You are on page 1of 27

NFPA® 13 : Standard for the Installation of Sprinkler Systems - 2013 Edition

Project Name MAINTENANCE WAREHOUSE

Address PLTU CIREBON

City CIREBON

Contract No. ( ID ) -

Date 04-Apr-23

Name of contractor PT. ACHIVON PRESTASI ABADI

Name of designer ILHAM KELANA

Address KAWASAN INDUSTRI KRAKATAU CILEGON

Hazard classification : Light Hazard Occupancies

Area coverage by sprinkler(As) : 200 ft² selected from tables As hazard type

Density(D) : 0.15 gpm/ft² By Default=0.15

Total area protection(Ap) : 9360 ft² figure 7-2.3.1.2 area/density curves.

K factor 5.6 Remember: you need 1/2 in. Sprinkler Orifice

Number of sprinkler = Ap/As 47 sprinkler

Flow rate per sprinkler(Qs)= D * As 30 gpm

P residual = 28.699 psi

Pipe material Black steel (wet systems including deluge)

Hazen–Williams C Values 120


Hady Habib's Hydraulic calculation sheet useing NFPA® 13 : Standard for the Installation of Sprinkler Systems - 2013 Edition Nicearb@yahoo.com
Pipe Fitting and Equivalence Length(ft) Friction loss pressure
path Q(gpm) D(in) Qyt. P(psi) Notes
Length(ft) Devices Length (ft) Total (Psi/ft) friction(Psi)
90° standard elbow 5 18 P2 = 28.705 Psi
Butterfly valve 3 12 k = 5.6
1-2 30 8 in. 1 446 1.407905E-05 0.006279257 28.705259
Swing check* 7 45 Q2 = 30.003 gpm
Gate valve 1 4
90° standard elbow 1 5 P3 = 29.249 Psi
45° elbow 3 2 k = 5.6
2-3 60.003 2 in. 1 15 0.036266138 0.543992064 29.249251
none 0 Q3 = 30.286 gpm
90° long-turn elbow 1 3
Tee or cross (flow turned 90°) 100 15 P4 = 46.391 Psi
45° elbow 4 3 k = 5.6
3-4 90.290 3 in. 1 1513 0.011329699 17.14183449 46.391085
none 0 Q4 = 38.142 gpm
none 0
90° standard elbow 1 10
Butterfly valve 70 12
4-a 128.432 4 in. 1 1071 0.005779112 6.189428683 52.580514
none 0
Swing check* 10 22

90° standard elbow 1 2 P6 = 29.522 Psi


none 0 k = 5.6
5-6 30 1 in. 1 3 0.274243008 0.822729025 29.521709
none 0 Q6 = 30.427 gpm
none 0
90° standard elbow 1 2 P7 = 32.527 Psi
none 0 k = 5.6
6-7 60.427 1 in. 1 3 1.001701484 3.005104452 32.526813
none 0 Q7 = 31.938 gpm
none 0
90° standard elbow 1 2 P8 = 39.115 Psi
none 0 k = 5.6
7-8 92.365 1 in. 1 3 2.196091641 6.588274922 39.115088
none 0 Q8 = 35.024 gpm
none 0
90° standard elbow 1 2
none 0
8-a 127.389 1 in. 1 3 3.980639212 11.94191764 51.057006
none 0
none 0 Qa = 129.275 gpm

