Professional Documents
Culture Documents
92
Gate Valves
SERIES 771H OS&Y GROOVE x GROOVE
SERIES 772H NRS GROOVE x GROOVE
SERIES 771F OS&Y GROOVE x FLANGE
SERIES 772F NRS GROOVE x FLANGE
SERIES 773 WALL POST INDICATOR
SERIES 774 UPRIGHT POST INDICATOR
The Series 771H OS&Y and Series 771F OS&Y gate valves are used when p ositive shut
off is required and a quick visual indicator of open/closed p
osition is required. The Series
772H NRS and Series 772F NRS gate valves are typically used for shut-off service where
the valve is operated remotely, such as when the valve is behind a wall or buried. Series
772H NRS and Series 772F NRS gate valves are offered with optional wall (Series 773) SERIES 771H SERIES 772H
or upright (Series 774) post indicators.
SERIES 774
MATERIAL SPECIFICATIONS Series 771 OS & Y and 772 NRS Gate Valves
Handwheel:
OS & Y Yoke (Series 771 only): Ductile iron conforming to ASTM A-536 grade 65-45-12
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2021 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
REV_G 10.92_1
IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES 10.92
Gate Valves
SERIES 771H OS&Y GROOVE x GROOVE
SERIES 772H NRS GROOVE x GROOVE
SERIES 771F OS&Y GROOVE x FLANGE
SERIES 772F NRS GROOVE x FLANGE
SERIES 773 WALL POST INDICATOR
SERIES 774 UPRIGHT POST INDICATOR
Optional:
• Indicator Post Flange: Ductile iron conforming to ASTM A-536 grade 65-45-12
available for NRS valves only
Window: Polycarbonate
CERTIFICATIONS/LISTINGS
76.1 mm 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa
3 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa
DN80
4 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa
DN100
165.1 mm 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa
6 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa
DN150
8 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa
DN200
10 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa
DN250
12 250 psi/1725 kPa 250 psi/1725 kPa 250 psi/1725 kPa – 250 psi/1725 kPa – 250 psi/1725 kPa –
DN300
14
DN350 250 psi/1725 kPa – 250 psi/1725 kPa – 250 psi/1725 kPa – 250 psi/1725 kPa –
16
DN400 250 psi/1725 kPa – 250 psi/1725 kPa – 250 psi/1725 kPa – 250 psi/1725 kPa –
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2021 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
10.92_2 REV_G
IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES 10.92
Gate Valves
SERIES 771H OS&Y GROOVE x GROOVE
SERIES 772H NRS GROOVE x GROOVE
SERIES 771F OS&Y GROOVE x FLANGE
SERIES 772F NRS GROOVE x FLANGE
SERIES 773 WALL POST INDICATOR
SERIES 774 UPRIGHT POST INDICATOR
DIMENSIONS D
C
C
A
A
SERIES 771H SERIES 772H
D D
B (Open) B (Open)
B (Closed) B (Closed)
B (Open) B (Open)
B (Closed) B (Closed)
C C C C
A A A A
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2021 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
REV_G 10.92_3
IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES 10.92
Gate Valves
SERIES 771H OS&Y GROOVE x GROOVE
SERIES 772H NRS GROOVE x GROOVE
SERIES 771F OS&Y GROOVE x FLANGE
SERIES 772F NRS GROOVE x FLANGE
SERIES 773 WALL POST INDICATOR
SERIES 774 UPRIGHT POST INDICATOR
DIMENSIONS D
details.
C
C
A
SERIES 771F SERIES
A 772F
D D
B (Open) B (Open)
B (Closed) B (Closed)
B (Open) B (Open)
B (Closed) B (Closed)
C C C C
A A A A
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2021 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
10.92_4 REV_G
IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES 10.92
Gate Valves
SERIES 771H OS&Y GROOVE x GROOVE
SERIES 772H NRS GROOVE x GROOVE
SERIES 771F OS&Y GROOVE x FLANGE
SERIES 772F NRS GROOVE x FLANGE
SERIES 773 WALL POST INDICATOR
SERIES 774 UPRIGHT POST INDICATOR
DIMENSIONS
C
B
B
C
Approx.
