Bar Graphic Temperature Indicators


Ordering Information Input Type and Using Range Dimensions

KN-1000B Series
This is only for reference, the actual product does not support all combinations. Input type Display Using range (℃) Using range (℉) • Unit: mm, For the detailed drawings, follow the Autonics website.
For selecting the specified model, follow the Autonics website . K (CA) TcK1 200 to 1350 -328 to 2,462 • Below is based on KN-1000B series.
K (CA) -199.9 to 999.9 -328 to 1,832

INSTRUCTION MANUAL
K N - 1 ❶ ❷ ❸ B
TcK2
J (IC) TC-J -199.9 to 800.0 -328 to 1,472
E (CR) TC-E -199.9 to 800.0 -328 to 1,472
❶ Alarm output ❷ Option output ❸ Power supply T (CC) TC-T -199.9 to 400.0 -199.9 to 752.0
0: No mark 0: No mark 0: 100-240 VACᜠ 50/60 Hz B (PR)* 100 to 1,800 212 to 3,272
Thermo-
TC-B
2: 2 alarm 1: PV Transmission 1: 24 VDCᜡ R (PR) 0 to 1,750 32 to 3,182
couple TC-R
TCD210153AB

144
4: 4 alarm 4: Communication S (PR)* 0 to 1,750 32 to 3,182

139
TC-S
N (NN)* TC-N -200 to 1,300 -328 to 2,372
C (W5)* TC-C 0 to 2,300 32 to 4,172
L (IC)* -199.9 to 900.0 -328 to 1,652
Thank you for choosing our Autonics product. Product Components
TC-L
U (CC)* -199.9 to 400.0 -199.9 to 752.0
Read and understand the instruction manual and manual thoroughly before
TC-U
Platinel II* 0 to 1,390 32 to 2,534
using the product. • Product • Instruction manual • Bracket ×2 36 10 32
TC-P
Cu50Ω* -199.9 to 200.0 -199.9 to 392.0
For your safety, read and follow the below safety considerations before using. 80
Cu50
• Unit sticker ×1 • Connector (KN-10□□B: ×3, KN-12□□B: ×4, Cu100Ω* -199.9 to 200.0 -199.9 to 392.0
For your safety, read and follow the considerations written in the instruction
Cu10
KN-140□B: ×4, KN-141□B: ×5, KN-144□B: ×5) RTD JPt100Ω -199.9 to 600.0 -328 to 1,112
JPt1
■ Bracket ■ Panel cut-out
manual, other manuals and Autonics website. DPt50Ω DPt5 -199.9 to 600.0 -328 to 1,112
Keep this instruction manual in a place where you can find easily. DPt100Ω -199.9 to 850.0 -328 to 1,530

8.5
Software
DPt1
The specifications, dimensions, etc are subject to change without notice for product 0.00 - 20.00 mA
Current
aMA1
improvement Some models may be discontinued without notice. 4.00 - 20.00 mA
Download the installation file and the manuals from the Autonics website.

140 +0.6
-1,999 to 9,999
aMA2

16
-50.0 - 50.0 mV

8.8

0
12
Follow Autonics website for the latest information. Analog
aMV1
(Display range is variable according to
■ DAQMaster Voltage
-199.9 - 200.0 mV aMV2 decimal point position.)
-1.000 - 1.000 V
DAQMaster is comprehensive device management program. It is available for 52.1
Safety Considerations
A-V1
-1.00 - 10.00 V
parameter setting, monitoring. A-V2
• Above input types which have the * mark are displayed only in Input specification expansion. Refer to 'Mode 33 +0.6
0

• Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards. Setting' to check how to enter the mode.

• ᜸ symbol indicates caution due to special circumstances in which hazards may occur.
Specifications ■ Display accuracy

᜸ Warning Failure to follow instructions may result in serious injury or death


Input type Using temperature Display accuracy Connections
KN-1000B Series At room temperature PV ±0.2% F.S. ±1 digit
Series Thermocouple
AC voltage DC voltage RTD
(25 ℃ ±5 ℃) • Thermocouple below -100 ℃: (PV ±0.4% F.S.) ±1digit ■ KN-10□□B ■ KN-12□□B
01. Fail-safe device must be installed when using the unit with machinery that Out of room
Power supply 100 - 240 VACᜠ 50/60 Hz 24 VDCᜡ Analog PV ±0.3% F.S. ±1 digit
may cause serious injury or substantial economic loss.(e.g. nuclear power temperature range
Allowable voltage range 90 to 110% of rated voltage
control, medical equipment, ships, vehicles, railways, aircraft, combustion • In case of TC-T, TC-U, ±2.0 ℃ will be added to the degree standard.
Power consumption ≤ 6 VA ≤4W '
apparatus, safety equipment, crime/disaster prevention devices, etc.)
Failure to follow this instruction may result in personal injury, economic loss or fire. Sampling period • Thermocouple, RTD: 250 ms • Analog: 100 ms

