You are on page 1of 3

INCOMER CABLE SECTION AND VOLTAGE DROP CLACULATION

SL NO DB NAME LOAD AMPS CABLE SIZE DISTANCE(M) V/A/KM VOLTAGE DROP % VOLTAGE DROP

1 MDB TO DB GF PART-A LIG 44.28 76.99 1 4C,35 1C,16 68 1 5.236 1.309

2 MDB TO DB GF PART-B LIG 26.90 46.78 1 4C,35 1C,16 121 1 5.660 1.415

3 MDB TO DB GF PART-A POW 28.30 49.21 1 4C,35 1C,16 67 1 3.297 0.824

4 MDB TO DB GF PART-B POW 21.40 37.21 1 4C,16 1C,10 121 1.4 6.304 1.576

5 MDB TO DB FF PART-A LIG 29.85 51.91 1 4C,35 1C,16 95 1 4.931 1.233

6 MDB TO DB FF PART-B LIG 41.13 71.52 1 4C,35 1C,16 141 1 10.084 2.521

7 MDB TO DB FF PART-A POW 42.80 74.43 1 4C,35 1C,16 96 1 7.145 1.786

8 MDB TO DB FF PART-B POW 29.50 51.30 1 4C,35 1C,16 140 1 7.182 1.796

9 MDB TO SMDB-AC-01 99.58 173.18 1 4C,95 1C,50 95 0.43 7.074 1.769

10 MDB TO SMDB-AC-02 89.67 155.94 1 4C,70 1C,35 124 0.55 10.635 2.659

11 MDB TO SMDB-AC-03 65.75 114.34 1 4C,50 1C,25 143 0.77 12.590 3.148

12 MDB TO SMDB-AC-04 75.92 132.03 1 4C,70 1C,35 143 0.55 10.384 2.596

13 MDB TO SMDB-AC-05 70.56 122.70 1 4C,70 1C,35 177 0.55 11.944 2.986

14 SMDB-SERVICE TO DB KITCHEN 37.67 65.50 1 4C,50 1C,25 123 0.77 6.204 1.551

15 SMDB-SERVICE TO DB GYM 40.13 69.79 1 4C,50 1C,25 73 0.77 3.923 0.981

16 SMDB-SERVICE TO DB LIFT 7.00 12.17 1 4C,10 1C,6 91 3.4 3.766 0.942

17 MDB TO SMDB 244.80 425.71 2 4C,120 1C,120 20 0.36 3.065 0.766


Copper cables Aluminium cables
c.s.a. Single-phase circuit Balanced three-phase circuit c.s.a. Single-phase circuit Balanced three-phase circuit
in mm 2
Motor power Motor power in mm 2
Motor power Motor power
Normal Start- Lighting Normal Lighting Normal Lighting Normal Lighting
Start-up Start-up Start-up
service up service service service
cos ϕ cos ϕ cos ϕ cos ϕ cos ϕ cos ϕ cos ϕ cos ϕ cos ϕ cos ϕ cos ϕ cos ϕ
0.8 0.35 1 0.8 0.35 1 0.8 0.35 1 0.8 0.35 1
1.5 25.4 11.2 32 22 9.7 27
2.5 15.3 6.8 19 13.2 5.9 16
4 9.6 4.3 11.9 8.3 3.7 10.3 6 10.1 4.5 12.5 8.8 3.9 10.9
6 6.4 2.9 7.9 5.6 2.5 6.8 10 6.1 2.8 7.5 5.3 2.4 6.5
10 3.9 1.8 4.7 3.4 1.6 4.1 16 3.9 1.8 4.7 3.3 1.6 4.1
16 2.5 1.2 3 2.1 1 2.6 25 2.5 1.2 3 2.2 1 2.6
25 1.6 0.81 1.9 1.4 0.7 1.6 35 1.8 0.9 2.1 1.6 0.78 1.9
35 1.18 0.62 1.35 1 0.54 1.2 50 1.4 0.7 1.6 1.18 0.61 1.37
50 0.89 0.5 1 0.77 0.43 0.86 70 0.96 0.53 1.07 0.83 0.46 0.93
70 0.64 0.39 0.68 0.55 0.34 0.59 120 0.6 0.37 0.63 0.52 0.32 0.54
95 0.5 0.32 0.5 0.43 0.28 0.43 150 0.5 0.33 0.5 0.43 0.28 0.43
120 0.41 0.29 0.4 0.36 0.25 0.34 185 0.42 0.29 0.41 0.36 0.25 0.35
150 0.35 0.26 0.32 0.3 0.23 0.27 240 0.35 0.26 0.31 0.3 0.22 0.27
185 0.3 0.24 0.26 0.26 0.21 0.22 300 0.3 0.24 0.25 0.26 0.21 0.22
240 0.25 0.22 0.2 0.22 0.19 0.17 400 0.25 0.22 0.19 0.21 0.19 0.16
300 0.22 0.21 0.16 0.19 0.18 0.14 500 0.22 0.2 0.15 0.19 0.18 0.13
INCOMER CABLE SECTION AND VOLTAGE DROP CLACULATION

SL NO DB NAME LOAD AMPS CABLE SIZE DISTANCE(M) V/A/KM VOLTAGE DROP % VOLTAGE DROP

1 HVAC DB - 4DE01 TO HVAC DB - 4DE02 10.00 18.04 10 0.000 0.000

2 HVAC DB - 4DE01 TO VRV 01-A 12.10 21.83 22 0.000 0.000

3 HVAC DB - 4DE01 TO VRV 01-B 8.72 15.73 25 0.000 0.000

4 HVAC DB - 4DE01 TO VRV 02-A 8.72 15.73 10 0.000 0.000

5 HVAC DB - 4DE01 TO VRV 02-B 6.56 11.83 10 0.000 0.000

6 HVAC DB - 4DE01 TO VRV 03-A 12.10 21.83 10 0.000 0.000

7 HVAC DB - 4DE01 TO VRV 03-B 8.72 15.73 10 0.000 0.000