90° standard elbow 1 2


none 0
a-b 257.707 1 in. 1 3 14.65697957 43.97093872 96.551453
none 0
none 0
Hady Habib's Hydraulic calculation sheet useing NFPA® 13 : Standard for the Installation of Sprinkler Systems - 2013 Edition Nicearb@yahoo.com
Pipe Fitting and Equivalence Length(ft) Friction loss pressure
path Q(gpm) D(in) Qyt. P(psi) Notes
Length(ft) Devices Length (ft) Total (Psi/ft) friction(Psi)
90° standard elbow 1 10 P10 = 28.703 Psi
none 0 k = 5.6
9-10 30 4 in. 1 11 0.000392186 0.004314044 28.703294
none 0 Q10 = 30.002 gpm
none 0
90° standard elbow 1 2 P11 = 31.669 Psi
none 0 k = 5.6
10-11 60.002 1 in. 1 3 0.988715285 2.966145855 31.669439
none 0 Q11 = 31.514 gpm
none 0
90° standard elbow 1 6 P12 = 31.904 Psi
none 0 k = 5.6
11-12 91.517 2 1/2 in. 1 7 0.033496057 0.234472402 31.903912
none 0 Q12 = 31.631 gpm
none 0
90° long-turn elbow 1 2
none 0
12-b 123.147 1 in. 1 3 3.738934264 11.21680279 43.120715
none 0
none 0 Qb = 184.273 gpm

90° standard elbow 1 27


Tee or cross (flow turned 90°) 3 60
b-c 441.980 12 in. 1 208 0.000286838 0.059662303 96.611115
none 0
none 0

90° standard elbow 1 27


Butterfly valve 3 21
c-d 441.980 1 in. 1 440 39.76086857 17494.78217 17591.393
Gate valve 4 6
Swing check* 5 65

90° standard elbow 1 27


none 0
d-e 441.980 1 in. 1 28 39.76086857 1113.30432 18704.698
none 0
none 0

90° standard elbow 1 27


none 0
e-f 441.980 1 in. 1 28 39.76086857 1113.30432 19818
none 0
none 0

P friction and residual = 1366.403 bar P static = 1.650485437 bar P total = 1368.054 bar
Hydraulic Calculations
for
MAINTENANCE WAREHOUSE
PLTU CIREBON - CIREBON
Contract No. - Date 04-Apr-23
Design data:
Occupancy classification Light Hazard Occupancies Density 0.15 gpm/ft²
Area of application 9360 ft² Coverage per sprinkler 200 ft² No. of sprinklers calculated 47
Hose streams 30 gpm Total water required including hose streams 442 gpm
Name of contractor PT. ACHIVON PRESTASI ABADI
Name of designer ILHAM KELANA
Address KAWASAN INDUSTRI KRAKATAU CILEGON
Authority having jurisdiction
Hady Habib's Hydraulic calculation sheet
using NFPA® 13 : Standard for the Installation of Sprinkler Systems - 2013 Edition

Fittings Quantities Takeoff

Nicearb@yahoo.com
Item Description Unit Qyt. Rate Total
1/2 in. 45° elbow Pcs 0 50.00 0
3/4 in. 45° elbow Pcs 0 30.00 0
1 in. 45° elbow Pcs 0 17.00 0
1 1/4 in. 45° elbow Pcs 0 25.00 0
1 1/2 in. 45° elbow Pcs 0 30.00 0
2 in. 45° elbow Pcs 3 37.00 111.00
2 1/2 in. 45° elbow Pcs 0 43.50 0
3 in. 45° elbow Pcs 4 50.00 200.00
3 1/2 in. 45° elbow Pcs 0 56.50 0
4 in. 45° elbow Pcs 0 63.00 0
5 in. 45° elbow Pcs 0 69.50 0
6 in. 45° elbow Pcs 0 76.00 0
8 in. 45° elbow Pcs 0 82.50 0
10 in. 45° elbow Pcs 0 89.00 0
12 in. 45° elbow Pcs 0 95.50 0
1/2 in. 90° standard elbow Pcs 0 10.00 0
3/4 in. 90° standard elbow Pcs 0 20.00 0
1 in. 90° standard elbow Pcs 9 17.00 153.00
1 1/4 in. 90° standard elbow Pcs 0 25.00 0
1 1/2 in. 90° standard elbow Pcs 0 30.00 0
2 in. 90° standard elbow Pcs 1 15.00 15.00
2 1/2 in. 90° standard elbow Pcs 1 21.50 21.50
3 in. 90° standard elbow Pcs 0 21.40 0
3 1/2 in. 90° standard elbow Pcs 0 21.30 0
4 in. 90° standard elbow Pcs 2 21.20 42.40
5 in. 90° standard elbow Pcs 0 21.10 0
6 in. 90° standard elbow Pcs 0 21.00 0
8 in. 90° standard elbow Pcs 5 20.90 104.5
10 in. 90° standard elbow Pcs 0 20.80 0
12 in. 90° standard elbow Pcs 1 20.70 20.70
1/2 in. 90° long-turn elbow Pcs 0 30.00 0
3/4 in. 90° long-turn elbow Pcs 0 14.00 0
1 in. 90° long-turn elbow Pcs 1 45.00 45.00
1 1/4 in. 90° long-turn elbow Pcs 0 44.67 0
1 1/2 in. 90° long-turn elbow Pcs 0 52.17 0
2 in. 90° long-turn elbow Pcs 1 59.67 59.666666667
2 1/2 in. 90° long-turn elbow Pcs 0 67.17 0
3 in. 90° long-turn elbow Pcs 0 39.00 0
3 1/2 in. 90° long-turn elbow Pcs 0 60.00 0
4 in. 90° long-turn elbow Pcs 0 59.67 0
5 in. 90° long-turn elbow Pcs 0 64.67 0
6 in. 90° long-turn elbow Pcs 0 69.67 0
8 in. 90° long-turn elbow Pcs 0 74.67 0
Hady Habib's Hydraulic calculation sheet
using NFPA® 13 : Standard for the Installation of Sprinkler Systems - 2013 Edition

