ED34-645A Control Functions

6.1.2 Field Setting

16

Control 819
Control Functions ED34-645A

Notes:
1. Setting is carried out in the group mode. however, if the mode number inside the parentheses is selected, indoor
units can also be set individually.
2. The SECOND CODE number is set to “ ” when shipped from the factory.
3. Not displayed if the indoor unit is not equipped with that function.
4. When returning to the normal mode. “88” may be displayed in the LCD in order for the remote controller to initialize
itself.
5. ∗ : Setting the static pressure selection for FXD (Q)
SECOND CODE NO.
01 (Factory Setting) 02 (High Static Pressure Setting)
FXD 20 Pa 49 Pa
FXDQ 15 Pa 44 Pa

6.1.3 Setting Group No. for Centralized Control


In order to conduct the central remote control using the central remote controller and the unified ON/OFF controller,
Group No. settings should be made by group using the operating remote controller.
Make Group No. settings for central remote control using the operating remote controller.
1. While in normal mode, press and hold the switch
for a period of four seconds or more to set the system to
"Field Setting Mode".” MODE NO.
GROUP NO.
2. Select the MODE No. “00” with the “ ” button. UNIT NO.
FIELD SET
3. Use the “ ” button to select the group No. for each SETTING MODE
group.
(Group numbers increase in the order of 1-00, 1-01, ... 1-15,
2-00, ... 4-15.)
4. Press “ ” to set the selected group No. TEST
3
5 4
5. Press “ ” to return to the NORMAL MODE.
2,6

Note:
„ For simplified remote controller, see the following.
„ For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the instruction manual
attached.

NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to keep the
installation table with the operation manual for maintenance.