02. Do not use the unit in the place where flammable/explosive/corrosive gas, Input specification Refer to 'Input Type and Using Range'. Unit Descriptions
high humidity, direct sunlight, radiant heat, vibration, impact or salinity Contact • ON: ≤ 2 kΩ • OFF: ≥ 90 kΩ
Digital 1. Display part(red)
may be present. Non contact • Residual voltage: ≤ 1.0 V • leakage current: ≤ 0.03 mA
input Run mode: Displays PV (Present value).
Outflow current ≈ 0.2 mA 7
Failure to follow this instruction may result in explosion or fire.
1 Setting mode: Displays parameter and setting
03. Install on a device panel to use. Alarm • 2 point relay: 250 VACᜠ 3 A 1c • 4 point relay: 250 VACᜠ 1 A 1a 2
Option value.
Failure to follow this instruction may result in fire or electric shock. PV transmission ISOLATED DC 4-20 mA (Load resistance: ≤ 600 Ω)
output 3 2. Unit sticker part
04. Do not connect, repair, or inspect the unit while connected to a power RS485 comm. Modbus RTU 8
3. Alarm output indicator
source. Display type 7 Segment (red), Graph bar (green) Turns ON when the alarm output is ON.
Failure to follow this instruction may result in fire or electric shock. Alarm output Hysteresis 1 to 999 digit 6
4 ■ KN-14□□B
4. [M] key
05. Check ‘Connections’ before wiring. • 2 point: ≥ 10,000,000 operations
Mechanical Used to enter parameter set mode, move to
Failure to follow this instruction may result in fire. Relay life • 4 point: ≥ 20,000,000 operations
5 parameters, save SV and return to RUN mode.
06. Do not disassemble or modify the unit. cycle • 2 point: ≥ 100,000 operations (load resistance: 250 VACᜠ 3 A)
Electrical 5. [◀], [▲], [▼] key
Failure to follow this instruction may result in fire or electric shock. • 4 point: ≥ 500,000 operations (load resistance: 250 VACᜠ 1 A)
Used to enter and change parameter setting value.
Between input terminal and power terminal: 2,000 VACᜠ 50/60
Dielectric strength 6. Bar graph (green)
᜸ Caution
Hz for 1 min
Failure to follow instructions may result in injury or product damage
0.75 mm amplitude at frequency of 5 to 55 Hz (for 1 min) in each X, Refer to 'Bar Graph'.
Vibration
Y, Z direction for 2 hours Back Front 7. Space for recognizing device by user
01. Use the unit within the rated specifications.
Insulation resistance ≥ 100 MΩ (500 VDCᜡ megger) 8. Selection switch for input specification
Failure to follow this instruction may result in fire or product damage
Noise immunity ±2 kV square shaped noise (pulse width 1 ㎲) by noise simulator
02. Use a dry cloth to clean the unit, and do not use water or organic solvent.
Memory retention ≈ 10 years (non-volatile semiconductor memory type) 0 - 20 mA: Select it for DC 0 (4) - 20 mA input (default)
Failure to follow this instruction may result in fire or electric shock.
03. Keep the product away from metal chip, dust, and wire residue which flow Ambient temperature -10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation) -1 - 10 V: Select it for -1 - 10 VDCᜡ input
into the unit. Ambient humidity 35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
RTD / TC / mV / ±1 V: Select it for Thermocouple, RTD, ±1 V, mV input
Failure to follow this instruction may result in fire or product damage. Approval ᜢᜫ
04. Check the polarity of the measurement input before wiring. Unit weight (packaged) ≈ 182 g (≈ 304 g) • The setting of input type selection switch and the setting value of input type parameter
Failure to follow this instruction may result in explosion or fire. should be same and it can display the proper measurement value.

