You are on page 1of 5

MADEL ®

we shape the air

AXP Fixed blades swirl diffusers

The AXP series rotational diffusers are designed to be applied in air conditioning, ventilation and heating.

They are mounted in false ceilings or hanging. Their round shape together with the helical design of their
blades causes a rotational diffusion of the air stream, obtaining a high induction index.

With AXP diffusers it is possible to obtain good results in sound pressure in the comfort area. These
diffusers can be used in premises from 2.6 to 4 meters high and a temperature differential up to 12º C.

1 M A D E L V-05/21
AXP CLASSIFICATION
A
C AXP Fixed blades circular swirl diffuser.

AXP-MOD AXP diffuser specially designed to

H
replace a 600x600 false ceiling tile.
E

Ø E A C H AXP-MOD/625 AXP diffuser specially designed to


125 230 192 123 75 replace a 625x625 false ceiling tile.
160 262 227 158 75
200 305 270 198 75 AXP-MOD/675 AXP diffuser specially designed to
250 355 320 248 75 replace a 675x675 false ceiling tile.
315 418 383 313 85

AXP-MOD MATERIAL
C
Diffuser with a nozzle made of spinned aluminium
85

and blades made of stamped aluminium.


All diffusers are provided with a seal on the back of
E
B

the frame in order that the perimeter in contact with


the ceiling is airtight.

MOD / 600 MOD / 625 MOD / 675


C E B E B E B
595 12 620 12 670 15
ACCESSORIES
125 123
160 158 595 12 620 12 670 15
200 198 595 12 620 12 670 15 PLXP Plenum box with a lateral circular
250 248 595 12 620 12 670 15
connection. It includes supports to hang from the
595 12 620 12 670 15
ceiling. Made in galvanised steel.
315 313
…-R Plenum box with a flow damper in the spigot.
…/S/ Plenum box with an upper circular neck
PLXP connector.
F
…/AIS/ Thermally insulated plenum box with foam.
52 Density 30 kg / m3 ISO 845. Thermal conductivity
20º C_0,040 W / mºK ISO 3386/1. Classified
reaction to fire B-s2, d0 EN 13501-1.
D1
Z

D2

D2 F Z D1
125 125 200 150 98
160 160 250 175 123
200 200 300 220 158
250 250 380 270 198
315 315 480 335 248

2 M A D E L V-05/21
FIXING SYSTEMS

1) Connection into a circular metallic duct by


means of rivets.
1)

P) Connection into the crossbar or to the plenum


box by means of central screw.

FINISHES

M9016 Painted white similar to RAL 9016


(85-95% gloss)
R9016S Painted white RAL 9016 semi-matt
(60-70% gloss)
R9010S Painted white RAL 9010 semi-matt
(60-70% gloss)
P) M9066 Painted grey similar to RAL 9006
(85-95% gloss)
RAL... Painted in other RAL colours

SPECIFICATION TEXT

Supply and mounting of circular swirl diffuser with


fixed blades series AXP+PLXP-R M9016 dim. 125
constructed from aluminium paint in white M9016.
With lateral circular connection plenum box and air
flow damper in the spigot PLXP-R.
Manufacturer MADEL.

3 M A D E L V-05/21
RECOMMENDED VELOCITY.
FREE VELOCITY, PRESSURE LOSS AND SOUND POWER LEVEL,
Vmin Vmax THROW WITH CEILING EFFECT.
AXP m/s m/s AXP + PLXP
125 2.5 6,2 3
Q ( m / h)
160 2.5 6.7 1200
50 100 150 200 300 400 500 700 1000 1500 2000
5.6

Vf ( m / s)
200 2.5 10
9 5 0 0 0 5
250 2.5 5,6 8 12 16 20 25 31
315 2.5 4.2 7
6
5

4
FREE FACE AREA (m2).
3

Ak Afree Qmin. Qmax.


AXP m2 m3/h m3/h
m2 2
125 0.012 0.006 55 135
160 0.015 0.009 80 220

200 0.028 0.0133 120 270


1
250 0.045 0.0192 175 390 150
( Pa )

0
0
5

5
0

25
20
12

100

31
16
315 0.066 0.0384 345 590
75
50
Dpt

A) 45
CORRECTION FACTOR FOR DPt AND Lwa1.
40

(d 4 0
)
30

B(
a1 35
100% 50% 10% 20
PLXP-R
=
Open Open Open
30

15
Lw

Dpt (Kp) 1 1.2 2


25

125 10
Lwa1 (Kf) +0,6 +1,6 +0,8
160 Dpt (Kp) 1 1.1 2.1
5
Lwa1 (Kf) +0,7 +1,7 +0,9
Dpt (Kp) 1 1.3 1.9
200
Lwa1 (Kf) +0 +0 +0,3
10
AL 0,3 (m)
AL 0,5 (m)

AL 0,2 (m)

Dpt (Kp) 1 1.4 2,1 4 6.6 0


5 0 0 5
250
Lwa1 (Kf) +0 +0 +0
3.6 6 9 12 16 20 25 31
3.2 5.3 8
Dpt (Kp) 1 1.2 1,8 2.8 4.6 7
315 6
Lwa1 (Kf) +0,7 +1,7 +0,9 2.4 4
2 3.3 5

DPt1 = Kp x DPt 1.6 2.6 4

Lwa = Lwa1 + Kf 1.2 2 3

A B B C
0.8 1.3 2
H

0.4 0.6 1
50 100 150 200 300 400 500 700 1000 1500 2000
1,8

1200
3
Q (m / h)

AL 0.2 = A
AL0.2 = B+H
AL 0.2= C+H

4 M A D E L V-05/21
CORRECTION FACTOR FOR
VERTICAL DIFFUSION (bV) CORRECTON FACTOR FOR
FOR DT (-). THROW (L0.2) DT (-).
0 0
D t ( C) D t ( C)
-10 -10

-5 -5

0 0
0.02 .03 .04 .05 .06 .07 0.1 0.14 1 0.95 0.9 0.85 0.8 0.75
Kh Kl

Kh = Correction factor for the vertical diffusion. Kl = Correction factor for the throw.

AL 0.2 bv = Kh x Al 0.2
bv

AL´ 0.2 ( Dt <0 ) = Kl x AL 0.2

TEMPERATURE RATIO. INDUCTION RATIO.

Dtl = t room - t x Qr Q total at x


i = =
Dtz t room - t supply Q 0 Q of supply.
5 0 0 0 5
31 25 20 16 12

0.15 150
100
0.1 90
80
70
0.08 60
50
0.06 40
0.05 30
0.04 20
0.03 15
31
5 10
12
0.02 5 8
16 20 25
0 0 0 6
0.015 5
1 1.5 2 2.5 3 4 5 6 7 8 9 10 1 1.5 2 2.5 3 4 5 6 7 8 9 10
AL 0.2 (m) AL 0.2 (m)