recommendation

10/11
Plugin Version 1.0
Graphs and pictures

TEV Histogram

TEV PRPD

11/11
Plugin Version 1.0

You might also like