You are on page 1of 12

Parameter Settings Report (Program) 04/04/2022 19:20:18

Program (Drive Selected / Connected):

Drive Type / Model: L1000E CIMR-L*2*0059***


Software: 7602

Project:
User:

Information

Default
Parameter Value Information Setting
A1 Initialization
A1-01 Access level 2 Advanced Level Access 2
A1-02 Control method 2 Open-loop vector control 1 2
A1-04 Enter password 0 0
A2 User Parameters
A2-01 User parameter 1 A1-02 Control method A1-02
A2-02 User parameter 2 b1-01 Speed Reference Selection b1-01
A2-03 User parameter 3 C1-01 Acceleration time 1 C1-01
A2-04 User parameter 4 C1-02 Deceleration time 1 C1-02
A2-05 User parameter 5 d1-01 Speed Reference 1 d1-01
A2-06 User parameter 6 d1-02 Speed Reference 2 d1-02
A2-07 User parameter 7 d1-03 Speed Reference 3 d1-03
A2-08 User parameter 8 d1-04 Speed Reference 4 d1-04
A2-09 User parameter 9 d1-26 Leveling Speed d1-26
A2-10 User parameter 10 E1-01 Input voltage setting E1-01
A2-11 User parameter 11 E1-04 Max. output frequency E1-04
A2-12 User parameter 12 E1-05 Max. voltage E1-05
A2-13 User parameter 13 E1-06 Base frequency E1-06
A2-14 User parameter 14 E1-09 Min. output frequency E1-09
A2-15 User parameter 15 E1-13 Base voltage E1-13
A2-16 User parameter 16 E2-01 Motor rated current E2-01
A2-17 User parameter 17 E2-04 Number of motor poles E2-04
A2-18 User parameter 18 E2-11 Motor rated output E2-11
A2-19 User parameter 19 L1-01 Motor protection selection L1-01
A2-20 User parameter 20 ----- -----
A2-21 User parameter 21 ----- -----
A2-22 User parameter 22 ----- -----
A2-23 User parameter 23 ----- -----
A2-24 User parameter 24 ----- -----
A2-25 User parameter 25 ----- -----

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 1/12


Default
Parameter Value Information Setting
A2-26 User parameter 26 ----- -----
A2-27 User parameter 27 ----- -----
A2-28 User parameter 28 ----- -----
A2-29 User parameter 29 ----- -----
A2-30 User parameter 30 ----- -----
A2-31 User parameter 31 ----- -----
A2-32 User parameter 32 ----- -----
A2-33 User parameter Automatic registration 0 Automatic registration is unavailable(Totally user setting from 0
Function A2-01 toA2-32)
b1 Operation Mode Selection
*b1-01 Speed Reference Selection... [M] 1 Control circuit terminal 0
b1-02 Operation method selection 1 Control circuit terminal 1
b1-03 Stopping method 0 Deceleration to stop 0
b1-06 Digital Input Scan Selection 1 2 Scans 1
b1-07 Local/remote run selection 0 Cycle External Run - If the run command is closed when 0
switching from LOCAL mode or alternative reference to
b1-08 Run command at programming 0 Cannot operate 0
REMOTE mode, the drive will not run.
b1-09 L/R select at drive 0 Disabled 0
b1-14 Phase Turn Selection 0 Normal 0
b2 DC Injection Braking
b2-05 DC injection P gain 0,05 0,05
b2-06 DC injection integral time 10,0 ms 10,0 ms
b2-07 DC injection limit 15,0 % 15,0 %
b2-08 Field compensation 0% 0%
b4 Timer Function
b4-01 Delay-ON timer 0,0 sec 0,0 sec
b4-02 Delay-OFF timer 0,0 sec 0,0 sec
b6 Dwell Function
b6-01 Dwell frequency at start 0,0 % 0,0 %
b6-02 Dwell time at start 0,0 sec 0,0 sec
b6-03 Dwell frequency at stop 0,0 % 0,0 %
b6-04 Dwell time at stop 0,0 sec 0,0 sec
C1 Acceleration and Deceleration Times
*C1-01 Acceleration time 1... [M] 3,00 sec 1,50 sec
*C1-02 Deceleration time 1... [M] 2,50 sec 1,50 sec
*C1-03 Acceleration time 2... [M] 2,00 sec 1,50 sec
*C1-04 Deceleration time 2... [M] 2,00 sec 1,50 sec
*C1-05 Acceleration time 3 for motor2... [M] 2,00 sec 1,50 sec
*C1-06 Deceleration time 3 for motor2... [M] 2,00 sec 1,50 sec
C1-07 Acceleration time 4 for motor2 1,50 sec 1,50 sec
C1-08 Deceleration time 4 for motor2 1,50 sec 1,50 sec
C1-09 Emergency stop time 1,50 sec 1,50 sec
C1-10 Accel/Decel time setting unit 0 0.01-second units 0
C1-11 Accel/Decel switching frequency 0,0 % 0,0 %
C1-12 Motor 2 Acceleration time 1,00 sec 1,00 sec
C1-13 Motor 2 Deceleration time 1,00 sec 1,00 sec
C1-15 Inspection Operation Deceleration Ramp 0,00 sec 0,00 sec
C2 S-Curve Characteristics
C2-01 S-curve acceleration at start 0,50 sec 0,50 sec