Fittings Quantities Takeoff

Nicearb@yahoo.com
Item Description Unit Qyt. Rate Total
10 in. 90° long-turn elbow Pcs 0 33.00 0
12 in. 90° long-turn elbow Pcs 0 40.00 0
1/2 in. Tee or cross (flow turned 90°) Pcs 0 10.00 0
3/4 in. Tee or cross (flow turned 90°) Pcs 0 55.56 0
1 in. Tee or cross (flow turned 90°) Pcs 0 44.83 0.00
1 1/4 in. Tee or cross (flow turned 90°) Pcs 0 44.83 0
1 1/2 in. Tee or cross (flow turned 90°) Pcs 0 44.83 0
2 in. Tee or cross (flow turned 90°) Pcs 0 44.83 0
2 1/2 in. Tee or cross (flow turned 90°) Pcs 0 44.83 0
3 in. Tee or cross (flow turned 90°) Pcs 100 54.80 5480.37
3 1/2 in. Tee or cross (flow turned 90°) Pcs 0 53.69 0
4 in. Tee or cross (flow turned 90°) Pcs 0 52.58 0
5 in. Tee or cross (flow turned 90°) Pcs 0 51.47 0
6 in. Tee or cross (flow turned 90°) Pcs 0 49.22 0
8 in. Tee or cross (flow turned 90°) Pcs 0 51.52 0
10 in. Tee or cross (flow turned 90°) Pcs 0 47.00 0
12 in. Tee or cross (flow turned 90°) Pcs 3 60.00 180.00
1/2 in. Butterfly valve Pcs 0 40.00 0
3/4 in. Butterfly valve Pcs 0 80.00 0
1 in. Butterfly valve Pcs 3 48.08 144.25
1 1/4 in. Butterfly valve Pcs 0 48.08 0
1 1/2 in. Butterfly valve Pcs 0 48.08 0
2 in. Butterfly valve Pcs 0 48.08 0
2 1/2 in. Butterfly valve Pcs 0 48.08 0
3 in. Butterfly valve Pcs 0 105.19 0
3 1/2 in. Butterfly valve Pcs 0 91.66 0
4 in. Butterfly valve Pcs 70 78.14 5469.5925926
5 in. Butterfly valve Pcs 0 64.61 0
6 in. Butterfly valve Pcs 0 46.06 0
8 in. Butterfly valve Pcs 3 47.61 142.81666667
10 in. Butterfly valve Pcs 0 19.00 0
12 in. Butterfly valve Pcs 0 32.25 0
1/2 in. Gate valve Pcs 0 5.00 0
3/4 in. Gate valve Pcs 0 40.00 0
1 in. Gate valve Pcs 4 51.33 205.33
1 1/4 in. Gate valve Pcs 0 51.33 0
1 1/2 in. Gate valve Pcs 0 51.33 0
2 in. Gate valve Pcs 0 51.33 0
2 1/2 in. Gate valve Pcs 0 51.33 0
3 in. Gate valve Pcs 0 119.57 0
3 1/2 in. Gate valve Pcs 0 101.94 0
4 in. Gate valve Pcs 0 84.30 0
5 in. Gate valve Pcs 0 66.67 0
Hady Habib's Hydraulic calculation sheet
using NFPA® 13 : Standard for the Installation of Sprinkler Systems - 2013 Edition

