DTG1125C
GENERATOR SPECIALISTS
CIRCUIT BREAKER
Set mounted 3-pole fixed output breaker, rated to maximum
output of generator set
Manufacturer: ABB OR SCHNEIDER
Rating: 2000 Amp
ALTERNATOR DIMENSIONS
Make: Stamford Length: 4478 mm
Model: TBA Width: 1682 mm
Insulation Class: Class H Height: 2211 mm
Ingress Protection: IP23 Wet Weight: 8,,822 kg
No. of Poles: 4
No. of Bearings: 2
Voltage Regulation: ± 0.25 %
GENERATING SET STANDARDS load with diesel fuel with specific gravity of 0.85 and conforming to
BS2869: 1998, Class A2, EN590.
The equipment meets the following standards: BS5000, All data provided subject to manufacturing tolerances.
ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22.
Skid mounted generator set with 1500 RPM industrial water
cooled diesel engine, brushless self-regulating alternator, POWER RATINGS
set mounted control panel (2 wire start), 24 Volt heavy duty lead
acid staring batteries, battery leads, starter motor, charge alternator, ESP - Emergency Standby to ISO 8528. limited to 200 hours per
anti-vibration mountings, 3 pole fixed type circuit breaker. Generators annum, 70% average load.
configuration includes a self-regulating battery charger and a PRP - Prime Rated Power to ISO8528, unlimited hours , 70% average load.
thermostatically controlled engine water jacket heater (Both DCC - Data Centre Continuous , unlimited hours, 100% load. Strictly for
require a separate single phase auxiliary supply). DC application only.
Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m Ratings based on ambient temperature 35 DegC / NTP Conditions.
(328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full For kW ratings apply a multiplication factor of 0.8 to the kVA rating.