Datasheet
Bently Nevada Machinery Condition Monitoring
Description
Transducer System
The 3300 XL 11 mm Proximity Transducer System consists of:
l 3300 XL 11 mm probe
l 3300 XL 11 mm extension cable
l 3300 XL 11 mm Proximitor Sensor1
Document: 146256
Rev. J
3300 XL 11mm Proximity Transducer System
Datasheet
protection against electrostatic discharge, take 3300 XL 11 mm probe comes standard with a
reasonable precautions to avoid electrostatic locknut with predrilled safety wire holes.
discharge during handling.
Notes:
Proximitor Sensor
1. Proximitor Sensors are supplied by
The 3300 XL 11 mm Proximitor Sensor has the default from the factory calibrated to AISI
same advanced features found in the 3300 XL 8 4140 steel. Calibration to other target
mm Proximitor Sensor. Its thin design allows it materials is available upon request.
to be mounted in either a high-density DIN-rail 2. Silicone tape is also provided with each
installation or a more traditional panel mount 3300 XL extension cable and can be used
configuration. Improved RFI/EMI immunity instead of connector protectors. Silicone
allows the 3300 XL Proximitor Sensor to achieve tape is not recommended in applications
European CE mark approvals without any special where the probe-to-extension cable
mounting considerations. This RFI immunity connection will be exposed to turbine oil.
also prevents the transducer system from being
adversely affected by nearby high frequency
radio signals. SpringLoc terminal strips on the
Proximitor Sensor require no special installation
tools and facilitate faster, highly robust field
wiring connections.
Proximity Probe and Extension Cable
The 3300 XL 11 mm probe comes in varying
probe case configurations, including armored
and unarmored ½-20, 5 ⁄ 8 -18, M14 X 1.5 and
M16 X 1.5 probe threads. The reverse mount
3300 XL 11 mm probe comes standard with
either 3 ⁄ 8 -24 or M10 X 1 threads. All
components of the transducer system have
gold-plated brass ClickLoc connectors. ClickLoc
connectors lock into place, preventing the
connection from becoming loose. The
patented TipLoc molding method provides a
robust bond between the probe tip and the
probe body. The probe cable is securely
attached to the probe tip utilizing our patented
CableLoc design that provides 330 N (75 lb) pull
strength.
3300 XL Probes and Extension Cables can also
be ordered with a FluidLoc cable option. This
option prevents oil and other liquids from
leaking out of the machine through the cable’s
interior. The connector protector option
provides additional protection of the
connectors in a humid or moist environment.
Connector protectors are recommended for all
installations and provide increased
environmental protection2 . Additionally, the
Unless otherwise noted, the following Extension 69.9 pF/m (21.3 pF/ft) typical
specifications are for a 3300 XL 11 mm cable
Proximitor Sensor, extension cable and probe capacitance
between 0°C and +45°C (+32°F to +113°F), with Field wiring 0.2 to 1.5 mm2 (16 to 24 AWG) [0.25
a -24 Vdc power supply, a 10 kW load, our to 0.75 mm2 (18 to 23 AWG) with
supplied AISI 4140 steel target that is 31 mm ferrules]. Recommend using three-
(1.2 in) diameter or larger, and a probe gap of conductor shielded triad cable.
2.5 mm (100 mils). The system accuracy and Maximum length of 305 meters
interchangeability specifications do not apply (1,000 feet) between the 3300 XL
when using a transducer system calibrated to Proximitor Sensor and the monitor.
any target other than our AISI 4140 steel target. See the frequency response graph
for signal rolloff at high frequencies
Electrical when using longer field wiring
lengths.
Proximitor Sensor Linear Range 4.0 mm (160 mils). Linear range
Input Accepts one non-contacting 3300 XL begins at approximately 0.5 mm (20
11 mm Proximity Probe and mils) from target and is from 0.5 to
Extension Cable. 4.5 mm (20 to 180 mils)
(approximately –1 to –17 Vdc).
Power Requires -17.5 Vdc to -26 Vdc
Extended Deviation from Straight
without barriers at 12 mA maximum
Line (DSL) range is from
consumption, -23 Vdc to -26 Vdc
approximately 0.5 to 5.0 mm (20 to
with barriers. Operation at a more
200 mils) (–1 to –19 Vdc). The
positive voltage than -23.5 Vdc can
extended DSL range is not
result in reduced linear range.
applicable when using zener
Supply Less than 2 mV change in output barriers.