Fittings Quantities Takeoff

Nicearb@yahoo.com
Item Description Unit Qyt. Rate Total
6 in. Gate valve Pcs 0 42.89 0
8 in. Gate valve Pcs 1 43.69 43.688888889
10 in. Gate valve Pcs 0 7.62 0
12 in. Gate valve Pcs 0 23.53 0
1/2 in. Swing check* Pcs 0 58.00 0
3/4 in. Swing check* Pcs 0 96.67 0
1 in. Swing check* Pcs 5 88.25 441.25
1 1/4 in. Swing check* Pcs 0 79.83 0
1 1/2 in. Swing check* Pcs 0 71.42 0
2 in. Swing check* Pcs 0 63.00 0
2 1/2 in. Swing check* Pcs 0 54.58 0
3 in. Swing check* Pcs 0 46.17 0
3 1/2 in. Swing check* Pcs 0 37.75 0
4 in. Swing check* Pcs 10 29.33 293.33333333
5 in. Swing check* Pcs 0 99.57 0
6 in. Swing check* Pcs 0 78.38 0
8 in. Swing check* Pcs 7 57.19 400.33
10 in. Swing check* Pcs 0 36.00 0
12 in. Swing check* Pcs 0 14.81 0

The total price of fittings is 13,573.73


Here you can add and edit the fittings prices as you wish
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 1/2 in. 3/4 in. 1 in. 1 1/4 in. 1 1/2 in. 2 in. 2 1/2 in. 3 in. 3 1/2 in. 4 in. 5 in. 6 in. 8 in. 10 in. 12 in.
2 45° elbow 50.00 30.00 17.00 25.00 30.00 37.00 43.50 50.00 56.50 63.00 69.50 76.00 82.50 89.00 95.50
3 90° standard elbow 10.00 20.00 17.00 25.00 30.00 15.00 21.50 21.40 21.30 21.20 21.10 21.00 20.90 20.80 20.70
4 90° long-turn elbow 30.00 14.00 45.00 44.67 52.17 59.67 67.17 39.00 60.00 59.67 64.67 69.67 74.67 33.00 40.00
5 Tee or cross (flow turned 90°) 10.00 55.56 44.83 44.83 44.83 44.83 44.83 54.80 53.69 52.58 51.47 49.22 51.52 47.00 60.00
6 Butterfly valve 40.00 80.00 48.08 48.08 48.08 48.08 48.08 105.19 91.66 78.14 64.61 46.06 47.61 19.00 32.25
7 Gate valve 5.00 40.00 51.33 51.33 51.33 51.33 51.33 119.57 101.94 84.30 66.67 42.89 43.69 7.62 23.53
8 Swing check* 58.00 96.67 88.25 79.83 71.42 63.00 54.58 46.17 37.75 29.33 99.57 78.38 57.19 36.00 14.81
Light Hazard Occupancies.
Classification of Occupancies:
Light Hazard Occupancies
Ordinary Hazard Group 1 Churches
Ordinary Hazard Group 2 Clubs
Extra Hazard Group 1 Eaves and overhangs,
Extra Hazard Group 2 Educational
Special Occupancy (High-Piled) Hazards Hospitals
Institutional