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 2/12


Default
Parameter Value Information Setting
C2-02 S-curve acceleration at end 0,50 sec 0,50 sec
C2-03 S-curve deceleration at start 0,50 sec 0,50 sec
C2-04 S-curve deceleration at end 0,50 sec 0,50 sec
C2-05 Jerk below leveling speed 0,50 sec 0,50 sec
C3 Slip Compensation
C3-01 Slip compensation gain 1,0 1,0
*C3-02 Slip compensation time... [M] 240 ms 2000 ms
C3-03 Slip compensation limit 200 % 200 %
C3-04 Slip compensation regeneration 0 Slip compensation is disabled during regeneration. 0
C3-05 Output V Limit 1 Enabled 1
C3-06 Flux selection 0 Magnetic flux is calculated after compensation 0
C3-15 Slip compensation regeneration lower limit 2,0 Hz 2,0 Hz
C4 Torque Compensation
C4-01 Torque compensation gain 1,00 1,00
C4-02 Torque compensation time 50 ms 50 ms
C4-03 Forward starting torque 0,0 % 0,0 %
C4-04 Reverse starting torque 0,0 % 0,0 %
C4-05 Torque compensation delay time 10 ms 10 ms
C4-06 Starting torque time constant 150 ms 150 ms
C6 Carrier Frequency
C6-02 Carrier frequency selection 0F Program 0F
C6-03 Carrier frequency upper limit 8,0 kHz 8,0 kHz
C6-07 Phase SW level 1,5 1,5
C6-09 Carrier in tune 0 5kHz 0
C6-10 Fc in stand tune 1 1.0 kHz 1
C6-21 Inspection Operation Carrier Frequency 1 2 kHz fix 1
C6-31 Rescue Operation 2kHz 0 C6-03 setting 0
d1 Frequency Reference
*d1-01 Speed Reference 1... [M] 2,00 Hz 0,00 Hz
*d1-02 Speed Reference 2... [M] 30,00 Hz 0,00 Hz
*d1-03 Speed Reference 3... [M] 45,00 Hz 0,00 Hz
*d1-04 Speed Reference 4... [M] 45,00 Hz 0,00 Hz
*d1-05 Speed Reference 5... [M] 25,00 Hz 0,00 Hz
*d1-06 Speed Reference 6... [M] 5,00 Hz 0,00 Hz
*d1-07 Speed Reference 7... [M] 5,00 Hz 0,00 Hz
*d1-08 Speed Reference 8... [M] 5,00 Hz 0,00 Hz
d1-18 Speed Reference Selection Mode 0 Use Multi-Speed references d1-01 to d1-08 0
*d1-24 Inspection Operation Speed... [M] 30,00 Hz 0,00 Hz
*d1-25 Rescue Operation Speed... [M] 6,00 Hz 0,00 Hz
*d1-26 Leveling Speed... [M] 4,80 Hz 0,00 Hz
d1-28 Leveling Speed Detection Level 0,0 % 0,0 %
d1-29 Inspection Speed Detection Level 0,0 % 0,0 %
d6 Field Weakening and Field Forcing
d6-03 Magnetic Field Forcing Enable/Disable 0 Disabled 0
Selection
d6-06 Field force limit 400 % 400 %
E1 Motor 1 V/f Pattern Characteristics
E1-01 Input voltage setting 230 VAC 230 VAC