Communication Interface
Cautions during Use
■ RS485
• Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected
Comm. protocol Modbus 1.1 RTU
accidents.
Maximum connection 32 units
• For connecting the power, use the crimp terminal (M3.5, max. 7.2 mm).
Synchronous method Asynchronous
• 24 VDCᜡ power supply should be insulated and limited voltage/current or Class 2,
Comm. method Two-wire half duplex
SELV power supply device.
• Keep away from high voltage lines or power lines to prevent inductive noise. Do not Comm. effective range ≤ 1,200 m (≤ 700 m recommended)

use near the equipment which generates strong magnetic force or high frequency Comm. speed 9,600 (default) / 4,800 / 2,400 / 1,200 bps (parameter)
noise. Data bit 8 bit (fixed)
• Install a power switch or circuit breaker in the easily accessible place for supplying or Parity bit None (fixed)
disconnecting the power. Stop bit 1 bit (fixed)
• Use twisted pair wire for communication line.
• This unit may be used in the following environments.
- Indoors (in the environment condition rated in ‘Specifications’)
- Altitude Max. 2,000 m
- Pollution degree 2
- Installation category II
-|Transparent Guide|-

Errors ■ Program mode Communication Parameter Setting Function: Bar Graph


Parameter Display Default Setting range Condition
Display Description Troubleshooting Input ■ RUN status group ■ Display method setting
2-1 aMA1 Refer to 'Input Type and Using Range'. -
Flashes when input sensor is disconnected or specification Address Parameter Display Output range It is possible to set in bar graph display method parameter.
IN-P
Check input sensor status. 2-1 Input
sensor is not connected. Display value
BURN
Temperature specification: 300001 (0000) - Display value Full bar Center bar
Flashes when PV is higher than input range. 2-2 ?C ℃, ℉ output
When input is within the rated input unit Thermocouple, [2 alarm output model]: 0 to 3
HHHH UNIT
range, this display disappears. 100 Displays the input from 100 Displays the input from zero
Flashes when PV is lower than input range. RTD [4 alarm output model]: 0 to 15
the bottom for bar graph point (0) for bar graph scale
LLLL
Check the setting condition and Using range low limit ≤ L-RG ≤ using
Flashes when there is an error of setting value 2-3 Low limit input Output Alarm status scale following to bar following to bar graph display
range high limit - 10% of F.S.
L-RG 0)00
reset. value Alarm 1 Alarm 2 Alarm 3 Alarm 4 scale parameter setting value
ERR
High limit L-RG + 10% of F.S. ≤ H-RG ≤ using graph display scale
2-4 0 OFF OFF OFF OFF 0 parameter setting value 0 ← Zero point
input range high limit 2-1 Input
H-RG 2)00
2-5 Decimal point 0.0, 0.00, 0.000, 0 specification: 1 ON OFF OFF OFF • L-BS= 100, H-BS= 100,
Mode Setting 2 OFF ON OFF OFF • L-BS= 100, H-BS= 100,
dP )0
2-6 Low limit scale -1,999 ≤ L-SC < H-SC ≤ 9,999 Analog -50 PV = 50 -50
3 ON ON OFF OFF PV = 50
L-SC 00)0
• When setting '2-24 Input special
2-7 High limit scale function: TUF' 4 OFF OFF ON OFF -100 ← Bottom -100
Monitoring mode
H-SC 10)0
[MODE] → [MODE] over 3 sec → L-SC: -760.0, H-SC: 0 to 9,999 5 ON OFF ON OFF
300002 (0001) Alarm output
setting 2-1 Input 6 OFF ON ON OFF ■ Alarm display in bar graph
-
-999 to 999, specification: 7 ON ON ON OFF
RUN [MODE] over 3 sec → Program mode setting [MODE] over 3 sec → L-SC < IN-B < H-SC Thermocouple, 8 OFF OFF OFF ON When setting or occurring the alarm, it displays the status by the bar graph. It is possible
Input
2-8 RTD 9 ON OFF OFF ON to check the alarm status. When setting alarm value, the bar LED for this alarm value
correction 01)
IN-B 0000
[▲] + [▼] over 3 sec → Digital input key Auto → RUN 2-1 Input 10 OFF ON OFF ON
-999 to 999,
specification: turns ON. When alarm occurs, the bar LED for this alarm value flashes.
L-SC ≤ L-RG≤ IN-B ≤ H-RG ≤ H-SC 11 ON ON OFF ON
Supply the power with Analog • If alarm set value is out of bar graph scale when setting the value or in RUN mode, this
→ Parameter reset Auto → 12 OFF OFF ON ON
pressing [M] + [◀] Bar graph • Input: Thermocouple, RTD value does not display in bar graph.
13 ON OFF ON ON
2-9 display low Input range low limit ≤ L-BS ≤ (H-
Supply the power with Input specification BS-1)
14 OFF ON ON ON Monitoring mode: setting alarm value Run mode: alarm display
→ Auto →
L-BS 00)0
pressing [M] expansion 01) limit scale 15 ON ON ON ON
(L-BS+1) ≤ H-BS ≤ Input range high
limit
- The bar LED for alarm setting value flashes. All set alarm values are displays and
01) Refer to 'Communication Parameter Setting' for checking the details about communication. Bar graph
• Input: Analog ■ Monitoring mode setting group When alarm set is complete, the bar LED when it is alarm value, the bar LED for this
2-10 display high
L-SC ≤ L-BS ≤ (H-SC-1) Address Parameter Display Setting range for this alarm value turns ON. alarm value flashes.
H-BS 10)0
limit scale
(L-SC+1) ≤ H-BS ≤ H-SC 302001 (07D0) [Alarm output model]
Parameter Setting Bar graph AL1 ~ 4 alarm
AL1
to Thermocouple, RTD input: Within input specification,
2-11 display fBAR F.BAR: Full bar, C.BAR: Center bar - temperature
-
BAR 302004 (07D3) Analog input: L-SC~ H-SC
