WATER ANALYSIS REPORT

Client / Site: Mr. Samy Khalid Alamer


Sampling Date: 25-Jan-23 Company Nalco Middle East FZE
Sample: COOLING TOWER CHILLED WARTER POTABLE WATER Office Jebel Ali - Dubai - UAE
Attention To: Mr. Samy Khalid Alamer Telephone No./ 00971 (0) 8146800 / 00971 (0) 8146801
Address: Abu-Fatira, Block 6, St.181, home 174 Contact Ahmed Awad → Mobile No.: 96713117

A - SUMMARY OF FINDINGS & RECOMMENDATION


MAKE-UP WATER
Make up water is Ministry water
CHILLED WATER
Findings : Recommendations:
Flushing and passivation - The sytem is fulshed and cleaned with fresh water and passivated with Nalprep
- water system quality is accepted for permanent treatment by adding the corrosion
inhibitor as per recommended dosage and maitian water circulation.
- After circulation water sample is required for measure the nitrite level.
CHEMICAL DOSAGE
Chemical Name Stock Level Dosage Note
TRAC 109 25 Kg as needed as per Nitrite level 4kg/1 m3 of water

B - ANALYSIS RESULT
PARAMETERS pH Conductivity TDS M- Ca Chlorides Iron Trac109 TSS Turbidity
Alkalinity Hardness
No. SAMPLE/ SOURCE µS/cm ppm ppm as ppm as ppm as CI ppm as ppm as ppm FAU
CaCO3 CaCO3 Fe NaNO2
1 Potable Water 7.53 230 114.9 42 46 51 0.05 0.03 0.9
Target 7-7.9 <290 < 150 < 60 <55 <100 < 0.2 Nil <0.5 <2
2
2 Target
Chilled Water 87.61
-8.5 < 242
1200 < 113
1000 < 43
175 <200
47 < 57
400 <2
0.37 0 <1.46
10 <3.00
20
Target 8.5- 10.5 1600-2000 < 900 < 175 <200 < 500 <2 700-1300 <3 <5
C REPORT PREPARED BY:
NAME: Ahmed Awad COMPANY: Nalco Middle East Co.