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 3/12


Default
Parameter Value Information Setting
E1-04 Max. output frequency 60,0 Hz 60,0 Hz
E1-05 Max. voltage 230,0 VAC 230,0 VAC
E1-06 Base frequency 60,0 Hz 60,0 Hz
E1-07 Mid output frequency 3,0 Hz 3,0 Hz
E1-08 Mid output frequency voltage 12,6 VAC 12,6 VAC
E1-09 Min. output frequency 0,5 Hz 0,5 Hz
E1-10 Min. output frequency voltage 2,3 VAC 2,3 VAC
E1-11 Mid output frequency 2 0,0 Hz 0,0 Hz
E1-12 Mid output frequency voltage 2 0,0 VAC 0,0 VAC
*E1-13 Base voltage... [M] 230,0 VAC 0,0 VAC
E2 Motor 1 Setup
*E2-01 Motor rated current... [M] 41,0 A 53,0 A
*E2-02 Motor rated slip... [M] 7,96 Hz 1,60 Hz
*E2-03 Motor no-load current... [M] 13,6 A 15,2 A
E2-04 Number of motor poles 4 4
*E2-05 Motor line-to-line resistance... [M] 0,282 Ohm 0,138 Ohm
*E2-06 Motor leak inductance... [M] 19,3 % 17,2 %
E2-07 Saturation Comp 1 0,50 0,50
E2-08 Saturation Comp 2 0,75 0,75
E2-09 Motor mechanical loss 0,0 % 0,0 %
*E2-11Motor rated output... [M] 11,00 kW 15,00 kW
E2-16 Motor Line Resistance Setting Unit Selection 0 ohm 0
F2 Analog Input Card (AI-A3)
F2-01 AI Option Input Mode Selection 0 3ch Individual Input 0
F2-02 AI Option Input Gain Setting 100,0 % 100,0 %
F2-03 AI Option Input Bias Setting 0,0 % 0,0 %
F3 Digital Input Card (DI-A3)
F3-01 DI Option Input Mode Selection 0 BCD 1% 0
F3-03 DI Option Bit Size Selection 2 16 bit 2
F4 Analog Monitor Card (AO-A3)
F4-01 Terminal V1 Monitor Setting 102 Output frequency 102
F4-02 Terminal V1 Monitor Gain Setting 100,0 % 100,0 %
F4-03 Terminal V2 Monitor Setting 103 Output current 103
F4-04 Terminal V2 Monitor Gain Setting 50,0 % 50,0 %
F4-05 Terminal V1 Monitor Bias Setting 0,0 % 0,0 %
F4-06 Terminal V2 Monitor Bias Setting 0,0 % 0,0 %
F4-07 AO1 Option Output Level Selection 1 -10 to 10 V (11 bit signed) 1
F4-08 AO2 Option Output Level Selection 1 -10 to 10 V (11 bit signed) 1
F5 Digital Output Card (DO-A3)
F5-01 Terminal P1-PC Function Selection 0000 Closed: There is a run command present or the drive is 0000
outputting voltage
F5-02 Terminal P2-PC Function Selection 0001 Closed: Output frequency is zero 0001
F5-03 Terminal P3-PC Function Selection 0002 Closed: Output frequency equals the speed reference (plus or 0002
minus the value set to L4-02)
F5-04 Terminal P4-PC Function Selection 0004 Closed: Output frequency is less than or equal to the value in 0004
L4-01 with hysteresis determined by L4-02.
F5-05 Terminal P5-PC Function Selection 0006 Closed: Drive Ready 0006
F5-06 Terminal P6-PC Function Selection 0037 During frequency output (ON: During frequency output) 0037
F5-07 Terminal M1-M2 Function Selection 000F Not used 000F
F5-08 Terminal M3-M4 Function Selection 000F Not used 000F

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 4/12


Default
Parameter Value Information Setting
F5-09 DO Option (DO08) Output Mode Selection 0 8ch Individual Output 0
F6 Option Card 1 Serial Communication
*F6-01 Operation selection after commun... [M] 0 Ramp to stop 1
F6-02 Selection of External Fault from 0 Always detect 0
Communication Option Board
*F6-03 Stopping Method for External Fau... [M] 0 Ramp to Stop 1
F6-04 Trace Sampling from Communications Option 2,0 sec 2,0 sec
Board
F6-07 Fref Priority Selection 0 NetREF/ComREF are available. 0
F6-08 Comm Parameter Initialize Selection 0 Comm Parameters are not initialized due to A1-02. 0
F6-10 Node Address 0 0
F6-11 Communication Speed 0 156 Kbps 0
F6-12 Data Length 0 Single word 0
F6-13 CC-LINK Mode Selection 0 Ver1.2 0
F6-14 BUS Error Auto Reset 0 Disabled 0
F6-20 Station Address 21 21
F6-21 Frame length 0 32byte mode 0
F6-22 Link Speed 0 10MHz 0
F6-23 Mon E register 0000 0000
F6-24 Mon F register 0000 0000
F6-25 BUS Error Detection Mode Selection 1 Coast to Stop 1
F6-26 Number of BUS error detection 2 2
F6-30 Node Address 0 0
F6-31 Clear Mode Selection 0 Resets back to zero. 0
F6-32 ProfibusMap Selection 0 PPO Type 0
F6-35 Node Address 0 0
F6-36 CANopen Communication Speed 6 500 Kbps 6
F6-50 MAC Address 64 64
F6-51 Baud Rate 4 Detect automatically 4
F6-52 PCA Setting 21 21
F6-53 PPA Setting 71 71
F6-54 Idle Mode Fault Detection 0 No Detection 0
F6-56 Speed Scaling 0 0
F6-57 Current Scaling 0 0
F6-58 Torque Scaling 0 0
F6-59 Power Scaling 0 0
F6-60 Voltage Scaling 0 0
F6-61 Time Scaling 0 0
F6-62 Heart Beat 0 0
F6-64 Dynamic Output Assembly 109 Parameter 1 0000 0000
F6-65 Dynamic Output Assembly 109 Parameter 2 0000 0000
F6-66 Dynamic Output Assembly 109 Parameter 3 0000 0000
F6-67 Dynamic Output Assembly 109 Parameter 4 0000 0000
F6-68 Dynamic Input Assembly 159 Parameter 1 0000 0000
F6-69 Dynamic Input Assembly 159 Parameter 2 0000 0000
F6-70 Dynamic Input Assembly 159 Parameter 3 0000 0000
F6-71 Dynamic Input Assembly 159 Parameter 4 0000 0000
F6-80 Trace sampling setting 0 0
F6-82 2 motor switch over command selection 0 Disable the data from PLC 0