Dimensions – Inches/millimeters Weight Ea.
Lbs.
Post Indicator A B-min. B-max. kg
14.00 15.54 127.8
Series 773 Wall —
356 394.6 58.0
39.92 21.65 61.42 163.0
Series 774 Upright
1014 550 1560 74.0
C
Nominal Dimension from
Size Centerline to
Inches Top of the Approximate
DN Operating Nut No. of Turns to Open
2 1/2 11.58
9
DN65 298
11.58
76.1 mm 9
298
3 12.92
10
DN80 328
4 14.29
13
DN100 363
6 17.13
16
DN150 453
17.13
165.1 mm 16
453
8 20.83
17
DN200 529
10 24.73
21
DN250 628
12 28.39
26
DN300 721
NOTE: Series 772H and Series 772F NRS Gate Valves must be equipped with
a mounting plate if used with the Series 774 Upright Post Indicator. Contact
Victaulic for details.
Series 773 and Series 774 Post Indicators are intended for use on NRS valves
only.
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2021 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
REV_G 10.92_5
IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES 10.92
Gate Valves
SERIES 771H OS&Y GROOVE x GROOVE
SERIES 772H NRS GROOVE x GROOVE
SERIES 771F OS&Y GROOVE x FLANGE
SERIES 772F NRS GROOVE x FLANGE
SERIES 773 WALL POST INDICATOR
SERIES 774 UPRIGHT POST INDICATOR
DIMENSIONS
Surface
4"/114.3 mm
Steel Pipe
Wall Wall
W
Max.
NOTE: Dimensions given are for standard rod length. Greater distances may be
achieved. Contact Victaulic for details.
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2021 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
10.92_6 REV_G
IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES 10.92
Gate Valves
SERIES 771H OS&Y GROOVE x GROOVE
SERIES 772H NRS GROOVE x GROOVE
SERIES 771F OS&Y GROOVE x FLANGE
SERIES 772F NRS GROOVE x FLANGE
SERIES 773 WALL POST INDICATOR
SERIES 774 UPRIGHT POST INDICATOR
DIMENSIONS
Bury line
W
Bury Depth
Inches
Size mm
Nomial Actual
Size Outside Dia.
Inches Inches
DN mm Minimum Maximum
2 1/2 2.875 31.23 71
DN65 73.0 793 1803
3 3.500 32.57 72.34
DN80 88.9 827 1837
4 4.500 33.94 73.71
DN100 114.3 862 1872
6.500 36.78 76.55
165.1 mm
165.1 934 1944
6 6.625 36.78 76.55
DN150 168.3 934 1944
8 8.625 40.48 80.25
DN200 219.1 1028 2038
10 10.750 44.38 84.15
DN250 273.0 1127 2137
12 12.750 48.04 87.81
DN300 323.9 1220 2230
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2021 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
REV_G 10.92_7
IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES 10.92
Gate Valves
SERIES 771H OS&Y GROOVE x GROOVE
SERIES 772H NRS GROOVE x GROOVE
SERIES 771F OS&Y GROOVE x FLANGE
SERIES 772F NRS GROOVE x FLANGE
SERIES 773 WALL POST INDICATOR
SERIES 774 UPRIGHT POST INDICATOR
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.
WARNING
• Read and understand all instructions before attempting to install any Victaulic
products.
• Always verify that the piping system has been completely depressurized and
drained immediately prior to installation, removal, adjustment, or maintenance of
any Victaulic products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury
and property damage.
• These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable
National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable
building and fire codes. These standards and codes contain important information regarding protection of systems from freezing
temperatures, corrosion, mechanical damage, etc.
• The installer shall understand the use of this product and why it was specified for the particular application.
• The installer shall understand common industry safety standards and potential consequences of improper product installation.
• It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system
and external environment.
• The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level,
and flow rate on materials to confirm system life will be acceptable for the intended service.
Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system
failure, resulting in death or serious personal injury and property damage.
10.92_8