NFPA® 13 Libraries,
Museums
Standard for the Nursing or accomodation

Installation of Sprinkler Offices,


Residential
Systems Restaurant seating areas

2013 Edition Theaters and auditoriums,


Unused attics
Ordinary Hazard Occupancies

Group 1 Group 2
Automobile parking Cereal mills
Bakeries Chemical plants — ordinary
Beverage manufacturing Confectionery products
Canneries Distilleries
Dairy products Dry cleaners
Electronic plants Feed mills
glass products manufacturing Horse stables
Laundries Leather goods manufacturing
Restaurant service areas Libraries — large stack room areas
showrooms Machine shops
Metal working
Mercantile
Paper and pulp mills
Paper process plants
Piers and wharves
Post offices
Printing and publishing
Repair garages
Resin application area
Stages
Textile manufacturing
Tire manufacturing
Tobacco products manufacturing
Wood machining
Wood product assembly
Extra Hazard Occupancies

Group 1 Group 2
Aircraft hangars Asphalt saturating
Combustible hydraulic fluid use areas Flammable liquids spraying
Die casting Flow coating
Metal extruding Manufactured home
Plywood and particles Open oil quenching
Printing Plastics processing
Rubber Solvent cleaning
Saw mills Varnish and paint dipping
Textile All kind
Upholstering with plastic foams
Table 6.2.3.1 Sprinkler Discharge Characteristi

Nominal
K-Factor
[gpm/(psi)1/2]
Table 23.4.4.7.1 Hazen–Williams C Values
Unlined cast or ductile iron 100 1.4
Black steel (dry systems including preaction) 100 1.9
Black steel (wet systems including deluge) 120 2.8
Galvanized steel (dry systems including preaction) 100 4.2
Galvanized steel (wet systems including deluge) 120 5.6
Plastic (listed) all 150 8.0
Cement-lined cast- or ductile iron 140
Copper tube or stainless steel 150
Asbestos cement 140 11.2
Concrete 140

14.0
16.8
19.6
22.4
25.2
28.0
2.3.1 Sprinkler Discharge Characteristics Identification
Percent of
Nominal K-Factor Range K-Factor Range Nominal Thread
K-Factor
[gpm/(psi)1/2] [L/min/(bar)1/2] K-5.6 Type
[L/min/(bar)1/2]
Discharge
20 1.3–1.5 19–22 25 1⁄2 in. NPT
28 1.8–2.0 26–29 33.3 1⁄2 in. NPT
40 2.6-2.9 38–42 50 1⁄2 in. NPT
60 4.0-4.4 57-63 75 1⁄2 in. NPT
80 5.3-5.8 76-84 100 1⁄2 in. NPT
115 7.4-8.2 107-118 140 3/4 in. NPT
0 or
0 1⁄2 in. NPT
160 10.7-11.7 159-166 200 1⁄2 in. NPT
0 or
0 3⁄4 in. NPT
200 13.5-14.5 195-209 250 3⁄4 in. NPT
240 16.0-17.6 231-254 300 3⁄4 in. NPT
280 18.6-20.6 272-301 350 1 in. NPT
320 21.3-23.5 311-343 400 2 in. NPT
360 23.9-26.5 349-387 450 3 in. NPT
400 26.6-29.4 389-430 500 4 in. NPT
Table 8.6.2.2.1(a) Protection Areas and Maximum Spacing of Standard Pendent and Upright Spray Sprinklers for Light Ha

Construction Type

Noncombustible unobstructed
Noncombustible unobstructed
Noncombustible obstructed
Noncombustible obstructed
Combustible unobstructed with no exposed members
Combustible unobstructed with no exposed members
Combustible unobstructed with exposed members 3 ft (0.91 m) or more on center
Combustible unobstructed with exposed members 3 ft (0.91 m) or more on center
Combustible unobstructed with members less than 3 ft (0.91 m) on center
Combustible obstructed with exposed members 3 ft (0.91 m) or more on center
Combustible obstructed with members less than 3 ft (0.91 m) on cente
Combustible concealed spaces in accordance with 8.6.4.1.4