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 5/12


Default
Parameter Value Information Setting
F7 Option Card 2 Serial Communication
F7-01 IP Address1 192 192
F7-02 IP Address2 168 168
F7-03 IP Address3 1 1
F7-04 IP Address4 20 20
F7-05 Subnet Mask1 255 255
F7-06 Subnet Mask2 255 255
F7-07 Subnet Mask3 255 255
F7-08 Subnet Mask4 0 0
F7-09 Gateway Address1 192 192
F7-10 Gateway Address2 168 168
F7-11 Gateway Address3 1 1
F7-12 Gateway Address4 1 1
F7-13 Address Startup Mode 2 DHCP 2
F7-14 Duplex Mode Setting 1 Auto Negotiate 1
F7-15 Speed Mode Setting 10 10 Mbps speed setting 10
F7-16 Timeout Value 0 0
F7-17 Speed Scaling 0 0
F7-18 Current Scaling 0 0
F7-19 Torque Scaling 0 0
F7-20 Power Scaling 0 0
F7-21 Voltage Scaling 0 0
F7-22 Time Scaling 0 0
F7-23 Dynamic Output Assembly 116 Parameter 1 0000 0000
F7-24 Dynamic Output Assembly 116 Parameter 2 0000 0000
F7-25 Dynamic Output Assembly 116 Parameter 3 0000 0000
F7-26 Dynamic Output Assembly 116 Parameter 4 0000 0000
F7-27 Dynamic Output Assembly 116 Parameter 5 0000 0000
F7-28 Dynamic Output Assembly 116 Parameter 6 0000 0000
F7-29 Dynamic Output Assembly 116 Parameter 7 0000 0000
F7-30 Dynamic Output Assembly 116 Parameter 8 0000 0000
F7-31 Dynamic Output Assembly 116 Parameter 9 0000 0000
F7-32 Dynamic Output Assembly 116 Parameter 10 0000 0000
F7-33 Dynamic Input Assembly 166 Parameter 1 0000 0000
F7-34 Dynamic Input Assembly 166 Parameter 2 0000 0000
F7-35 Dynamic Input Assembly 166 Parameter 3 0000 0000
F7-36 Dynamic Input Assembly 166 Parameter 4 0000 0000
F7-37 Dynamic Input Assembly 166 Parameter 5 0000 0000
F7-38 Dynamic Input Assembly 166 Parameter 6 0000 0000
F7-39 Dynamic Input Assembly 166 Parameter 7 0000 0000
F7-40 Dynamic Input Assembly 166 Parameter 8 0000 0000
F7-41 Dynamic Input Assembly 166 Parameter 9 0000 0000
F7-42 Dynamic Input Assembly 166 Parameter 10 0000 0000
H1 Multi-Function Digital Inputs
H1-01 Terminal S1 function selection 40 Forward Run Command 40
H1-02 Terminal S2 function selection 41 Reverse Run Command 41
*H1-03 Terminal S3 function selection... [M] 03 Multi-step speed reference 1 24

