Boiler Failure Investigation Framework

Step 1
Damage Type Area/Pattern
Tube Crack Welding
Transverse
(Along the circumference)
Longitudinal
(Along the length)
Burst Water Side to Fire Side (Fish mouth thin
lip)
Water Side to Fire Side (Fish mouth
thick lip)
Fire Side to Water Side
Corroded Water Side
Fire Side
Distortion Hogging
Sagging
Random
Oxidized/Melted Fireside
Furnace Crack Refractory
Body
Bulge Body
Refractory
Collapse Body
Drum Crack Welding
Body
Collapse Body
Explode Body
Corroded Internal Sections
Step 2
Specific Damage Condition Cause
Tube-welding-crack Short term overheating Undetected prolonged water
starvation during operation
Hydrogen embrittlement Manufacturing defect
(occurs in 1-5 years of usage)
Material thickness difference Manufacturing defect
(Occurs in 1-5 years of usage)
Tube-transverse-crack Material failure Manufacturing defect
(Occurs in 1-5 years of usage)
Long term overheating Scaling (water side)
(abnormal) Soot deposition
Contaminant in boiler water
(eg. Oil)
Tube-longitudinal-crack Propagation from tube Refer to tube-welding-crack
weldment
Long term overheating Scaling (water side)
(abnormal) Soot deposition
Contaminant in boiler water
(eg. Oil)
Material failure Manufacturing defect
(Occurs in 1-5 years of usage)
Tube-burst-waterside to Long term overheating Scaling
fireside (fish mouth thin (abnormal) Soot deposition
lip) Contaminant in boiler water
(eg. Oil)
Long term overheating Maximum cyclic load
(normal) exceeded
Tube-burst-waterside to Short term overheating Undetected prolonged water
fireside (fish mouth thick starvation
lip)
Tube-corroded-waterside Corrosive boiler water Boiler water ph
Boiler water oxygen content
Tube-corroded-fireside Heat assisted oxidation Soot deposition
Chemical oxidation Steam leak
Tube-distortion-hogging Explosion Fuel leak
Improper combustion
Improper purge
Long term overheating End of life span
(normal)
Tube support failure Corrosion of tube supports
Short term overheating (initial Undetected prolonged water
stage) starvation during operation
Tube-distortion-sagging Implosion (rare circumstances) Vacuum in system
Tube support failure Corrosion on tube supports
Long term overheating End of lifespan
(normal)
Short term overheating (initial Undetected prolonged water
stage) starvation during operation
Tube-distortion-random Thermal shock Wrong low water level
condition recovery

Non gradual admittance of


feed water

Tube-oxidized-melted Meltdown/fire Final stage of undetected


overheating

Furnace-crack-refractory Explosion/fire (low to medium Fuel leak


magnitude) Improper combustion
Improper purge
Improper repair/installation Refractory- insufficient
(if installation then should be settling time/
within 1-5 years of usage) Manufacturing defect
Wrong selection of refractory
type/
Manufacturing defect
Water wall tube distortion Refer to tube-distortion
Implosion Vacuum
Furnace-crack-body Improper welding Manufacturing defect
(Occurs in 1-5 years of usage)
Explosion (medium to high Fuel leak
magnitude) Improper combustion
Improper purge
Furnace-bulge-body Explosion (medium Fuel leak
magnitude) Improper combustion
Improper purge
Improper material selection Manufacturing defect
Furnace-bulge-refractory Improper repair/installation Refractory- insufficient
(if installation then should be settling time/
within 1-5 years of usage) Manufacturing defect
Wrong selection of refractory
type/
Manufacturing defect
Implosion Vacuum
Furnace-collapse-body Implosion Vacuum
Short term overheating (if fire Undetected prolonged water
tube boiler) starvation during operation
Drum-crack-welding Hydrogen embrittlement Manufacturing defect
(occurs in 1-5 years of usage)
Material thickness difference Manufacturing defect
(occurs in 1-5 years of usage)
Drum-collapse-body Implosion Vacuum
Drum-explode-body Overpressure Steam pressure exceeding 10
to 20 % above rated capacity
Drum-corroded-internal Corrosive boiler Boiler water ph
section water/condensate Boiler water oxygen content
Step 3
Cause Origin
Undetected prolonged water starvation Water supply valve failure (feed water valve)
during operation Water supply valve actuating mechanism
failure
Water supply pump failure (feed pump)
Water level transmitter failure
Water level receiver failure
Automation or automation sequence failure
Non gradual admittance of feed water Faulty feed water valve actuator
Faulty feed water valve
Automation or automation sequence failure
Manual recovery method failure
Wrong water level recovery Check method of recovery
Scaling Inadequate or no water treatment
Soot deposition Inadequate air supply ratio
Inadequate fuel supply ratio
Inadequate maintenance
Non-suitable fuel usage
Contaminant in boiler water Heating coil leakage
Ingress through cascade or expansion tank
Breach through or steam consumer
Water ph and oxygen content Inadequate or no water treatment
Steam leak Boiler tube crack (find cause using
framework)
Steam pressure exceeding 10 to 20 % of Safety valve failure
rated capacity
Vacuum Boiler vent valve failure or error in operating
boiler vent valve
Steam drum vortex eliminator failure
Fuel leak Burner nozzle failure
Fuel release valve failure
Automation sequence failure
High fuel ratio
Improper combustion Inadequate air supply ratio
Inadequate fuel ratio
Water content in oil
Improper atomization (for liquid fuel)
Improper pulverization (for coal dust)
Improper flame propagation (dirty or
damaged swirler)

Improper purge Failure of air supply fan (force draught fan)


Failure or fault in force draught fan air vanes
Automation sequence failure
If controlled manually, then check set values
by operator (to match with manufacturer
recommendation)
Refractory insufficient settling time Boiler fired too soon after renewing
refractory (1 hour drying time for every inch
of refractory thickness)
Wrong selection of refractory type Selection done based on ash acidic value
(refractory type recommendation is given by
manufacturer)
Manufacturing defect Usually occurs within 1 to 5 years from boiler
installation date (if above 5 years disregard
this point)

End of life span Tubes are designed for service life of 20 – 30


years, also depends on thermal cycles. Refer
to boiler manual for thermal cyclic load
number. If boiler age is below 20 years,
disregard this point.