*See 8.6.4.1.4.4.
pright Spray Sprinklers for Light Hazard

Maximum
Maximum Spacing
System Type Protection Area

ft2 m2 ft2 m2
Hydraulically calculated 225 20.9 15 4.6
Pipe schedule 220 18.6 15 4.6
Hydraulically calculated 225 20.9 15 4.6
Pipe schedule 200 18.6 15 4.6
Hydraulically calculated 225 20.9 15 4.6
Pipe schedule 200 18.6 15 4.6
Hydraulically calculated 225 20.9 15 4.6
Pipe schedule 200 18.6 15 4.6
All 130 12.1 15 4.6
All 168 15.6 15 4.6
All 130 12.1 15 4.6
All 120 11.1 15 4.6
Parallel to Parallel to
the slope 10 the slope
perpendicul 3.05
ar to the perpendicul
slop * ar to the
slop *
Table 8.6.2.2.1(b) Protection Areas and Maximum Spacing of Standard Pendent
and Upright Spray Sprinklers for Ordinary Hazard

Maximum
Maximum Spacing
Construction Type System Type Protection Area

ft2 m2 ft2 m2
All All 130 12.1 15 4.6
Table 8.6.2.2.1(c) Protection Areas and Maximum Spacing of Standard Pendent and Upright Spray Sprinklers for
Extra Hazard

Maximum
Maximum Spacing
Construction Type System Type Protection Area

ft2 m2 ft2
All Pipe schedule 90 8.4 12*
All Hydraulically calculated with density ≥0.25 100 9.3 12*
All Hydraulically calculated with density <0.25 130 12.1 15
*In buildings where solid structural members create bays up to 25 ft (7.6 m) wide, maximum spacing between
sprinklers is permitted up to 12 ft 6 in. (3.8 m).
ray Sprinklers for Table 8.6.2.2.1(d) Protection Areas and Maximum Spacing of Standard Pendent and Upright Spray
High-Piled Storage

Maximum
Maximum Spacing Construction
System Type Protection Area
Type

m2 ft2
3.7* All Hydraulically calculated with density ≥0.25 100
3.7* All Hydraulically calculated with density <0.25 130
4.6 *In buildings where solid structural members create bays up to 25 ft (7.6 m) wide, maximum spacin
sprinklers is permitted up to 12 ft 6 in. (3.8 m).
cing between
rd Pendent and Upright Spray Sprinklers for
Table 23.4.3.1.1 Equivalent Schedule 40 Steel Pipe Length Chart

Maximum
Maximum Spacing Fittin
Protection Area

m2 ft2 m2 1/2 in. 3/4 in.


9.3 12* 3.7* fittings and valves (15mm) (20mm)
12.1 15 4.6 45° elbow - 1
7.6 m) wide, maximum spacing between 0.3
90° standard elbow 1 2
0.3 0.6
90° long-turn elbow 0.5 1
0.2 0.3
Tee or cross (flow turned 90°) 3 4
0.9 1.2
Butterfly valve - -

Gate valve - -

Swing check* - -

none
For SI units, 1 in. = 25.4 mm; 1 ft = 0.3048 m.
Note: Information on 1⁄2 in. pipe is included in this table only because it is allo
*Due to the variation in design of swing check valves, the pipe equivalents in
pe Length Chart

Fittings and valves Expressed in Equivlant Feet (Meters) of Pipe

1 in. 1 1/4 in. 1 1/2 in. 2 in. 2 1/2 in. 3 in. 3 1/2 in. 4 in. 5 in.
(25mm) (32mm) (40mm) (50mm) (65mm) (80mm) (90mm) (100mm) (125mm)
1 1 2 2 3 3 3 4 5
0.3 0.3 0.6 0.6 0.9 0.9 0.9 1.2 1.5
2 3 4 5 6 7 8 10 12
0.6 0.9 1.2 1.5 1.8 2.1 2.4 3 3.7
2 2 2 3 4 5 5 6 8
0.6 0.6 0.6 0.9 1.2 1.5 1.5 1.8 2.4
5 6 8 10 12 15 17 20 25
1.5 1.8 2.4 3 3.7 4.6 5.2 6.1 7.6
- - - 6 7 10 - 12 9
1.8 2.1 3 3.7 2.7
- - - 1 1 1 1 2 2
0.3 0.3 0.3 0.3 0.6 0.6
5 7 9 11 14 16 19 22 27
1.5 2.1 2.7 3.4 4.3 4.9 5.8 6.7 8.2

is table only because it is allowed under 8.15.19.4 and 8.15.19.5.