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 6/12


Default
Parameter Value Information Setting
*H1-04 Terminal S4 function selection... [M] 04 Multi-step speed reference 2 14
*H1-05 Terminal S5 function selection... [M] 05 Multi-step speed reference 3 03
*H1-06 Terminal S6 function selection... [M] 0F Not used(Unused / when use it as a pass-through mode.) 04
*H1-07 Terminal S7 function selection... [M] 1A Accel/Decel time 2 05
H1-08 Terminal S8 function selection 0F Not used(Unused / when use it as a pass-through mode.) 0F
H1-13 Selection external BB 1 Fout = 0 during external BB 1
H2 Multi-Function Digital Outputs
H2-01 Terminal M1-M2 Selection 0050 Brake Control 0050
H2-02 Terminals P1 (M3-M4) Function Selection 0051 Output Contactor Control 0051
H2-03 Terminals P2 (M5-M6) Function Selection 0006 Closed: Drive Ready 0006
H2-04 Terminals P3 (P1) Function Selection 0037 During frequency output (ON: During frequency output) 0037
H2-05 Terminals P4 (P2) Function Selection 000F Not used 000F
H3 Multi-Function Analog Inputs
H3-01 Terminal A1 Signal Level Selection 0 0 to +10 V 0
H3-02 Terminal A1 Function Selection 00 Frequency Bias 00
*H3-03 Terminal A1 Gain Setting... [M] 8,4 % 100,0 %
H3-04 Terminal A1 Bias Setting 0,0 % 0,0 %
H3-09 Terminal A2 Signal Level Selection 0 0 to +10 V 0
H3-10 Terminal A2 Function Selection 1F Not used. Enter this setting when not using the terminal or 1F
when using it in the through mode.
H3-11 Terminal A2 Gain Setting 100,0 % 100,0 %
H3-12 Terminal A2 Bias Setting 0,0 % 0,0 %
H3-13 Filter Avg time 0,03 sec 0,03 sec
H3-16 Terminal A1 Offset 0 0
H3-17 Terminal A2 Offset 0 0
H3-18 Terminal A3 Offset 0 0
H4 Multi-Function Analog Outputs
H4-01 Multi-Function Analog 1(Analog Terminal 102 Output frequency 102
Monitor Selection)
H4-02 Multi-Function Analog 1(Analog Terminal 100,0 % 100,0 %
Output Gain)
H4-03 Multi-Function Analog 1(Analog Terminal 0,0 % 0,0 %
Output Bias)
H4-04 Multi-Function Analog 2(Analog Terminal 103 Output current 103
Monitor Selection)
H4-05 Multi-Function Analog 2(Analog Terminal 50,0 % 50,0 %
Output Gain)
H4-06 Multi-Function Analog 2(Analog Terminal 0,0 % 0,0 %
Output Bias)
H4-07 Multi-Function Analog 1(Signal Level 0 0 to +10 V 0
Selection)
H4-08 Multi-Function Analog 2(Signal Level 0 0 to +10 V 0
Selection)
H4-09 Gain/Bias selection 1 YEA type 1
H5 MEMOBUS/Modbus Communications
H5-01 Station address 01 01
H5-02 Communication speed selection 3 9600 bps 3
H5-03 Communication parity selection 0 No parity 0
H5-04 Serial fault selection 3 Operation continued 3
H5-05 CE Detection Selection 1 Enabled 1
H5-06 Send wait time 5 ms 5 ms
H5-07 RTS control ON/OFF 1 Enabled 1
H5-09 CE detection time 2,0 sec 2,0 sec
H5-10 Output voltage monitor(Register No.25) unit 0 0.1V unit 0
H5-11 ENTER function selection of transmission 0 A constant is reflected and memorized when ENTER is input. 0
H5-12 Run Command Method Selection 0 FWD/STOP,REV/STOP type 0