Sensitivity voltage per volt change in input
Recommended 2.5 mm (100 mils)
voltage.
Gap Setting
Output 50 Ω
Incremental 3.94 V/mm (100 mV/mil) ±10%
resistance
Scale Factor including interchangeability error
(ISF) when measured in increments of 0.5
Probe dc resistance mm (20 mils) over the 4.0 mm (160
Probe Length Resistance from the Center mil) linear range.
(m) Conductor to the Outer Conductor Deviation from best fit straight line (DSL)
(RPROBE ) (ohms)
Standard DSL Less than ±0.10 mm (±4 mils).
1.0 5.9 ± 0.5 range
5.0 7.2 ± 0.8 Extended DSL Less than ±0.15 mm (±6 mils).
9.0 8.5 ± 1.1 range
System Over a probe temperature range of
Extension cable dc resistance Performance -35°C to +120°C (-31°F to +248°F)
Length of Resistance from Resistance from over extended with the Proximitor Sensor and
Extension Center Conductor Coaxial Conductor temperatures extension cable between 0°C to
Cable (m) to Center to Coaxial +45°C (+32°F to +113°F), the ISF
Conductor (RCORE) Conductor (RJACKET) remains within ±25% of 3.94 V/mm
(ohms) (ohms)
Output voltage in mil pp/gauss Reverse mount 22.6 N•m 7.5 N•m
probes
Gap Proximitor Probe Ext. Cable (200 in•lb) (66 in•lb)
Sensor
Connector-to-connector torque
Environmental Limits
Probe Temperature Range
Operating -52°C to +177°C (-62°F to +351°F)
and Storage
Temperature
Exposing the probe to temperatures below -34°C (-
30°F) may cause premature failure of the pressure
seal.
Extension Cable Temperature Range
Operating -52°C to +177°C (-62°F to +351°F)
and Storage
Temperature
Proximitor Sensor Temperature Range
Compliance and Certifications nA, ec: Class I, Zone 2: AEx/Ex nA IIC T4/T5
Gc;
When installed Class I, Division 2, Groups A, B, C,
FCC without and D;
barriers per Class I, Zone 2: AEx/Ex ec llC T4/T5
This device complies with part 15 of the drawing Gc;
FCC Rules. Operation is subject to the 140979. Class I, Division 2, Groups A, B, C,
following two conditions: and D;
l This device may not cause harmful
interference. T5 @ Ta= -55 ˚C to + 40 ˚C
l This device must accept any T4 @ Ta= -55 ˚C to + 80˚C
interference received, including
interference that may cause
undesired operation. 3300 XL Probe
EMC ia: Class I, Zone 0: AEx/Ex ia IIC T5...T1
EN 61000-6-2 Ga;
When installed Class 1, Groups A, B. C, and D,
EN 61000-6-4 with Class II, Groups E, F, and G,
intrinsically Class III;
EMC Directive 2014/30/EU safe zener
barriers per (see Temperature Schedule) table
RoHS drawing to follow)
141092 or
RoHS Directive 2011/65/EU when installed
with galvanic
Maritime isolators.
ABS 2009 Steel Vessels Rules nA, ec: Class I, Zone 2: AEx/Ex nA IIC T5…T1
Gc;
1-1-4/7.7,4-8-3/1.11.1,4-9-7/13 When installed Class 1, Division 2, Groups A, B, C, D;
without Class 1, Zone 2: AEx/Ex ec llC T5…T1
barriers per Gc; Class I, Division 2, Groups A, B,
drawing C, and D;
Hazardous Area Approvals 140979.
(see Temperature Schedule table to
CSA/NRTL/C follow)
ia:
II 1 G
Ex ia IIC T4/T5 Ga
Ex ia IIIC T90C/T105C Dc
For EPL Dc: Temperature Schedule
Figure 10: Frequency Response, phase change of typical 3300 XL 11mm System
with various lengths of field wiring, no barriers
Note: Connector Protector only installed on female end when optioned. Both ends available as
accessories.