You are on page 1of 3

Safety and Distributed Control

PAC8000 Process Controllers


PAC8000 delivers full-specification performance in a broad range of harsh process environment conditions; extreme
temperatures, humidity or corrosives and conditions subject to shock and vibration. In ATEX environments, PAC8000 also excels. All
components can be installed and maintained in Zone 2/Division 2 hazardous areas. The I/O includes modules that can be connected
directly to Intrinsically Safe (Exi) or Increased Safety (Exe) field wiring. PAC8000 provides comprehensive diagnostic data on
controllers, Bus Interface Modules (BIM), I/O modules, field wiring and field instruments, allowing users to respond to issues quickly
and effectively.
PAC8000 Controllers are used in conventional distributed control architectures, with the I/O modules connected directly to the
Controllers. The same I/O modules may be used in remote IO architectures.

Benefits of PAC8000 • I/O Modules • Environmental and Hazardous


Controllers A broad range of PAC8000 I/O Area Operation
• Controller Options modules are available to meet the PAC8000 can go where other
needs of different applications. All products cannot. They can be field
PAC8000 Controllers include a Process
modules provide comprehensive mounted and will operate under the
Controller featuring DCS style function
diagnostic information. Analog and following conditions:
block programming, a Logic Controller
discrete output modules are typically • -40°C to +70°C operating range
with 61131-style PLC programming,
8-channel, with 8-, 16- or 32-channel
and a Hybrid Controller that provides • ISA Level G3 corrosive atmospheres
discrete input modules. Up to 64
the capabilities of both. An RTU
modules can be mounted on each node. • 30g shock and 5g vibration
Controller is also available, providing
DNP3 communication. The SIL 2 • Class I, Division 2 and Zone 2
SafetyNet Controller is also part of the hazardous areas, with I/O field
PAC8000 family. wiring including intrinsically safe (Exi)
and increased safety (Exe) options.
continued next page

5.26 Automation & Control Systems www.geautomation.com


Safety and Distributed Control PAC8000 SafetyNet

• Controller Redundancy • Ease of Use • Power Supplies


Application availability is improved A range of features are provided to 12 V controller power must be
with Controller redundancy, which is simplify the day-to-day operation of a connected to each controller, in
implemented by simply mounting a Process Automation System: addition to the 12 V system power
second controller on the carrier. No – Controllers feature numerous LEDs connected to the controller carrier.
configuration is required; the new to assist with fault finding. This can be supplied by the AC power
controller automatically becomes supply, 8913-PS-AC, or the DC power
the standby when a button on – Controllers report failed power supply, BQ2320-9R-EX.
the Controller Carrier is pressed. supplies when used in conjunction
Rendezvous redundancy is employed to with PAC8000 AC power supplies
guarantee bump-less transfer of control and the 8410-NS-PS nodes
from the master to the standby. services module.

• Network Redundancy – On replacing an IO module, the


Controller will automatically bring
Network redundancy helps assure it online if it recognizes the type as
uninterrupted communications. being correct.
PAC8000 Controllers each have
two fault-tolerant Ethernet ports to – Online download of new application
provide redundant communication programs is possible with simplex
LANs. If a fault occurs in one controllers, and online download of
LAN pathway, communication is new firmware is often possible with
automatically re-routed. redundant controllers.

• Peer-to-Peer Communications – PAC8000 controllers feature an


RS485 serial connection for Modbus
PAC8000 Controllers communicate RTU communication (a second serial
directly with each other and share connection can be made on the
data on a peer-to-peer basis without Controller Carrier).
having to route data through a
centralized database or server. Contact – When used with the dedicated AC
GE or information regarding large Power Supplies, PAC8000 nodes can
installations that feature more than be configured to “warm start” after
12 redundant PAC8000 nodes (or 24 power failure – the power supplies
simplex nodes). provide sufficient hold up time for
the controller to store all necessary
• HART Support live data and to re-commence control
PAC8000 Controllers can pass HART from the point the power was lost,
data from smart field devices to asset when it is restored.
management software applications, • Event Recording
allowing remote configuration and
access to field instrument diagnostic Controllers can record up to 8000 Publication Reference Chart
information. PAC8000 Controllers can events in internal memory. Data read INM8521 Hybrid, Process, Logic & EBIM
also acquire HART data for use in the from dedicated SOE modules are time INM8900 Power Supplies
process control application. stamped by the module. All other data
is time stamped by the Controller, and
• Engineering Tools the accuracy of the time stamp is then
The Workbench provides an integrated dependent on the execution cycle. The
project development environment records must be read from the internal
coupled with development modules memory by a suitable historian package
and tools and a comprehensive set before the event buffer is filled and
of diagnostic utilities. Different over-written by new data.
versions of the Workbench work with
each Controller.