alves, the pipe equivalents indicated in this table are considered average.
0 0 0 0 0
Diameter
(in)
Nominal
Pipe Size  Thickness
(in)
External Internal

6 in. 8 in. 10 in. 12 in. 1/2 in. 0.84 0.62 0.11


(150mm) (200mm) (250mm) (300mm) 3/4 in. 1.05 0.82 0.11
7 9 11 13 1 in. 1.32 1.05 0.13
2.1 2.7 3.4 4 1 1/4 in. 1.66 1.38 0.14
14 18 22 27 1 1/2 in. 1.9 1.61 0.15
4.3 5.5 6.7 8.2 2 in. 2.38 2.07 0.15
9 13 16 18 2 1/2 in. 2.88 2.47 0.2
2.7 4 4.9 5.5 3 in. 3.5 3.07 0.22
30 35 50 60 3 1/2 in. 4 3.55 0.23
9.1 10.7 15.2 18.3 4 in. 4.5 4.03 0.24
10 12 19 21 5 in. 5.56 5.05 0.26
3 3.7 5.8 6.4 6 in. 6.63 6.07 0.28
3 4 5 6 8 in. 8.63 7.98 0.32
0.9 1.2 1.5 1.8 10 in. 10.75 10.02 0.37
32 45 55 65 12 in. 12.75 11.94 0.41
9.5 13.7 16.8 20
Based on ASTM A53 - Standard Specification for Pipe, Ste
none
45° elbow ASTM A53 pipe - also referred to as ASME SA53 pipe - is
water, gas and air lines. Suitable for welding and forming lik
90° standard elbow
90° long-turn elbow
Tee or cross (flow turned 90°)
Butterfly valve
Gate valve
Swing check*
0 0 0 0 0 0 0 0 0
Transverse Areas Length of Pipe Weight
(in2) (per sq. foot of)
Number of
Volume Threads
External (ft3/ft) per inch of
Internal Screw
External Internal Steel Surface Surface (ft) lb/ft kg/m
(ft)

0.55 0.3 0.25 4.55 6.14 0.0021 0.85 1.26 14


0.87 0.53 0.33 3.64 4.64 0.0037 1.13 1.68 14
1.36 0.86 0.49 2.9 3.64 0.006 1.68 2.5 11 ½
2.16 1.5 0.67 2.3 2.77 0.0104 2.27 3.38 11 ½
2.84 2.04 0.8 2.01 2.37 0.0141 2.72 4.04 11 ½
4.43 3.36 1.08 1.61 1.85 0.0233 3.65 5.43 11 ½
6.49 4.79 1.7 1.33 1.55 0.0333 5.79 8.62 8
9.62 7.39 2.23 1.09 1.25 0.0513 7.58 11.27 8
12.56 9.89 2.68 0.95 1.08 0.0687 9.11 13.56 8
15.9 12.73 3.17 0.85 0.95 0.0884 10.79 16.06 8
24.3 20 4.3 0.69 0.76 0.1389 14.61 21.74 8
34.47 28.89 5.58 0.58 0.63 0.2006 18.97 28.23 8
58.42 50.02 8.4 0.44 0.48 0.3552 28.55 42.49 8
90.76 78.85 11.9 0.36 0.38 0.5476 40.48 60.24 8
127.64 111.9 15.74 0.3 0.32 0.7763 53.6 79.77 8

d Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless

to as ASME SA53 pipe - is intended for mechanical and pressure applications. Can be used in steam,
le for welding and forming like coiling, bending and flanging.
0

You might also like