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 7/12


Default
Parameter Value Information Setting
L1 Protection
L1-01 Motor protection selection 1 General-purpose motor protection 1
L1-02 Motor protection time constant 1,0 min 1,0 min
L1-03 Motor Overheat Alarm Operation Selection 3 Coast to stop with timer 3
(PTC input)
L1-04 Motor Overheat Fault Operation Selection 1 Coast to stop 1
(PTC input)
L1-05 Motor Temperature Input Filter Time (PTC 0,20 sec 0,20 sec
input)
L1-13 Electronic thermal continues 1 Continue Electronic thermal 1
L2 Momentary Power Loss
L2-05 Undervoltage detection level 190 VDC 190 VDC
L3 Stall Prevention Function
L3-01 StallP acceleration selection 1 Enabled 1
L3-02 StallP acceleration level 150 % 150 %
L3-03 StallP CHP level 50 % 50 %
L3-04 StallP deceleration selection 0 Disabled - The drive decelerates at the selected Dec time.If the 0
load is too large or the Dec time is too short, an OV fault may
L3-07 StallP gain 1,00 1,00
occur.
L3-08 StallP integral time 100 ms 100 ms
L3-09 Shortened T rate 1,0 1,0
L3-10 Stall Prev deceleration level 92 % 92 %
L4 Frequency Detection
L4-01 Speed agreement level 0,0 % 0,0 %
L4-02 Speed agreement width 4,0 % 4,0 %
L4-03 Speed agreement level +- 0,0 % 0,0 %
L4-04 Speed agreement width +- 4,0 % 4,0 %
L4-05 Reference loss selection 0 Stop 0
L4-06 Frequency reference at floss 80,0 % 80,0 %
L4-07 Frequency Detect Selection 0 No Detection during BB 0
L4-13 Door Zone Level 0,0 % 0,0 %
L5 Fault Reset
L5-01 Number of auto restart attempts 0 0
L5-02 Auto restart operation selection 0 Not output(Fault contact is not activated) 0
L5-03 Time to Continue Making Fault Restarts 10,0 sec 10,0 sec
(enabled only when L5-05 = 0)
L5-04 Fault Reset Interval Time 10,0 sec 10,0 sec
L5-06 Under Voltage Fault Restart Selection 0 Same as L5-01 condition 0
L6 Overtorque Detection
L6-01 Torque detection selection 1 0 Overtorque/undertorque detection disabled 0
L6-02 Torque detection level 1 150 % 150 %
L6-03 Torque detection time 1 0,1 sec 0,1 sec
L6-04 Torque detection selection 2 0 Overtorque/undertorque detection disabled 0
L6-05 Torque detection level 2 150 % 150 %
L6-06 Torque detection time 2 0,1 sec 0,1 sec
L7 Torque Limit
L7-01 Forward drive torque Limit 200 % 200 %
L7-02 Reverse drive torque Limit 200 % 200 %
L7-03 Forward regenerative torque limit 200 % 200 %
L7-04 Reverse regenerative torque limit 200 % 200 %
L7-06 Torque limit time 200 ms 200 ms
L7-07 Torque limit selection 0 Proportional control 0

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 8/12


Default
Parameter Value Information Setting
L7-16 Torque Limit rise mode selection at start 1 Effective delay time 1
L8 Hardware Protection
L8-01 DB resistor protect 0 Disabled 0
L8-02 Overheat pre-alarm level 120 °C 120 °C
L8-03 Overheat pre-alarm selection 3 Operation continued(monitor display only) 3
L8-04 OH1 fault level 125 °C 125 °C
L8-05 Phase loss input selection 1 Enabled always 1
L8-06 Phase loss input 22,0 % 22,0 %
L8-07 Phase loss output selection 0 Disabled 0
L8-08 Phase loss output level 5,0 % 5,0 %
L8-09 Ground protection selection 1 Enable 1
L8-10 Cooling fan control selection 0 Operates when inverter is running 0
L8-11 Cooling fan control delay time 60 sec 60 sec
L8-12 Ambient temperature 40 °C 40 °C
L8-14 Inverter Overload Protection Selection 1 Inverter Protective OL Enable 1
L8-15 OL characteristics at low speeds 1 L8-16,17 setting enable 1
L8-16 Low speed OL2 frequency 6,0 Hz 6,0 Hz
L8-17 OL2 0Hz gain 50 % 50 %
L8-38 Torque Boost Function Selection 0 Disabled 0
L8-39 Reduction carrier frequency 3,0 kHz 3,0 kHz
L8-40 Reduction carrier frequency time 0,00 sec 0,00 sec
L8-41 Current warning 0 Disable 0
L8-42 Input phase detection time 10 sec 10 sec
L8-43 Output phase detection time 0,5 sec 0,5 sec
L8-46 AVR selection 1 Enabled 1
L8-47 Ground Fault Level 50 % 50 %
L8-48 Ground Fault Detection Filter Constant Time 12,0 ms 12,0 ms
L8-49 Frequency gradual decrease cycle at OH 10 sec 10 sec
Pre-alarm
L8-50 Load Short-circuit protection selection 1 With load short circuit protection 1
L8-55 Internal DB Transistor Protection 1 Enable 1
Enable/Disable Selection
L8-59 rr Fault Detection Count 4 4
L8-60 BTR Answer Back monitor Timer 15 usec 15 usec
L8-61 SC Protection 1 Reset Disable 1
L8-62 Operation selection at Input phase loss 1 Coast to Stop 1
L8-64 Cooling fan ON level 60 °C 60 °C
L8-77 Oscill Suppress 0 0
L8-88 Safety Operation Mode 1 Mode 1 (L7 mode) 1
L8-89 Current monitor function selection 0 Disabled 0
L8-99 Current monitor level 10,0 % 10,0 %
n1 Hunting Prevention
n1-08 leacage current vibration control selection 0 method 1 0
n2 Speed Feedback Detection Control Function
n2-01 AFR gain 1,50 1,50
n2-02 AFR time 50 ms 50 ms
n2-03 AFR time 2 750 ms 750 ms
n2-04 AFR limit 5,0 Hz 5,0 Hz
n2-05 AFR Gain Reduction Modulation Level 85 % 85 %