www.geautomation.com Automation & Control Systems 5.27


Safety and Distributed Control

PAC8000 Process Controllers


The PAC8000 Controllers include a Process Controller featuring distributed control system (DCS)-
style function block programming; a Logic Controller featuring 61131-style programmable logic
controller (PLC) programming; and a Hybrid Controller that provides both programming styles in the
same unit. A SIL 2 SafetyNet Controller and an RTU Controller are also available, which provides DNP3
communication for the PAC8000 family.
The 8521-EB-MT Bus Interface Module, for remote I/O applications, shares the same hardware as
the controllers listed below. It can be upgraded from a bus interface module to a full controller by
firmware download, which is especially useful in ongoing legacy system replacement.

8521-LC-MT 8521-PC-MT 8521-HC-MT 8521-RT-DE

Product Name Logic Controller Process Controller Hybrid Controller RTU Controller

Lifecycle Status Active Active Active Active

IEC 61131 languages: Function Block Combines programming IEC 61131 languages:
Ladder Diagram (LD) Programming languages of Logic and Ladder Diagram (LD)
Structured Text (ST) Hybrid Controllers Structured Text (ST)
Instruction List (IL) in a single unit Instruction List (IL)
Programming Languages
Sequential Function Chart Sequential Function Chart
(SFC) (SFC)
Function Block Diagram (FBD) Function Block Diagram (FBD)
And Flow Chart And Flow Chart

LAN Communication Protocol Modbus TCP/IP Modbus TCP/IP Modbus TCP/IP DNP3

24 (24 nodes with simplex 24 (24 nodes with simplex 24 (24 nodes with simplex 24 (24 nodes with simplex
controllers or 12 with controllers or 12 with controllers or 12 with controllers or 12 with
Number of Controllers per LAN redundant controllers) - redundant controllers) - redundant controllers) - redundant controllers) -
with maximum IO modules. For with maximum IO modules. For with maximum IO modules. For with maximum IO modules. For
larger systems, contact GE. larger systems, contact GE. larger systems, contact GE. larger systems, contact GE.

Number of Modules per Controller 64 64 64 64

2 RJ45 Connectors 2 RJ45 Connectors 2 RJ45 Connectors 2 RJ45 Connectors


LAN Connections
per Controller per Controller per Controller per Controller

100Base TX or 100Base TX or 100Base TX or 100Base TX or


LAN Transmission Medium
10BaseT Ethernet 10BaseT Ethernet 10BaseT Ethernet 10BaseT Ethernet

LAN Transmission Speed 10 – 100 Mb/s 10 – 100 Mb/s 10 – 100 Mb/s 10 – 100 Mb/s

LAN Isolation 1500 V dielectric withstand 1500 V dielectric withstand 1500 V dielectric withstand 1500 V dielectric withstand

One male 9-pin D-type One male 9-pin D-type One male 9-pin D-type One male 9-pin D-type
Serial Connections on each Controller (second on each Controller (second on each Controller (second on each Controller (second
female connector on Carrier) female connector on Carrier) female connector on Carrier) female connector on Carrier)

Serial Transmission Medium RS485 half-duplex RS485 half-duplex RS485 half-duplex RS485 half-duplex

Serial Transmission Speed 1.2 – 115 kb/s 1.2 – 115 kb/s 1.2 – 115 kb/s 1.2 – 115 kb/s

Direct connection to Controller: Direct connection to Controller: Direct connection to Controller: Direct connection to Controller:
Controller Power 12 VDC (10.9 – 12.6), 12 VDC (10.9 – 12.6), 12 VDC (10.9 – 12.6), 12 VDC (10.9 – 12.6),
0.4 A typical, 0.5 A max 0.4 A typical, 0.5 A max 0.4 A typical, 0.5 A max 0.4 A typical, 0.5 A max

System Power Consumption 15 mA (max) 15 mA (max) 15 mA (max) 15 mA (max)

Dimensions (W x H x D) in mm 232 x 69 x 138 232 x 69 x 138 232 x 69 x 138 232 x 69 x 138

Weight (kg) 1.35 1.35 1.35 1.35

5.28 Automation & Control Systems www.geautomation.com