• Some parameters are activated/deactivated depending on the model or setting of method
AL4
302005 (07D4) High peak -
4 mA [Transmission output model]
hPEK
other parameters. Refer to the descriptions of each item. 302006 (07D5) Low peak -
2-12 transmission 00)0 • Input: Thermocouple, RTD:
lPEK
• [MODE] key: Move to next item after saving
lOUT
output scale
20 mA
Within input range
- ■ Program mode setting group
[◀] key: Select parameter / Move digits • Input: Analog
2-13 transmission hOUT 10)0 L-SC ≤ L.OUT ≤ 10% of F.S. Address Parameter Display Setting range Condition
[▲], [▼] key: Select parameter / Change setting value
output scale ≤ H.OUT ≤ H-SC Value Display Value Display Value Display
Value Display
• Return to the RUN mode without saving when there is no key input for more than 30 [Transmission output model] 0 TcK1 (6) TC-B (12) TC-P 18 aMA1
seconds. Input and Setting Transmission
Input range 2-1 Input 1 TcK2 (7) TC-S (13) Cu50 19 aMA2
transmission value output range
■ Monitoring Mode 2-14
output
ExI0 SP
0P No extension 4 - 20 mA
specification: 2 TC-J (8) TC-N (14) Cu10 20 aMV1
Analog Input TC-E (9) TC-C 15 JPt1 21 aMV2
Parameter Display Default Setting range Condition extension 02) 5P ±5% extension 3.2 - 20.8 mA 301001 (03E8) IN-P 3
specification
10P ±10% extension 2.4 - 21.6 mA 4 TC-T (10) TC-L 16 DPt5 22 A-V1
AL1 alarm
1-1 [Alarm output model] 5 TC-R (11) TC-U 17 DPt1 23 A-V2
temperature Sensor input: within using range
AL1 09(9
2-15/17/19/21 □□□ • The setting values in '( )' parenthesis can be set only in
AL2 alarm Analog Input: L-SC ≤ AL□ ≤ H-SC 'Input specification expansion' mode. Refer to 'Mode
1-2 AL-1/2/3/4 AL1 alarm AT0: Off
temperature 2-15 - Setting'.
operation AT1: Absolute high limit alarm
AL2 09(9
alarm
AL3 alarm operation: AT2: Absolute low limit alarm Temperature
1-3 301002 (03E9) UNIT 0: ℃, 1: ℉ • The bar LED for the alarm value flashes. • AL1/2: • AL3/4:
temperature [4 alarm output model] AT!A SBA: Sensor break alarm unit
AL3 00)1
AT1, AT2
AL4 alarm Same as 1-1/2 AL1/2 alarm temperature
AL-1
□□□.■ ■ 301003 (03EA) Low limit Input Low limit alarm High limit alarm
1-4 Same as parameter setting range
L-RG
temperature A: Standard alarm B: Alarm latch 301004 (03EB) High limit Input
■ Scale value relation
AL4 00)1 H-RG
Check only (not available to set) AL1 alarm C: Standby D: Alarm latch and 301005 (03EC) Decimal point dP 0: 0, 1: 0.0, 2: 0.00, 3: 0.000
2-16 -
1-5 High peak ---- Displays high/low peak (Max./Min. option sequence standby sequence 301006 (03ED) Low limit scale
Same as parameter setting range Below is relation example of input specification, high/low limit input, high/low limit
L-SC
•E  nter to option setting: Press [◀] key
hPEK
input) value 301007 (03EE) High limit scale
in 2-15 AL-1 alarm operation. scale, bar graph display high/low limit scale, 4/20 mA transmission output scale when
H-SC
• Initial high/low peak is saved after 2 sec - Bar graph
from supplying the power. AL2 alarm 301008 (03EF) display low limit using 4 to 20 mA input specification.
2-17 [Alarm output model]
1-6 Low peak operation
L-BS
---- • V alue reset: [▲] + [▼] key over 3 sec in scale
AT!A Same as 2-15/16 AL1 alarm operation/ - Same as parameter setting range Refer to 'Parameter Setting' for the details about setting range and condition.
lPEK
1-5/6 High/Low peak parameter AL2 alarm Bar graph
AL-2
2-18 option
option 301009 (03F0) display high
Input specification
H-BS
AL3 alarm limit scale
2-19
operation Bar graph
301010 (03F1) BAR 0: Full bar, 1: Center bar
AL3 alarm display method High/Low limit input
AL-3 AT@A
2-20 [4 alarm output model]
option 4 mA
Same as 2-15/16 AL1 alarm operation/ - 301011 (03F2) transmission
AL4 alarm
2-21 option
lOUT
operation output scale
Same as parameter setting range High/Low limit scale
AL4 alarm
AL-4 AT@A 20 mA
2-22 301012 (03F3) transmission
option hOUT
2-15/17/19/21 output scale
Input and Bar graph display
AL-1/2/3/4
2-23
Alarm output
001 001 to 999 alarm transmission Same as each high/low limit scale
hysteresis 301013 (03F4) ExIO 0: 0 %, 1: 5 %, 2: 10 %
output
A-HY
operation: AT1, parameter setting
extension
AT2 condition
301014 (03F5) AL-1 1: Absolute high limit alarm , 4/20 mA transmission
2-1 Input AL 1 to 4
Input special LIN: Linear, ROOT: Root, SQAR: to - 2: Absolute low limit alarm, output scale
2-24 specification: alarm operation
function Square, TUF: Two unit function 301017 (03F8) AL-4 3: Sensor break alarm, 4: Off
InSF LIN
Analog
Input digital 01 (OFF) to 16 10: Standard alarm, 11: Alarm latch,
2-25 - 301018 (03F9)
filter • It does not affect the display cycle. AL 1 to 4 12: Standby sequence, 13: Alarm
AL-1
to
MAvF 04
Digital input * 2-16/18/20/22 alarm option latch and standby sequence,
-
301021 (03FC)
2-26 HOLD HOLD: Hold, ZERO: Zero-point 14: No alarm (not settable)
Terminal AL1/2/3/4
DI-T AL-4
adjustment, AL.RE*: Alarm reset Alarm output
Digital input Alarm option: 301022 (03FD) A-HY Same as parameter setting range
2-27 HOLD *[Alarm output model] hysteresis
key B, D
DI-K
Sensor break [Transmission output model] Input special 0: Linear, 1: Root, 2: Square,
2-28 - 301023 (03FE)
alarm output OFF: 4 mA, ON: 20 mA function 3: Two unit function
BURN OFF InSF