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 9/12


Default
Parameter Value Information Setting
n6 Online Tuning
n6-01 Line-to-Line Motor Resistance Online Tuning 2 Enable (Primary impedance and Speed) 2
n6-02 R1 Online Change Amount 0,0001 0,0001
n6-03 R1 Online Change Width 40 % 40 %
n6-04 R1 Online Iq Lower Limit 10,0 % 10,0 %
n6-05 Online compensation gain 1,0 1,0
n6-06 Slip temperature compensation limit 10,0 % 10,0 %
n6-07 Slip temperature compensation adjustment 0,0001 % 0,0001 %
n6-08 Voltage compensation filter time constant 0,40 sec 0,40 sec
n6-09 Voltage compensation limit 10,0 % 10,0 %
n6-10 Field estimation filter time constant 10,0 sec 10,0 sec
n9 Factory Level
n9-01 Inverter rate current 47,0 A 47,0 A
n9-02 DCCT gain 1,106 1,106
n9-03 ACR Q gain 0,10 0,10
n9-04 ACR Q I time 0,0 ms 0,0 ms
n9-05 ACR Q limit 5% 5%
n9-06 ACR D gain 0,30 0,30
n9-07 ACR D I time 0,0 ms 0,0 ms
n9-08 ACR D limit 5% 5%
n9-10 AVR time 1,0 ms 1,0 ms
n9-11 On-Delay time 3,5 us 3,5 us
n9-12 On-Delay comp 2,00 us 2,00 us
n9-13 IGBT volt drop 0,0 % 0,0 %
n9-16 IDFB filter 1,00 sec 1,00 sec
n9-17 R IDFB filter 1,00 sec 1,00 sec
n9-18 L-Tuning filter 1000 ms 1000 ms
n9-19 DCCT filter time 0 us 0 us
n9-20 Current limit gain 2,00 2,00
n9-21 Current limit time constant 0,5 ms 0,5 ms
n9-22 Current limit 1 150,0 % 150,0 %
n9-23 Current limit 2 150,0 % 150,0 %
n9-24 CL switch point 6,0 Hz 6,0 Hz
n9-25 Current limit 3 300,0 % 300,0 %
n9-26 Correction level 1,50 % 1,50 %
n9-27 IGBT conversion 0,44 0,44
n9-29 IGBT volt drop2 0,0 % 0,0 %
n9-36 IGBT volt drop comp I 16,7 % 16,7 %
n9-60 A / D conversion start delay time 14,0 us 14,0 us
n9-61 Current offset adjustment selection at drive 0 Disable 0
n9-62 On-delay comp gradual decrease start 60,0 Hz 60,0 Hz
frequency
n9-63 On-delay comp disable frequency 120,0 Hz 120,0 Hz
n9-67 On-Delay Compensation Method Selection 2 Logic Detection Method 2
n9-68 Logic Detection Error Mode Selection 3 Alarm Only 3
n9-69 Logic Detection Offset Compensation 0,30 us 0,30 us
n9-74 Current Averaging Selection 0 Disabled 0
n9-75 CurrOffsetTunSel 1 Filter method 1

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 10/12


Default
Parameter Value Information Setting
n9-95 CLA level 3847 3847
n9-96 CLB level 4077 4077
n9-97 Overcurrent level 4459 4459
n9-98 Current limit selection 0 0
n9-99 Select Test mode 0 Normal mode and Actual test (normal mode) 0
o1 Display Settings
o1-01 Monitor selection 106 Output voltage 106
o1-02 Monitor selection after power up 1 Frequency reference 1
*o1-03 Display scaling... [M] 0 0.01Hz units 1
o1-05 LCD Contrast Control 3 3
o1-06 Monitor Mode Selection 0 Scroll 0
o1-07 2 dig Mon Sel 102 Output Frequency 102
o1-08 3 dig Mon Sel 103 Output Current 103
o1-23 HBB nondisplay sel 0 disable 0
o2 Key Selections
o2-01 LOCAL/REMOTE key enable/disable 0 Disable 0
o2-02 Operation STOP key 0 Enabled when the inverter is operated by dig. Operator 0
o2-04 KVA selection 6D CIMR-L*2*0059*** 6D
o2-05 Frequency Reference Setting Method 0 Enter key needed 0
Selection
o2-06 Operator detection 0 Operation continues even if the dig. Operator is disconnected 0
o2-09 Initialize mode selection 1 American spec 1
o3 Copy Function
*o3-02 Copy Allowed Selection... [M] 1 Enabled - Copying allowed. 0
o4 Maintenance Period
o4-02 Cumulative operation time selection 0 Cumulative time when the Inverter power is on 0
o4-03 Fan operation time setting 17 1=10H 17 1=10H
o4-04 Cooling Fan Maintenance Time 7884 1=10H 7884
1=10H
o4-05 Capacitor maintenance setting 0% 0%
o4-06 Capacitor Maintenance Time 7884 1=10H 7884
1=10H
o4-07 Rush-in prevention relay maintenance setting 0% 0%
o4-08 DC Bus Pre-charge Relay Maintenance Time 16200 x10 16200 x10
time(s) time(s)
o4-09 IGBT maintenance setting 0% 0%
o4-10 IGBT Maintenance Setting 90 % 90 %
o4-16 Mainenance Monitoring Selection 1000 1000
S1 Brake Sequence
S1-01 Zero Speed Level at Stop 1,000 % 1,000 %
*S1-02 DC Injection Current at Start... [M] 10 % 50 %
*S1-03 DC Injection Current at Stop... [M] 75 % 50 %
*S1-04 DC Injection / Zero Servo Time a... [M] 0,00 sec 0,40 sec
*S1-05 DC Injection / Zero Servo Time a... [M] 0,80 sec 0,60 sec
*S1-06 Brake Release Delay Time... [M] 0,00 sec 0,20 sec
S1-07 Brake Close Delay Time 0,10 sec 0,10 sec
S1-10 Run Command Delay Time 0,10 sec 0,10 sec
S1-11 Output Contactor Open Delay Time 0,10 sec 0,10 sec
S1-12 Atun Contactor ON 0 Disabled 0
S1-20 DC Injection ACR P-gain 0,05 0,05
S1-21 DC Injection ACR I-time 10,0 ms 10,0 ms

