You are on page 1of 2

No.

A7-2-2, Block A, Megan Salak Park


Jalan 2/125E, Taman Desa Petaling
57100 Kuala Lumpur
Tel : 03-9056 3228 Fax : 03-9056 2800 E-mail : tass@topaire.com.my
Website : www.topaire.com.my

Project: GALERI MUZIUM PERDANA LANGKAWI


Equipment : TOPAIRE AIR COOLED DX CHILLER (SCREW COMPRESSOR) - R134A

MODEL:
TAHX 260 D3 (4 NOS) & TAHX 210 D3 (2 NOS)

ITEM UNIT NO MODEL CAPACITY KWI KWI/TR QTY


1 BLOCK A - CH 1 & 2 TAHX 260 D3 253.4 284.4 1.12 2
2 BLOCK B - CH 1 & 2 TAHX 210 D3 203.7 233.5 1.15 2
3 BLOCK C - CH 1 & 2 TAHX 260 D3 253.4 284.4 1.12 2

PRODUCT FEATURES

> A complete factory package which are 100% run tested in the factory.
> Optimized design for Ozine friendly R134a.
> Seme-hermetic twin screw compressor from Bitzer.
> Wide operating range of ambient temperature from 10oC to 52oC.
> Full fuction microprcessor control and user friendly touchable screen panel.
> Offers a wide variety of chiller options that are suitable for different kinds of applications and requirements.
> Easy to Installation, Testing & Commissioning and operation.

PRODUCT BENEFITS

1 Compressor Semi-hermetic Bitzer compressor, with SKF bearing 50,000hrs stable operation
2 DX Shell & Tube Evaporator Improve the heat transfer coefficient, strengthen the heat trasnfer
Water flows more smoothly and there is less vibration and noise
No heat transfer dead area, all the transfer area can be used, good for avoid freezing
Without any oil problem especially in lower part load
Significantly lower water pressure drop (about 30% lower at the same flow rate)
3 Air Cooled Condenser W shape condenser increase the heat exchange as well as imorove the serviceability
High efficiency seamless innver groove copper tube
4 Hydrophilic Aluminium Fins More eco-friendly
Better hydrophilicity, better performance
Enhance corrosion resistance performance
Increase pollution resistance
Reduce dust adhesion
5 Electronic Expansion Valve High precise control
Real PID modulation (Proportion Integration Differentiation)
6 7" colorful Touch Screen Easy operation, Full automatically, Password protection, Schneider brand
Multi languages, Power-down memory function, Weekly operation scheduling
7 Remote control cabinet Installed in the control room. Through the cable connected to the unit touch screen,
it can display all states information and complete all the operations of unit
(startup / shutdown, error, etc) Communication distance up to 500 m
No.A7-2-2, Block A, Megan Salak Park
Jalan 2/125E, Taman Desa Petaling
57100 Kuala Lumpur
Tel : 03-9056 3228 Fax : 03-9056 2800 E-mail : tass@topaire.com.my
Website : www.topaire.com.my

Project: GALERI MUZIUM PERDANA LANGKAWI


Equipment : TOPAIRE AIR COOLED DX CHILLER (SCREW COMPRESSOR) - R134A

ADVANTAGES OF AIR COOLED SCREW CHILLER

1 Simple structure, fewer moving parts, less wearing parts, low failure rate and long life screw compressor
2 Screw compressor has a smooth circulation motion, no surge phenomenon during the low load operation,
low noise and low vibration
3 Compact unit structure, and convenient maintenance
4 Cool efficiently according to building capacity
5 Ocupacy very less space for installation of plant

DISADVANTAGES OF AIR COOLED MODULAR CHILLER

1 Required more installation of fittings and chilled water pipe that contribute to higher cost
2 Bigger foot print and require more space
3 High requirement for water quality. Once scaling and blocking, it will affect the heat transfer of the evaporator
4 Low compression ratio and small single cooling capacity
5 Poor adjustment performance under partial load of a single head, no stepless adjustment