Comm. [Communication output model] 301024 (03FF) Input correction IN-B Same as parameter setting range
2-29 - Input digital
address 01 to 99 301025 (0400) MAvF Same as parameter setting range
ADRR 01
[Communication output model] filter
2-30 Comm. speed - Digital input
9600, 4800, 2400, 1200 bps 301026 (0401) DI-T 0: Alarm reset, 1: Hold,
BAUD 9600
OFF Terminal
2: Zero-point adjustment
LOC1: P rogram mode lock (check 301027 (0402) Digital input key DI-K
only) Sensor break
301028 (0403) BURN 0: 20 mA, 1: 4 mA
Monitoring mode unlock alarm output
2-31 Lock - 301029 (0404) Comm. address ADDR Same as parameter setting range
LOC2: Checking and setting program
LOC OFF
mode lock 301030 (0405) Comm. speed BAUD 0: 9600, 1: 4800, 2: 2400, 3: 1200
Monitoring mode setting lock 301031 (0406) Lock LOCK 0: OFF, 1: LOC1, 2: LOC2
(check only)
01) When '2-24 input special function' parameter is set to 'TUF', the function corrects the atmospheric pressure input
value.
02) Extension is not allowed below 0 mA and 0 V. ±1 V and 10 V inputs cannot be set to 10P.

18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002


www.autonics.com | +82-2-2048-1577 | sales@autonics.com