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 11/12


Default
Parameter Value Information Setting
S1-24 ACR limit during DC Injection 15,0 % 15,0 %
S1-25 Baseblock delay time 0 ms 0 ms
S2 Slip Compensation
S2-02 Slip Compensation Gain in Motoring Mode 0,7 0,7
S2-03 Slip Compensation Gain in Regenerative 1,0 1,0
mode
S2-04 Silp Compensation Limit 200 % 200 %
S2-05 Slip Compensation Torque Detection Delay 1000 ms 1000 ms
Time
S2-06 Slip Compensation Torque Detection Time 500 ms 500 ms
S3 Start Stop Optimization
S3-20 Dwell2 Speed Reference 0,00 % 0,00 %
S3-21 Dwell2 End Speed 0,00 % 0,00 %
S3-25 DC Injection Gain in Regenerative Operation 100 % 100 %
S3-26 DC Injection Gain in Motoring Operation 20 % 20 %
S4 Rescue Operation
S4-01 Light Load Direction Search Selection 0 Disabled 0
S4-02 Light Load Direction Search Method 1 Regenerative direction detecion 1
S4-03 Light Load Direction Search Time 1,0 sec 1,0 sec
S4-04 Light Load Direction Search Speed Reference 5,00 % 5,00 %
S4-05 Rescue Operation Torque Limit 100 % 100 %
S4-06 Rescue Operation Power Supply Selection 0 Battery 0
S4-07 UPS Power 0,0 kVA 0,0 kVA
S4-08 UPS Operation Speed Limit Selection 2 Enabled 2
S4-09 Single Phase Operation Factor 50 % 50 %
S4-10 UPS Operation Speed Limit 20 % 20 %
S4-11 UPS Power Ratio 100 % 100 %
S4-12 Main Circuit Voltage During Rescue Operation 0 V 0V
S4-13 Rescue Operation Power Supply Deterioration 80 % 80 %
Detection Level
S4-14 Rescue Operation Power Supply Deterioration 5,0 sec 5,0 sec
Detection Time
S4-15 Fref sel on rescue operation 0 D1-25 0
S5 Short Floor Operation
S5-01 Short Floor Operation Selection 0 Disabled 0
S5-02 Normal Speed for Short Floor Calculation 0,0 % 0,0 %
S5-03 Short Floor Minimum Constant Speed Time 0,0 sec 0,0 sec
S5-04 Distance Calculation Acceleration Time Gain 150,0 % 150,0 %
S5-05 Distance Calculation Deceleration Time Gain 150,0 % 150,0 %
S6 Error Detection
S6-01 SE1 Detection/Reset Seletion 0 Manual Reset 0
S6-02 SE2 Detection Delay Time 200 ms 200 ms
S6-03 SE2 Detection Current 25 % 25 %
S6-04 SE3 Detection Delay Time 200 ms 200 ms
S6-05 SE4 Detection Time 500 ms 500 ms
S6-15 Speed Reference Loss Detection 1 Enabled 1
S6-16 Restart after Baseblock Selection 0 Restart Disabled. The Run command has to be cycled to 0
restart

DriveWizard iQrise for Windows (C) by Yaskawa America, Inc. 12/12

You might also like